3.3 Prefabricated Chimneys

The Jøtul F 500 V3 may be connected to a prefabricated 

metal chimney following the pipe manufacture’s 

instructions. Use all required components.  Most 

manufacturers offer an adaptor that attaches to the 

bottom section of the metal chimney and permits the 

connector pipe to be secured to it using three sheet metal 

screws. See figure 7.

4. Clearances to Combustibles

4.1 Floor Protection Requirements

The F 500 V3 requires floor protection as specified 
below in any installation unless installed on concrete 
over earth. 

*  The supplied bottom heat shield must be installed on 

the stove.

•  Floor protection under the stove must be composed of 

continuous, non-combustible materials for protection 

against sparks and embers.  

*  Individual sections of floor protection must be 

mortared or otherwise sealed together to prevent 

spark penetration to combustibe floor materials. Any 

carpeting must be removed from under the floor 

protection.

•  Alcove Installations: In addition to the Bottom Heat 

Shield, floor protection must include materials having 

a minimum R-value of 1.6. See Appendix B, page 27, to 

determine various material R-values.

 

The hearth protection surface must extend continuously:
•  A minimum of 18” (457mm) in front of the stove and from 

the left side load door (measured from the door opening).

•  8” (200mm) on the right side and back of the stove 

(measured from side and back panels).

This will result in a minimum floor protection of 
  54.25”W X 50,5”D (1378mm x 1283mm).  See figure 8.
For a rear vent installation, the floor protection must also 

extend under the stove pipe a minimum of 2” (50mm) 

beyond either side of the pipe. Fig. 8.

Alternate Hearth Protection

 

A hearth pad measuring 46”wide X 50,5” deep 

(1168mmx1283mm)  can be used only if the left side 

door is locked to prevent use. Door Lock Kit #155850 is 

available for this purpose from your dealer.

4.2 Clearances to Walls and Ceilings

The following clearances have been tested to UL 

and ULC standards and are the minimum clearances 

specifically established for the F 500 V3.

The following diagrams give the required clearances 

you must maintain when installing the F 500 V3 near 

combustible surfaces. See pages 22-23.

A combustible surface is anything that can burn  

(i.e. sheet rock, wall paper, wood, fabrics etc.).  These 

surfaces are not limited to those that are visible and 

also include materials that are behind non-combustible 

materials.  

If you are not sure of the combustible nature of a 

material, consult your local fire officials. Contact your 

local building officials about restrictions and installation 

requirements in your area.

“Fire Resistant” materials are considered combustible; 

they are difficult to ignite, but will burn. “Fire-rated” sheet 

rock is also considered combustible.

4.3 Using Shields to Reduce Clearances

Pipe shields: When using listed pipe shields to reduce 

the connector clearance to combustibles, it must start 

1”(25,4mm) above the lowest exposed point of the 

connect pipe and extend vertically a minimum of 25” 

(635mm) above the top surface of the stove.

Double wall pipe: Listed double wall pipe is an 

acceptable alternative to connector pipe heatshields.

Wall-Mounted Protection: When reducing clearances 

through the use of wall mounted protection:

Refer to NFPA 211, Standard for Chimneys, Fireplaces, 

Vents and Solid Fuel Burning Appliances, for acceptable 

materials, proper sizing and construction guidelines.

Jøtul F 500  V3  Rear Heatshield Kit #154332

 

This shield is specifically approved for use to reduce 

clearances on this appliance only. No other heat 

shield may be used. 

See  pages  22-23  for complete clearance specifications  

and diagrams.

Содержание Classic F 500 V3

Страница 1: ...make them available to anyone using or servicing this wood heater This wood heater contains a catalytic combustor that requires periodic inspection and repair for proper operation See this manual for...

Страница 2: ...tove Inspection 13 6 2 Ash Removal 13 6 3 Chimney System 13 6 4 Enamel Care 13 6 5 Glass Care Glass Replacement 14 6 6 Gaskets 14 7 Accessories 15 8 Illustrations Figures 16 21 Clearance Chart and Dia...

Страница 3: ...NDING WHEN ADDING FUEL Avoid creating a low pressure condition in the room where the stove is operating Be aware that operation of an exhaust fan or clothes dryer can create a low pressure area and co...

Страница 4: ...ws The maximum horizontal run is 36 915mm and a recommended total length of stove pipe should not exceed 10 feet Horizontal runs must slope upward 1 4 6 35mm per foot toward the chimney Where passage...

Страница 5: ...collar Larger chimney flues should be relined with a listed or code approved liner The masonry chimney must have a fireclay liner or equivalent with a minimum thickness of 5 8 16mm and must be instal...

Страница 6: ...be installed to resize the flue The fireplace installation must also conform to the tested clearances to surrounding trim and mantels See clearance specifications on pages 22 23 In addition a fireplac...

Страница 7: ...50 5 deep 1168mmx1283mm can be used only if the left side door is locked to prevent use Door Lock Kit 155850 is available for this purpose from your dealer 4 2 Clearances to Walls and Ceilings The fo...

Страница 8: ...ned 2 All chimney components including chimney sections supports spark arrestor etc shall comply with the Standard for Factory built Chimneys for Residential Type and Building Heating Appliances UL 10...

Страница 9: ...as the stove The monitor should be located as far away as possible from the stove to avoid alerts when the doors are opened 5 3 Wood Fuel and Performance Use dry wood The F 500 V3 is designed to burn...

Страница 10: ...d into the atomosphere When the combustor is functioning no smoke will be observed exiting the chimney This is evidence that the stove is operating in the so called sweet spot wherein optimum efficien...

Страница 11: ...or the most efficient burn is between 400 and 600 204 C 316 C 2 Take the magnet off of thermometer and replace into the correct orientation as shown in fig 13c 13e 3 Place the thermometer fully into h...

Страница 12: ...full open position far right To minimize any smoke spillage open the door slightly before opening fully This will allow air flow to stabilize within the firebox and chimney flue Use a stove tool or po...

Страница 13: ...h to empty the drawer and then securely closed Inspect the gasket on the ash pan door regularly and replace as necessary 6 Maintenance See Appendix A page 24 for Combustor Maintenance and Replacement...

Страница 14: ...pattern as you would tighten the lugs on an automobile wheel 6 6 Gaskets Check door and glass panel gaskets for tightness To check the seal of the front door close and latch the door on a dollar bill...

Страница 15: ...ed with Rear Heat Shield 154332 not included Outside Air Kit 154335 Provision for outside air may be required by your local building codes The outside air kit includes a 3 inch adapter used to connect...

Страница 16: ...F 500 V3 Oslo 4 20 16 Fig 1a Fig 1b Fig 4 Masonry chimney penetration Fig 3 Chimney height 3 2 10 Rule Fig 2 Chimney connector assembly 8 Illustrations Fig 5 Chimney thimble components 24 3 4 629mm...

Страница 17: ...ns 2 50 mm Min width 50 5 1283mm Min width 56 1422 mm 18 460 mm 8 200 mm 8 200 mm 18 460 mm Min depth 50 1 2 1283 mm Min width 54 1 4 1378 mm Fig 6 Fireplace chimney construction Fig 7 Prefabricated c...

Страница 18: ...ature Monitor FULLY CLOSED FAR LEFT FULLY OPEN FAR RIGHT Combustion Monito r DO NOT REMOVE THIS SET SCREW Fig 13b Fig 13c Removemagnetfromcurrentorientation Fig 13d Orient magnet Incorrect Orientation...

Страница 19: ...e bottom 1 Bend the flattened heat shield on the perforations as shown painted side down 2 Use a 10 mm wrench to remove the two bolts from the bottom of the ash compartment Unpainted Side Up Fig 16 Bo...

Страница 20: ...F 500 V3 Oslo 4 20 20 F 500 V3 Illustrated Parts Breakdown Purchase replacement parts only from a J tul Authorized dealer...

Страница 21: ...le Cast Straight 10243892 31 Spring Door Handle 126164 32 Coiled Spring Pin 5x24 118070 33 Washer Door Handle 117587 34 Gasket Round LD2 375 Graphite 225695 35 Insulation Blanket Burn Plates 128903 36...

Страница 22: ...e Protected surface Single wall pipe 18 460mm 12 300mm Double wall pipe 6 150mm 6 150mm Fireplace Mantle and Trim Clearance no shielding reduction permitted Stove Side to Side Trim 1 thick or less 12...

Страница 23: ...ce Parallel to the Wall Unprotected Surface Corner Installation Protected Surface Corner Installation E F A G C F A G F A D F D D D B F F F F D A D F D D D F D D PER NFPA 211 or CAN CSA B365 Important...

Страница 24: ...periodically monitor the operation of the catalytic combustor to ensure that it is functioning properly and to determine when it needs to be replaced A non functioning combustor will result a loss of...

Страница 25: ...nd the front plate inside the stove as in fig 19 2 Use the 3mm hex key to remove the two M6x40 set screws on the left and right sides See fig 20 2 Wearing gloves grasp each side and lift the front of...

Страница 26: ...F 500 V3 Oslo 4 20 26 Fig 24 Left and Right Side insulation panel removal and replacement Fig 23 Lift combustor from the chamber Expansion gasket RRefactory member...

Страница 27: ...lue 3 If the overall R value of the system is greater than the R value of the specified floor protector the alternate is acceptable Example The specified floor protector should be 3 4 thick material w...

Страница 28: ...sions and Limitations Notice This warranty is void if installation or service is performed by someone other than an authorized installer or service agency or if installation is not in conformance with...

Страница 29: ...EASONABLY COULD HAVE BEEN DISCOVERED This warranty is given by J tul North America Inc 55 Hutcherson Drive Gorham Maine 04038 USA Return to Applied Ceramics Customer Service Department 5555 Pleasantda...

Страница 30: ...eplacement STEEL COMBUSTOR fails to function the prorated warranty will allow replacement at the following special price schedule Year 3 130 00 Year 4 140 00 Year 5 150 00 Year 6 160 00 Year 7 and aft...

Страница 31: ...F 500 V3 Oslo 4 20 31 This page is intentionally left blank...

Страница 32: ...box 1411 N 1602 Fredrikstad Norway www jotul us 139946_R10 April 2020 For Your Records Record the following information to help your dealer determine what you will need should your stove ever require...

Отзывы: