background image

F 500 V3 Oslo   4 / 20

11

2.  Light a second fire, allowing the stove to reach a maximum 

temperature of 400°F (204°C) for 1 hour.

3.  Cool the stove to room temperature.
4.  Light a third fire and gradually allow the stove to reach 

and maintain a surface temperature of 500°F (260°C).

5.  Cool stove to room temperature. This completes the 

“break-in” procedure.

NOTE: Keep the stove under 400°F (204°C) surface 

temperature during any “break-in fire”, with the 

exception of the last “break-in” fire.  If the temperature 

exceeds 400°F, move the primary air control lever all the 

way to the left to minimize the air supply. It is normal for 

the stove top temperature will continue to climb until 

the fuel burns down somewhat. Once the fire is out and 

the stove has cooled to room temperature, continue 

the break-in procedure. Never attempt to reduce the 

temperature by removing burning logs from the fire.

5.7 Starting and Maintaining a Fire

Burn only solid wood directly on the bottom grate of the 

stove. Do not elevate the fire in any way.

WARNING: THE ASH PAN DOOR MUST ALWAYS BE 

SECURELY CLOSED WHEN THE STOVE IS IN BURNING. 

OPERATING THE STOVE WITH THE ASH DOOR OPEN WILL 

PROMOTE UNEVEN THERMAL EXPANSION AND CAN 

RESULT IN DAMAGE TO THE STOVE AND VOID YOUR 

WARRANTY.

Traditional Fire Building  

1.  Set the primary air control lever in the full open 

position (to the right). Place several sheets of 

crumpled newspaper placed directly on the grate. On 

top of the newspaper, place several pieces of small 

dry kindling (approx. 1” in diameter) with two to three 

small logs (approx. 3” to 5” in diameter) on top.  

2.  Light the fire and close the door, slowly building the 

fire by adding larger and larger logs. Be sure to follow 

the break-in procedure before creating a hot fire that 
could damage the stove.  

3.  Once the stove has reached a temperature range of 

between 500° and 600°, (260°C -316°C), adjust the 

primary air control lever as necessary to generate the 

heat output and burn time desired.  

   You can also use a stove top thermometer to monitor 

the surface temperature of the stove. The optimum 

surface temperature range for the most efficient burn 
is between 400° and 600° (204°C -316°C).   

2.  Take the magnet off of thermometer and replace into the 

correct orientation as shown in fig. 13

c-13e. 

3.   

Place the thermometer fully into hole with magnet to cast 

as shown in figs. 13b . 

Seated within the right side directly behind the 

catalytic element, the thermometer accurately reports 

combustion activity.  Secondary combustion takes place at 

temperatures between 500°F (260°C) and 1200°F   

(260°C - 649°C). 

 

The primary air valve should remain at the fully 

open setting, (to the Right), at least until the monitor 

registers 500°F (260°C).  Maintain that temperature for 

15-20 minutes before adjusting the primary air lever 

to Medium Low - Medium High settings. The optimum 

temperature range for most efficient combustion is 

between 500°F and 800° (260°C -371°C).  Chimney draft 

should be in the .05 - 1.0 w.c. range. The so-called “sweet 

spot” combustion zone is best maintained at those 

temperatures.

Visual Monitoring

 

Evidence of efficient combustion can be observed in 

three distinct ways: 

1.    At temperatures over 500° F, look up through the  

 

door glass to the steel baffle and catalytic element at  

 

the top of the firebox. As exhaust gases ignite, jets of  

 

flame can be seen projecting from the baffle ports  

 

and the catalyst will glow vividly red. 

2.  Little or no smoke will be seen flowing from the  

 

chimney flue outside of the house. 

3.  If the stove has been properly operated, brushing  

 

the chimney flue will produce mostly fly ash. Little or  

 

no creosote accummulation will be evident.  

See appendix A for more information regarding combustor 
performance.

5.6 Stove Break-In Procedure

The Jøtul F 500 V3 is constructed of cast iron plates 

and sealed with stove furnace cement.  Cast iron, while 

very durable, expands and contracts as it is heated and 

cooled. This type of construction requires the stove to 

be “broken-in” gradually so that thermal expansion 

does not occur too quickly. this process is accomplished 

by burning a short  series of small-to-medium fires as 

described below.

1.   Fully open the primary air valve. Light a small fire of 

newspaper and kindling. Only allow the stove monitor to 

reach a temperature of 200°F (93° C). Maintain the fire at 

that level for approximately 1 hour and allow the stove to 

cool to room temperature.

Содержание Classic F 500 V3

Страница 1: ...make them available to anyone using or servicing this wood heater This wood heater contains a catalytic combustor that requires periodic inspection and repair for proper operation See this manual for...

Страница 2: ...tove Inspection 13 6 2 Ash Removal 13 6 3 Chimney System 13 6 4 Enamel Care 13 6 5 Glass Care Glass Replacement 14 6 6 Gaskets 14 7 Accessories 15 8 Illustrations Figures 16 21 Clearance Chart and Dia...

Страница 3: ...NDING WHEN ADDING FUEL Avoid creating a low pressure condition in the room where the stove is operating Be aware that operation of an exhaust fan or clothes dryer can create a low pressure area and co...

Страница 4: ...ws The maximum horizontal run is 36 915mm and a recommended total length of stove pipe should not exceed 10 feet Horizontal runs must slope upward 1 4 6 35mm per foot toward the chimney Where passage...

Страница 5: ...collar Larger chimney flues should be relined with a listed or code approved liner The masonry chimney must have a fireclay liner or equivalent with a minimum thickness of 5 8 16mm and must be instal...

Страница 6: ...be installed to resize the flue The fireplace installation must also conform to the tested clearances to surrounding trim and mantels See clearance specifications on pages 22 23 In addition a fireplac...

