SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
89
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen displays all information pertinent to the
Medium Voltage Solid State Starter (MVSSS). Soft-
ware version C.OPT.01.15.307 (or later) is required for
MVSSS applications.
DISPLAY ONLY
Motor Run (LED)
Indicates when the OptiView Control Center is com-
manding the motor to run.
Motor Current % Full Load Amps
Displays the motor current as a percentage of Job Full
Load Amps Setpoint.
Current Limit Setpoint
Displays the current limit in use. This value could
come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2
to 10VDC input in Analog Remote mode, PWM signal
in Digital Remote mode, E-Link Gateway interface in
ISN Remote mode or a locally programmed value in
Local mode.
Pulldown Time Left
Displays the time remaining in the programmed
pulldown period.
Input Power
Displays the kilowatts measured by and transmitted
from the starter.
KW Hours
Displays the cumulative kilowatt hours. The mi-
croboard calculates this value from the Input Power
transmitted from the starter. When the number exceeds
999999 KWH, the value will rollover to zero.
Voltage – Phase A, B, C
Displays the 3-phase input line voltage as measured by
and transmitted from the starter.
Current – Phase A, B, C
Displays the 3-phase motor current as measured by and
transmitted from the starter.
Starter Model
Displays the starter model number as transmitted from
the starter.
MEDIUM VOLTAGE SOLID STATE STARTER SCREEN
LD12573a
FIGURE 29 -
MEDIUM VOLTAGE SOLID STATE STARTER SCREEN
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...