FORM 160.54-O1
ISSUE DATE: 9/10/2014
JOHNSON CONTROLS
182
SECTION 3 - DISPLAY MESSAGES
Oil – Low Temperature
The oil temperature has decreased to less than 55°F.
The chiller will automatically restart when the tem-
perature increases to greater than 55.0°F and is greater
than the Condenser Saturated temperature by 30 or
40°F, as described above in the Oil – Low Temperature
Differential message description.
Control Panel – Power Failure
A Control Power failure has occurred. If the power fail-
ure occurred while the chiller was running, it will auto-
matically restart when power is restored. However, if the
power failure duration was less than the duration of the
applicable coastdown period (2.5 minutes standard; 15
minutes steam turbine) when power is restored, the re-
mainder of the coastdown will be performed, prior to the
chiller starting. This message can indicate a Cycling (au-
to-restart after power failure) or Safety (manual restart
after power failure) shutdown, depending upon Control
Center configuration. It indicates a cycling shutdown
when displayed in orange characters; safety shutdown
when displayed in red characters. The Control Center is
configured for auto-restart or manual restart after power
failure by a qualified Service Technician following in-
structions in
OptiView Control Center - Service Instruc-
tions (Form 160.54-M1)
.
Leaving Chilled Liquid – Low Temperature
The Leaving Chilled Liquid Temperature has decreased
to the programmed Shutdown Temperature Setpoint. If
the chiller is running when this occurs, the Pre-rotation
Vanes are driven fully closed prior to shutting down
the chiller. The chiller will automatically restart when
the temperature increases to the programmed Restart
Temperature Setpoint.
If the chiller is operating in Heat Pump Heating mode,
(Heat Pump Duty is enabled, and the Heat Pump Op-
erational mode setpoint is set to Heating), there is ad-
ditional logic that will cause this Shutdown when the
Leaving Chilled Liquid Temperature (LCHLT) de-
creases below the programmed Heating LCHLT Shut-
down Temperature Setpoint. For details of this setpoint,
refer to the HEAT PUMP Screen.
Leaving Condenser Liquid – High Temperature
(Software version C.OPT.01.23.307 and later)
The Leaving Condenser Liquid Temperature has in-
creased to the programmed Leaving Condenser Liquid
Temperature Cycling Offset - Shutdown Setpoint. This
shutdown is only applicable to Heat Pump Duty en-
abled and operating in Heating mode (Heat Pump Op-
erational Setpoint set to Heating mode). Refer to HEAT
PUMP Screen. Anytime the Leaving Condenser Liq-
uid Temperature Setpoint is decreased, the shutdown
threshold becomes 125°F for the next 10 minutes. Af-
ter 10 minutes have elapsed, the shutdown threshold
becomes the programmed setpoint value. The Heat
Pump will automatically restart when the temperature
decreases to the programmed Leaving Condenser Liq-
uid Temperature Cycling offset – Restart Setpoint.
Leaving Chilled Liquid – Flow Switch Open
The Chilled Liquid Flow Switch has remained open for
5 continuous seconds (2 seconds with software version
C.OPT.01.15A.xxx and earlier) while the chiller was
running or failed to close during the System Prelube
period. The chiller will automatically restart when the
flow switch closes.
With software version C.OPT.01.23.307 (and later),
while this cycling shutdown is active, the evaporator
pump relay contacts (TB2-44/45) remain closed un-
til the chiller is given a stop command or has another
fault. With all previous software versions, these con-
tacts open at completion of coastdown.
Condenser – Flow Switch Open
The condenser water flow switch has remained open
for 30 continuous seconds (2 seconds with software
version C.OPT.01.15A.xxx and earlier) while the chill-
er was running. This check is bypassed for the first 30
seconds of System Run. The chiller will automatically
restart when the flow switch closes.
With software version C.OPT.01.23.307 (and later),
while this cycling shutdown is active, the condenser
pump contacts (TB2-150/151) remain closed until the
chiller is given a stop command or has another fault.
With all previous software versions, these contacts
open at completion of coastdown.
Motor Controller – Contacts Open
The CM-2 Current Module (Electromechanical starter ap-
plications) or Solid State Starter Logic Board (Mod “A”
Solid State Starter applications) has shutdown the chiller.
When detecting a fault condition that places the starter
or motor at risk, these devices open the Motor Controller
contacts “CM” (located on the respective device and con-
nected between TB6-16 and TB6-53 in the Control Cen-
ter) to initiate a shutdown. Since there are several different
faults that are monitored, LED’s on the respective device
illuminate to identify the specific fault that has occurred.
Содержание YORK YK Style G OPTIVIEW
Страница 38: ...JOHNSON CONTROLS 38 FORM 160 75 O1 111 NOTES ...
Страница 242: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 202 SECTION 3 DISPLAY MESSAGES THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 258: ...FORM 160 54 O1 ISSUE DATE 9 10 2014 JOHNSON CONTROLS 218 NOTES ...
Страница 266: ...JOHNSON CONTROLS 6 FORM 160 75 N1 ISSUE DATE 4 30 2014 THIS PAGE INTENTIONALLY LEFT BLANK ...