Страница 7: ...50 5 deep 1168mmx1283mm can be used only if the left side door is locked to prevent use Door Lock Kit 155850 is available for this purpose from your dealer 4 2 Clearances to Walls and Ceilings The fo...

Страница 8: ...ned 2 All chimney components including chimney sections supports spark arrestor etc shall comply with the Standard for Factory built Chimneys for Residential Type and Building Heating Appliances UL 10...

Страница 9: ...as the stove The monitor should be located as far away as possible from the stove to avoid alerts when the doors are opened 5 3 Wood Fuel and Performance Use dry wood The F 500 V3 is designed to burn...

Страница 10: ...d into the atomosphere When the combustor is functioning no smoke will be observed exiting the chimney This is evidence that the stove is operating in the so called sweet spot wherein optimum efficien...

Страница 11: ...or the most efficient burn is between 400 and 600 204 C 316 C 2 Take the magnet off of thermometer and replace into the correct orientation as shown in fig 13c 13e 3 Place the thermometer fully into h...

Страница 12: ...full open position far right To minimize any smoke spillage open the door slightly before opening fully This will allow air flow to stabilize within the firebox and chimney flue Use a stove tool or po...

Страница 13: ...h to empty the drawer and then securely closed Inspect the gasket on the ash pan door regularly and replace as necessary 6 Maintenance See Appendix A page 24 for Combustor Maintenance and Replacement...

Страница 14: ...pattern as you would tighten the lugs on an automobile wheel 6 6 Gaskets Check door and glass panel gaskets for tightness To check the seal of the front door close and latch the door on a dollar bill...

Страница 15: ...ed with Rear Heat Shield 154332 not included Outside Air Kit 154335 Provision for outside air may be required by your local building codes The outside air kit includes a 3 inch adapter used to connect...

Страница 16: ...F 500 V3 Oslo 4 20 16 Fig 1a Fig 1b Fig 4 Masonry chimney penetration Fig 3 Chimney height 3 2 10 Rule Fig 2 Chimney connector assembly 8 Illustrations Fig 5 Chimney thimble components 24 3 4 629mm...

Страница 17: ...ns 2 50 mm Min width 50 5 1283mm Min width 56 1422 mm 18 460 mm 8 200 mm 8 200 mm 18 460 mm Min depth 50 1 2 1283 mm Min width 54 1 4 1378 mm Fig 6 Fireplace chimney construction Fig 7 Prefabricated c...

Страница 18: ...ature Monitor FULLY CLOSED FAR LEFT FULLY OPEN FAR RIGHT Combustion Monito r DO NOT REMOVE THIS SET SCREW Fig 13b Fig 13c Removemagnetfromcurrentorientation Fig 13d Orient magnet Incorrect Orientation...

Страница 19: ...e bottom 1 Bend the flattened heat shield on the perforations as shown painted side down 2 Use a 10 mm wrench to remove the two bolts from the bottom of the ash compartment Unpainted Side Up Fig 16 Bo...

Страница 20: ...F 500 V3 Oslo 4 20 20 F 500 V3 Illustrated Parts Breakdown Purchase replacement parts only from a J tul Authorized dealer...

Страница 21: ...le Cast Straight 10243892 31 Spring Door Handle 126164 32 Coiled Spring Pin 5x24 118070 33 Washer Door Handle 117587 34 Gasket Round LD2 375 Graphite 225695 35 Insulation Blanket Burn Plates 128903 36...

Страница 22: ...e Protected surface Single wall pipe 18 460mm 12 300mm Double wall pipe 6 150mm 6 150mm Fireplace Mantle and Trim Clearance no shielding reduction permitted Stove Side to Side Trim 1 thick or less 12...

Страница 23: ...ce Parallel to the Wall Unprotected Surface Corner Installation Protected Surface Corner Installation E F A G C F A G F A D F D D D B F F F F D A D F D D D F D D PER NFPA 211 or CAN CSA B365 Important...

Страница 24: ...periodically monitor the operation of the catalytic combustor to ensure that it is functioning properly and to determine when it needs to be replaced A non functioning combustor will result a loss of...

Страница 25: ...nd the front plate inside the stove as in fig 19 2 Use the 3mm hex key to remove the two M6x40 set screws on the left and right sides See fig 20 2 Wearing gloves grasp each side and lift the front of...

Страница 26: ...F 500 V3 Oslo 4 20 26 Fig 24 Left and Right Side insulation panel removal and replacement Fig 23 Lift combustor from the chamber Expansion gasket RRefactory member...

Страница 27: ...lue 3 If the overall R value of the system is greater than the R value of the specified floor protector the alternate is acceptable Example The specified floor protector should be 3 4 thick material w...

Страница 28: ...sions and Limitations Notice This warranty is void if installation or service is performed by someone other than an authorized installer or service agency or if installation is not in conformance with...

Страница 29: ...EASONABLY COULD HAVE BEEN DISCOVERED This warranty is given by J tul North America Inc 55 Hutcherson Drive Gorham Maine 04038 USA Return to Applied Ceramics Customer Service Department 5555 Pleasantda...

Страница 30: ...eplacement STEEL COMBUSTOR fails to function the prorated warranty will allow replacement at the following special price schedule Year 3 130 00 Year 4 140 00 Year 5 150 00 Year 6 160 00 Year 7 and aft...

Страница 31: ...F 500 V3 Oslo 4 20 31 This page is intentionally left blank...

Страница 32: ...box 1411 N 1602 Fredrikstad Norway www jotul us 139946_R10 April 2020 For Your Records Record the following information to help your dealer determine what you will need should your stove ever require...

Отзывы: