background image

F 500 V3 Oslo   4 / 20

5

      Any of the preceding conditions can adversely 

affect performance.  Weak or erratic draft can cause 

“backpuffing”- a condition when smoke leaks into the 

room through the stove or chimney connector joints. 

Poor draft will also make it difficult to maintain a steady, 

controlled burn and lead to creosote accumulation in the 

chimney or combustor. 

 

A short, masonry chimney on the exterior of a 

house will promote poor performance.  This is because 

it will be difficult to initiate and maintain temperatures 

warm enough to sustain adequate draft.  In extremely 

cold northern areas, it may be necessary to reline 

the chimney or extend its height to help improve 

performance. Conversely, a tall, masonry chimney inside 

the house will warm more quickly and retain heat 

longer.

     On the other hand, overly strong draft can also cause a 

different set of issues such as excessive temperatures and 

short burn times 

     Ideally, whether masonry or prefabricated, the chimney 

should be centrally located  inside the house where it will 

be least affected by exterior conditions and the stove’s 

radiant heat can be most evenly dispersed.

The following guidelines give the necessary chimney 

requirements based on the national code, ANSI-NFPA 211. 

However, many local codes differ from the national code 

to take into account climate, altitude, or other factors. 

NOTE:

 

Consult your local code authority to 

determine what building and fire codes apply in 

your area before installing your new stove.    Your 

local inspector has final authority in approving your 

installation.

2.3 Masonry Chimneys

A masonry chimney must conform to the following 

guidelines:

•   The chimney flue size should not be less than the 

cross-sectional area of the stove flue collar.

•   The cross-sectional area of the flue of a chimney with 

no walls exposed to the outside below the roofline 

shall not be more than three times the cross-sectional 

area of the stove flue collar.

•   The cross-sectional area of a chimney flue having 

one or more walls exposed to the outside below the 

roofline shall not be more than two times the cross-

sectional area of the stove flue collar.

•   Larger chimney flues should be relined with a listed 

or code approved liner.

•  The masonry chimney must have a fireclay liner or 

equivalent, with a minimum thickness of 5/8” (16mm) 

and must be installed with refractory mortar. There 

must be at least 1/4” (6,35mm) air space between the 

flue liner and chimney wall.  

•  The fireclay flue liner must have a nominal size of 8” 

X 8”, and should not be larger than 8” X 12”. If a round 

fireclay liner is to be used it must have a minimum 

inside diameter of 6” (157mm) and not larger than 8” 

(208mm) in diameter. 

•  If a chimney with larger dimensions is to be used, it 

should be relined with an appropriate liner that is 

code approved.

•  The masonry wall of the chimney, if brick or modular 

block, must be a minimum of 4”(106mm) nominal 

thickness. A mountain or rubble stone wall must be at 

least 12” (310mm) thick.

•  A newly-built chimney must conform to local codes and 

in their absence must recognize national regulations. 

When using an existing chimney, it must be inspected 

by a licensed professional chimney sweep, fire official, 

or code officer, to ensure that the chimney is in proper 

working order.

•  No other appliance can be vented into the same flue.
•  An airtight clean-out door should be located at the base 

of the chimney.

2.4 Prefabricated Chimneys

A prefabricated metal chimney must be tested and 

listed  for use with solid fuel burning appliances to High 
Temperature (HT) Chimney Standard UL 103 for the U.S. 

The manufacturer’s installation instructions must 

be followed precisely. Always maintain the proper 

clearance to combustibles as established by the pipe 

manufacturer.  This clearance is usually a minimum of 

2” (56mm), although it may vary by manufacturer or for 

certain chimney components.

2.5 Chimney Height

The minimum chimney height is 15 feet (4.57 m). The 

chimney must also be at least 3 feet higher than the 

highest point where it passes through the roof and at 

least 2 feet higher than the highest part of the roof or 

structure that is within 10 feet of the chimney, measured 

horizontally. See figure 3.

Chimneys shorter than 14 feet may not provide 

adequate draft. This could result in smoke spilling into 

the room from the stove when loading the stove, or 

when the door is open. In addition, inadequate draft can 

cause back puffing, which is a build up of gases inside 

the firebox.  

Содержание Classic F 500 V3

Страница 1: ...make them available to anyone using or servicing this wood heater This wood heater contains a catalytic combustor that requires periodic inspection and repair for proper operation See this manual for...

Страница 2: ...tove Inspection 13 6 2 Ash Removal 13 6 3 Chimney System 13 6 4 Enamel Care 13 6 5 Glass Care Glass Replacement 14 6 6 Gaskets 14 7 Accessories 15 8 Illustrations Figures 16 21 Clearance Chart and Dia...

Страница 3: ...NDING WHEN ADDING FUEL Avoid creating a low pressure condition in the room where the stove is operating Be aware that operation of an exhaust fan or clothes dryer can create a low pressure area and co...

Страница 4: ...ws The maximum horizontal run is 36 915mm and a recommended total length of stove pipe should not exceed 10 feet Horizontal runs must slope upward 1 4 6 35mm per foot toward the chimney Where passage...

Страница 5: ...collar Larger chimney flues should be relined with a listed or code approved liner The masonry chimney must have a fireclay liner or equivalent with a minimum thickness of 5 8 16mm and must be instal...

Страница 6: ...be installed to resize the flue The fireplace installation must also conform to the tested clearances to surrounding trim and mantels See clearance specifications on pages 22 23 In addition a fireplac...

Страница 7: ...50 5 deep 1168mmx1283mm can be used only if the left side door is locked to prevent use Door Lock Kit 155850 is available for this purpose from your dealer 4 2 Clearances to Walls and Ceilings The fo...

Страница 8: ...ned 2 All chimney components including chimney sections supports spark arrestor etc shall comply with the Standard for Factory built Chimneys for Residential Type and Building Heating Appliances UL 10...

Страница 9: ...as the stove The monitor should be located as far away as possible from the stove to avoid alerts when the doors are opened 5 3 Wood Fuel and Performance Use dry wood The F 500 V3 is designed to burn...

Страница 10: ...d into the atomosphere When the combustor is functioning no smoke will be observed exiting the chimney This is evidence that the stove is operating in the so called sweet spot wherein optimum efficien...

Страница 11: ...or the most efficient burn is between 400 and 600 204 C 316 C 2 Take the magnet off of thermometer and replace into the correct orientation as shown in fig 13c 13e 3 Place the thermometer fully into h...

Страница 12: ...full open position far right To minimize any smoke spillage open the door slightly before opening fully This will allow air flow to stabilize within the firebox and chimney flue Use a stove tool or po...

Страница 13: ...h to empty the drawer and then securely closed Inspect the gasket on the ash pan door regularly and replace as necessary 6 Maintenance See Appendix A page 24 for Combustor Maintenance and Replacement...

Страница 14: ...pattern as you would tighten the lugs on an automobile wheel 6 6 Gaskets Check door and glass panel gaskets for tightness To check the seal of the front door close and latch the door on a dollar bill...

Страница 15: ...ed with Rear Heat Shield 154332 not included Outside Air Kit 154335 Provision for outside air may be required by your local building codes The outside air kit includes a 3 inch adapter used to connect...

Страница 16: ...F 500 V3 Oslo 4 20 16 Fig 1a Fig 1b Fig 4 Masonry chimney penetration Fig 3 Chimney height 3 2 10 Rule Fig 2 Chimney connector assembly 8 Illustrations Fig 5 Chimney thimble components 24 3 4 629mm...

Страница 17: ...ns 2 50 mm Min width 50 5 1283mm Min width 56 1422 mm 18 460 mm 8 200 mm 8 200 mm 18 460 mm Min depth 50 1 2 1283 mm Min width 54 1 4 1378 mm Fig 6 Fireplace chimney construction Fig 7 Prefabricated c...

Страница 18: ...ature Monitor FULLY CLOSED FAR LEFT FULLY OPEN FAR RIGHT Combustion Monito r DO NOT REMOVE THIS SET SCREW Fig 13b Fig 13c Removemagnetfromcurrentorientation Fig 13d Orient magnet Incorrect Orientation...

Страница 19: ...e bottom 1 Bend the flattened heat shield on the perforations as shown painted side down 2 Use a 10 mm wrench to remove the two bolts from the bottom of the ash compartment Unpainted Side Up Fig 16 Bo...

Страница 20: ...F 500 V3 Oslo 4 20 20 F 500 V3 Illustrated Parts Breakdown Purchase replacement parts only from a J tul Authorized dealer...

Страница 21: ...le Cast Straight 10243892 31 Spring Door Handle 126164 32 Coiled Spring Pin 5x24 118070 33 Washer Door Handle 117587 34 Gasket Round LD2 375 Graphite 225695 35 Insulation Blanket Burn Plates 128903 36...

Страница 22: ...e Protected surface Single wall pipe 18 460mm 12 300mm Double wall pipe 6 150mm 6 150mm Fireplace Mantle and Trim Clearance no shielding reduction permitted Stove Side to Side Trim 1 thick or less 12...

Страница 23: ...ce Parallel to the Wall Unprotected Surface Corner Installation Protected Surface Corner Installation E F A G C F A G F A D F D D D B F F F F D A D F D D D F D D PER NFPA 211 or CAN CSA B365 Important...

Страница 24: ...periodically monitor the operation of the catalytic combustor to ensure that it is functioning properly and to determine when it needs to be replaced A non functioning combustor will result a loss of...

Страница 25: ...nd the front plate inside the stove as in fig 19 2 Use the 3mm hex key to remove the two M6x40 set screws on the left and right sides See fig 20 2 Wearing gloves grasp each side and lift the front of...

Страница 26: ...F 500 V3 Oslo 4 20 26 Fig 24 Left and Right Side insulation panel removal and replacement Fig 23 Lift combustor from the chamber Expansion gasket RRefactory member...

Страница 27: ...lue 3 If the overall R value of the system is greater than the R value of the specified floor protector the alternate is acceptable Example The specified floor protector should be 3 4 thick material w...

Страница 28: ...sions and Limitations Notice This warranty is void if installation or service is performed by someone other than an authorized installer or service agency or if installation is not in conformance with...

Страница 29: ...EASONABLY COULD HAVE BEEN DISCOVERED This warranty is given by J tul North America Inc 55 Hutcherson Drive Gorham Maine 04038 USA Return to Applied Ceramics Customer Service Department 5555 Pleasantda...

Страница 30: ...eplacement STEEL COMBUSTOR fails to function the prorated warranty will allow replacement at the following special price schedule Year 3 130 00 Year 4 140 00 Year 5 150 00 Year 6 160 00 Year 7 and aft...

Страница 31: ...F 500 V3 Oslo 4 20 31 This page is intentionally left blank...

Страница 32: ...box 1411 N 1602 Fredrikstad Norway www jotul us 139946_R10 April 2020 For Your Records Record the following information to help your dealer determine what you will need should your stove ever require...

Отзывы: