FORM 160.54-O1
ISSUE DATE: 9/10/2014
JOHNSON CONTROLS
14
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
The chiller operating program resides in the OptiView
Control Center Microboard. The Control Center could
be equipped with either of the following Microboards:
•
031-01730-000 – shipped in new production chill-
ers until January 2004. The program resides in a
replaceable Flash Memory Card. The software
version (C.MLM.01.xx.yzz) is printed on label
adhered to card. Program can be upgraded by re-
placing the card.
•
031-02430-000 – shipped in new production chill-
ers between January 2004 and June 2006. The pro-
gram resides in non-removable onboard memory.
The software version is C.OPT.01.xx.yzz, and is
viewable on the DIAGNOSTICS Screen in SER-
VICE access level. The program can be upgrad-
ed by downloading a new program from a Pro-
gram Card. Program Cards are shirt-pocket-size
portable memory storage devices available from
YORK.
•
031-02430-001 – Shipped in new production
chillers after June 2006. This is an upgraded ver-
sion of the 031-02430-000 microboard. The up-
grade is necessary to operate with the Medium
Voltage Solid State Starter, Medium Voltage Vari-
able Speed Drive and those Variable Speed Drives
and Style B Solid State Starters that serially com-
municate with the microboard using Modbus Pro-
tocol. Variable Speed Drive Modbus applications
require software version C.OPT.01.16.307 (or
later). Style B Solid State Starter Modbus appli-
cations require software version C.OPT.01.18.307
(or later).
The upgrade includes a larger BRAM (U38) and
an additional RS-485 port on COM2 serial port
for Modbus communications. When used in larger
BRAM configuration, requires software ver-
sion C.OPT.01.15.xxx (or later). This board is
backward compatible with YK chillers presently
using the 031-01730-000 or 031-02430-000 mi-
croboard.
Earlier vintage chillers could be equipped with a later
Microboard due to service replacement.
Software versions
(C.MLM.01.xx.yzz or C.OPT.01.
xx.yzz)
are alpha-numeric codes that represent the ap-
plication, language package and revision levels per be-
low. Each time the controls portion or language section
is revised, the respective revision level increments.
•
C – Commercial chiller
•
MLM – Used on Microboard 031-01730-000
•
OPT – Used on Microboard 031-02430-000
•
01 – YK chiller
•
xx – controls revision level (00, 01, etc)
•
y – language package (0 equals English only, 1
equals NEMA, 2 equals CE, 3 equals NEMA/CE )
•
zz – language package revision level (00, 01, etc)
Throughout this manual, reference is made to functions
and features that are only available in certain Flash
Memory Card revision levels (C.MLM.01.xx.xxx). To
cross reference C.MLM software to C.OPT software,
refer to the controls revision level. Software version
C.OPT.01.08A.300 is of the same controls revision
level as C.MLM.01.08.105A/.206A. From this starting
point, both receive the same updates at each revision.
Software upgrades should only be performed by a Ser-
vice Technician.
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...