Jøtul GF 370 DV MV Скачать руководство пользователя страница 15

15

130102- 1   GF 370 DV MV   2/22

Figure 7.3.  Pressure test points located on the front of the 

valve.

Manifold

Inlet 

Pilot Adjustment

E

A

Figure 7.2. Gas supply valve types and fittings.

 

 









Soap Solution Leak Test

•  Mix a 50-50 solution of water and dish soap.
•  Light appliance - see lighting instructions on the back 

cover of this manual or on the rating plate.

•  Brush or spray all joints and connections with the soapy 

water solution.

•  If bubbles appear at any connection or seam or a gas 

odor is detected, immediately turn gas control knob to 

the OFF position.  

Tighten or reconnect the leaking joint and retest for any 

gas leaks.

The line must be disconnected from the gas supply line 

by closing the main supply manual gas shut-off valve (gas 

cock) during any pressure testing of the gas supply piping 

system that is equal to or exceeds pressures of 1/2 psig (3.5 

kPa).

4. Testing Gas Pressure

Proper gas pressure provides a consistent flow of gas to 

the appliance and is instrumental in checking for gas leaks. 

There are two pressure test points on the front of the stove 

control valve where test gauge connections are made. See 

Fig. 7.3.  Gauge connections are identified by:
•  E  for inlet or supply pressure ( the amount of gas com-

ing to the valve.)

•  A  for manifold pressure (the amount of gas that is com-

ing out of the valve to the burner.)

WARNING

DO NOT ALLOW THE INLET GAS PRES-

SURE TO EXCEED 14.0” WC (OR 1/2 PSIG) 

AS SERIOUS DAMAGE TO THE VALVE MAY 

RESULT.

NEVER USE AN OPEN FLAME TO CHECK FOR 

GAS LEAKS.

ALWAYS REFER TO THE LIGHTING INSTRUC-

TIONS ON THE INSIDE BACK COVER OF THIS 

MANUAL WHEN LIGHTING THE STOVE.

Inlet Pressure

 

                          MIN    MAX 

    Natural Gas:   5.0 WC  (1.24 kPa)        7.0 WC  (1.74 kPa)

    Propane:       12.0 WC  (2.99 kPa)      14.0 WC (3.48 

kPa)

Manifold Pressure

 

                          MIN    MAX 

    Natural Gas:   1.6 WC  (0.398 kPa)       3.5 WC  (.87 kPa)

    Propane:         6.4 WC  (1.59 kPa)     10.0 WC  (2.48 kPa)

ALWAYS TEST PRESSURES WITH VALVE REGULA-

TOR CONTROL AT THE HIGHEST SETTING. 

Symptoms of incorrect gas pressure include:

Insufficient gas pressure:  

•  Small pilot flame which can result in insufficient milli-

volts.  

•  Little variation in flame picture between HI and LO 

regulator settings.

•  Insufficient gas to support more than one appliance caus-

ing nuisance outages or gas surges.

Excessive gas pressure:

•  Permanent damage to valve causing complete appliance 

shut down.

•  Too large a pilot flame resulting in overheating of the 

power generator and consequent shut down.

•  Sooting due to impingement and/or incorrect fuel to air 

mix.

Содержание GF 370 DV MV

Страница 1: ...ll be installed in the same room as the appliance WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or los...

Страница 2: ...rvice External regulator for Propane only Piping that complies with local code Manual shut off valve T Handle valve may be required in Massachusetts Sediment trap if required by code Tee joint Pipe wr...

Страница 3: ...9 12 Lighting Instructions 31 Unpacking the Stove 1 Before beginning the installation inspect the stove for shipping damage and immediately report any evidence of damage to your dealer 2 Confirm stove...

Страница 4: ...th America Gorham Maine USA J tul AS Fredrikstad Norway Test Standards This appliance complies with National Safety standards and is tested and listed by Intertek Testing Services of Middleton Wiscons...

Страница 5: ...cal codes This appliance is only for use with the type s of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used 4 The installati...

Страница 6: ...appliance Clothing or other flammable materials should not be placed on or near the fireplace Never allow anyone to use the fireplace if they are unfamiliar with its operation NEVER store or use gaso...

Страница 7: ...S Comply with CSA Z240 4 Gas Equipped Recreational Vehicles and Mobile Housing in Canada 3 Always contact your local officials about installation restrictions and requirements in your area THIS APPLI...

Страница 8: ...imney components supplied by the following manufacturers M G DuraVent Inc Direct Vent Pro Series P O Box 1510 Vacaville CA 95696 1510 800 835 4429 Selkirk Corporation 1301 W President George Bush Hwy...

Страница 9: ...entsuppliers A maximum of two 90 or four 45 elbows may be used in a vertical termination Whenever possible use 45 elbows instead of 90 elbows as they offer less restriction to the flow of flue gases a...

Страница 10: ...0 square hole is adequate for proper pipe clearance through a wall provided the vent is positioned to maintain 2 minimum clearance at the top A 1 minimum clearance must be maintained to combustible ma...

