SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
DC Bus Voltage
Displays the DC Bus voltage as reported by the VSD.
DC Inverter Link Current
Displays the DC Inverter link current as reported by
the VSD.
Internal Ambient Temperature
Displays the ambient temperature inside the VSD cabi-
net as reported by the VSD.
Converter Heatsink Temperature
Displays the heatsink temperature of the converter as
reported by the VSD.
Baseplate Temperature
Displays the baseplate temperature of the 3-phase volt-
age regulators as reported by the VSD.
VSD Model
Access Level Required: SERVICE
Displays the horsepower configuration of the Variable
Speed Drive control.
100% Full Load Amps
Displays the Full Load Amps value as reported by the
VSD.
For fields requiring access level of SER
-
VICE. Service Technicians refer to the
OptiView Control Center - Service Instruc
-
tions (Form 160.54-M1) for operation
instructions and explanation of all pro-
grammable setpoints and displayed values.
PROGRAMMABLE
Local Motor Current Limit
Access Level Required: OPERATOR
Allows the user to specify the maximum allowed mo-
tor current (as a percentage of FLA). When the motor
current reaches this value, the Pre-rotation Vanes will
not be permitted to open further. If the motor current
rises above this value, the Pre-rotation Vanes will close
to reduce the current to this value.
Pulldown Demand Limit
Access Level Required: OPERATOR
Allows the user to specify the current limit value (as a
percentage of FLA) to which the chiller will be limited
during the specified pulldown limit time. This value
will override the Motor Current Limit value during this
time period. This function is used to provide energy
savings following chiller start-up.
Pulldown Demand Time
Access Level Required: OPERATOR
Allows the user to set a period of time for which the
pulldown demand limit will be in effect after the chiller
starts.
NAVIGATION
Home
Access Level Required: VIEW
Returns user to HOME Screen.
VSD
Access Level Required: VIEW
Returns user to VSD Screen.
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...