SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
49
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen displays a cutaway view of the chiller con-
denser, along with the liquid refrigerant level sensor
and variable orifice. Liquid Level Control setpoints
are maintained on this screen. Through animation, the
variable orifice position is displayed.
Requires a login access level of SERVICE.
Service Technicians refer to the OptiView
Control Center - Service Instructions
(Form 160.54-M1) for operation instruc-
tions and explanation of all programmable
setpoints and displayed values.
DISPLAY ONLY
Refrigerant Level Position
Displays the present position of the liquid level. The
refrigerant level is animated in the cutaway view of
the condenser. When the actual level is 0% to 15%, the
level is shown about 50% full. When the actual level is
16% to 31%, the level is shown about 60% full. When
the actual level 32% to 47%, the level is shown about
70% full. When the actual level is 48% to 63%, the
level is shown about 80% full. When the actual level
is 64% to 79%, the level is shown as about 90% full.
Actual levels above 79% are shown as 100% full.
PROGRAMMABLE
[Refrigerant Level] Setpoint
Displays the setpoint to which the refrigerant level is
being controlled.
[Refrigerant Level Control] Period
The entire chiller run time is divided into Level Con-
trol Periods.
[Refrigerant Level Control] Proportional Limit
Open
This key establishes the response to the Proportion
Error. The amount of change in the level within the
Proportion Error is compared to Setpoints Proportion
Limit Open (if level is above setpoint).
REFRIGERANT LEVEL CONTROL SETPOINTS SCREEN
(SOFTWARE VERSION C.MLM.01.07.XXX TO C.MLM.01.10D.XXX OR C.OPT.01.10D (AND EARLIER))
LD09097
FIGURE 14 -
REFRIGERANT LEVEL CONTROL SETPOINTS SCREEN (SOFTWARE VERSION C.MLM.01.07.
XXX TO C.MLM.01.10D.XXX OR C.OPT.01.10D (AND EARLIER))
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...