Страница 11: ...onmechanical air supply inlet to building or the combustion air inlet to any other appliance 12 in 30 cm 9 in 23 cm K Clearance to a mechanical air supply inlet 6 ft 1 83 m 3 ft 91 cm above if within...

Страница 12: ...adjustments 3 Tighten the locking screw and replace the Trim Rings Vent Restriction Adjustments The J tul GF 370 DV MV features adjustment controls for both intake air and exhaust to accommodate a va...

Страница 13: ...these offer less restriction to the flow of flue gases and intake air Reduce the overall horizontal run by 5 feet for each additional 45 and 90 elbow When two or more elbows are used in a horizontal...

Страница 14: ...MASSACHUSETTS The stove and gas control valve must be disconnected from the gas supply piping during any pressure testing of the system at test pressures in excess of 1 2 psig For pressures lower tha...

Страница 15: ...g 7 3 Gauge connections are identified by E for inlet or supply pressure the amount of gas com ing to the valve A for manifold pressure the amount of gas that is com ing out of the valve to the burner...

Страница 16: ...nd wrench or deep well socket to remove the burner orifice from the brass orifice holder Replace with the orifice supplied in the kit CAUTION Do NOT over tighten the Burner Injector Over tightening ca...

Страница 17: ...dentificationlabelstothestovesothattheycanbeseen byanypersonthatmaybeservicingthestove Label A Applytofrontlipofthevalvecompartment Label B Apply to the Rating Plate Small valve sticker Apply to valve...

Страница 18: ...d on pages 21 22 Figure 7 8 High Altitude Conversion Label This appliance has been converted for use at an altitude of___________ Orifice Size __________ Manifold Press _______ Input Btu Hr _________...

Страница 19: ...pilot ignition See figs 7 16 and 10 3 for examples StarFire Glass Embers Do not use more than the four pounds in two 2 lb bags of glass media provided For best results evenly spread the contents of th...

Страница 20: ...Lean the Right Log up against the upper right corner of the firebox and engage the slot on the tip with the pin on the Bottom Log Figure 7 16 Evenly disperse the Ember Stones over the burner plate ar...

Страница 21: ...bottom of Rear Log 2 with the two steel pins B at the left rear corner of the burner plate 5 Engage the two holes in the bottom of the Center Log 3 with the two burner plate pins C 6 Engage the holes...

Страница 22: ...monia based glass cleaner 2 Hold the glass frame to firebox front with holes in align ment where socket head screws were removed 3 Replace the socket head screws into glass frame finger tight Readjust...

Страница 23: ...oting in the Ceramic Burner Guide if greater than 4 seconds Reinstall the glass frame prior to hot start testing C Hot Start After the burner has been on for 5 10 minutes turn it off and wait 2 minute...

Страница 24: ...source for the thermostat At the thermostat the two wires should be connected to the two connection screws on the thermostat base plate per the manufacturer s instructions CAUTION LABEL ALL WIRES PRIO...

Страница 25: ...and the area under the appliance free of dust Always keep the appliance area clear and free from combustible materials gasoline and other flammable liquids 4 This appliance is operated with a continu...

Страница 26: ...e assembly upside down on a flat surface protecting the frame from scratches using a blanket or towel 3 The glass panel is held in place by four retainer tabs Use a screwdriver to carefully pry these...

Страница 27: ...er GF 370 MB 38 225402 Outer Rod Exhaust Restrictor 39 223224 Skamol Rear Panel 40 223235 Skamol Side Panel 2 not illustrated No Part Number Description 1 9911 Bolt Hex Cap M6x45 DIN 933 Class 8 8 Blk...

Страница 28: ...or Catch GF 370 Matte Black 21 156843 Lower Door Hinge Asy GF 370 MB 22 156835 Replacement Outer Side Glass GF 370 25 223220 Plate Centering GF 370 Figure 11 2 External parts identification 27 2255849...

Страница 29: ...29 130102 1 GF 370 DV MV 2 22 Figure 11 3 GF 370 DV MV Spud assembly parts identification...

Страница 30: ...lock 25 117922 Nut Hex M4 DIN 934 Plain 26 3902576 Igniter Bracket 27 3902573 Piezo Ignitor Button 28 117920 Screw Pan Head Phillips M4 X 8 29 224799 Switch Plate GF 373 30 225631 Valve Bracket GF 373...

Страница 31: ...31 130102 1 GF 370 DV MV 2 22 This Page is intentionally left blank...

Страница 32: ...32 130102 1 GF 370 DV MV 2 22 This Page is intentionally left blank...

Страница 33: ...ge due to incorrect installations not in conformance with the installation instructions contained in this owner s manual or local and or national fire and building regulations 3 Damage due to service...

Страница 34: ...________________________ PHONE ____________________________________ INSTALLER __________________________________ FUEL TYPE ____________________________________ FUEL CONVERSION NO _______ YES_____ NOTE...

Страница 35: ...INSTRUCTIONS WARNING IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE A This appliance has a pilot which must be l...

Страница 36: ...s appliance must be installed in conformance with local and national building regulations Before beginning the installation it is important that the these instructions be carefully read and understood...

Отзывы: