JOHNSON CONTROLS

14

FORM 160.00-O10 

ISSUE DATE: 8/24/2020

SECTION 1 - GENERAL INFORMATION

DRIVE AND CHILLER OPERATION 

When the chiller enters a start command, the OSCD 

is commanded to precharge, the pre-charge contactor 

will close and slowly charge the DC bus capacitors 

through the pre-charge resistors. This is called the 

precharge period, which will last for 12-seconds. Af-

ter the 12-second time period has expired, the supply 

contactor will close and the pre-charge contactor will 

open. The supply and pre-charge contactors will re-

main in this state for the duration of the run cycle. The 

OSCD logic board directly provides the commands for 

the precharge contactor and a pilot relay to provide 

power to the supply contactor's coil. The coil power 

requirements for the supply contactor it too large to be 

directly driven by the drive logic board. 
The cooling fans and pumps will turn on after the 

precharge time is complete, and continue to run for 2 

minutes after the stop command is provided from the 

OptiView panel.
During normal chiller run conditions the OptiView 

panel provides a speed command to the OSCD. The 

speed command is converted into the proper turn-on 

and turn-off commands for the inverter by the drive 

logic board.

OPTISPEED COMPRESSOR DRIVE CONTROL 

SYSTEM OVERVIEW

The HYP model of OSCD can only be controlled by 

the OptiView Control Panel with a 031-03630 mi-

croboard installed.
The OSCD control system is composed of various 

components located within both the OptiView Control 

Panel and the OSCD. Thus integrating the Control Cen-

ter with the OSCD. The OSCD system utilizes various 

microprocessors, which are linked together through a 

ModBus communication link.
Data such as output currents, baseplate temperatures, 

and input voltage are communicated from the OSCD 

to the microboard for display through the ModBus 

communications link. The OptiView panel collects 

data from the many chiller sensors to determine the 

optimum speed for the compressor. This information 

is communicated to the drive logic board. The drive 

logic board then determines the output voltage and fre-

quency to control the compressor motor.

OptiView Control Panel VSD Functions

Refer to the specific OptiView™ Control Panel service 

and operation manual for detailed information. All of 

the OSCD related information is contained under the 

Motor and Compressor Screens.

Drive Not Reducing Speed

The ACC may begin the process of reducing speed, but 

may stop speed reduction if instability in the leaving 

liquid temperature is encountered. Once the system 

again becomes unstable, no additional speed reduction 

can occur. The most common causes for instability are:

•  High Condenser liquid temperature.
•  Dirty Condenser tubes.
•  Chillers with very light loads.
•  Rapid changes to chilled or condenser liquid flow.
•  Valves on air-handler coils closing rapidly caus-

ing changes in heat-load.

•  Extremely short chilled liquid loop.
•  Parallel chiller with poor control is causing tem- 

perature variations.

•  Parallel Chiller with poor control of chilled or 

condenser water flows.

•  Improper evaporator refrigerant level.

If you experience a problem with an OSCD not re- 

ducing speed at all, make certain the system is not 

in manual speed control, or locked into fixed speed. 

Either situation will cause the chiller to maintain full 

speed. If the OSCD is reducing speed, but not running 

as slow as you expect it should, it is likely because it is 

either in an unstable condition, or running just above a 

mapped surge point. 

Содержание YORK HYP1100A

Страница 1: ...415 VAC 371 06172 XXX 1300 HP 60 HZ 460 VAC 371 06172 XXX MODELS HYP1100A HYP1300A LIQUID COOLED OPTISPEED COMPRESSOR SPEED DRIVE OPERATION MANUAL Supersedes 160 00 O10 217 Form 160 00 O10 820 Issue...

Страница 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Страница 3: ...g and operating service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chill...

Страница 4: ...173 Retrofit Package YK Filter Model HYP1100RKC30B 50A 371 06172 175 Retrofit Package YK Filter Model 1100 HP 400 VAC HYP1100RKC30B 42A 371 06172 185 Retrofit Package YK Filter Model HYP1100RKC30B 50...

Страница 5: ...Demand Distortion 16 VSD Input Current Overload 16 VSD Input DCCT Offset Lockout 16 VSD Inverter Program Fault 16 VSD Line Voltage Phase Rotation 16 VSD Logic Board Hardware 16 VSD Logic Board Plug 1...

Страница 6: ...B Input Gate Driver 21 VSD Phase C Input Gate Driver 21 VSD Phase A Motor Gate Driver 21 VSD Phase B Motor Gate Driver 21 VSD Phase C Motor Gate Driver 21 VSD Precharge Low DC Bus Voltage 1 21 VSD Pre...

Страница 7: ...power devices required for one phase of input and output In other words the rectifier and inverter are integrated into one power unit This design has 2 methods of detecting a ground fault The circuit...

Страница 8: ...COMPRESSOR DRIVE DETAILS The 1300 HP drive contains 3 power assemblies Each power assembly contains 2 capacitors with the rectifier of the left side of the power assembly and the inverter on the righ...

Страница 9: ...OSCD to provide input current limit ground fault detection and information for the harmonic current filtering The bus voltage is moni tored to verify that bus voltage is present The line volt age is...

Страница 10: ...SSUE DATE 8 24 2020 SECTION 1 GENERAL INFORMATION Figure 1 HYP1100A HYP1300A HP COMPLETE DRIVE CABINET Cooling Coil Supply Contactor Fan Assembly A Phase Power Assembly B Phase Power Assembly BUS Stru...

Страница 11: ...RMATION FORM 160 00 O10 ISSUE DATE 8 24 2020 1 Figure 2 LEFT SIDE OF HYP1100A HYP1300A HP DRIVE CABINET Voltage Transient Board Line Voltage Isolation Board Drive Logic Board Cooling Fans Cooling Coil...

Страница 12: ...JOHNSON CONTROLS 12 FORM 160 00 O10 ISSUE DATE 8 24 2020 SECTION 1 GENERAL INFORMATION Figure 3 RIGHT SIDE OF HYP1100A HYP1300A HP DRIVE CABINET Inlet Coolant Hose Step Down Transformers LD21854...

Страница 13: ...JOHNSON CONTROLS 13 SECTION 1 GENERAL INFORMATION FORM 160 00 O10 ISSUE DATE 8 24 2020 1 Figure 4 DRIVE LOGIC BOARD LD16293 Figure 5 RECTIFIER SIDE OF THE POWER UNIT HYP1100A AND HYP1300A LD16292...

Страница 14: ...ogether through a ModBus communication link Data such as output currents baseplate temperatures and input voltage are communicated from the OSCD to the microboard for display through the ModBus commun...

Страница 15: ...pre charge to start The unit s fan s and water pump s shall remain energized during this wait time The VSD shall allow up to three consecutive pre regulation related faults i e VSD DC BUS PRE REGULAT...

Страница 16: ...he input current overload value must be greater than the shutdown value for 10 continuous seconds for this shutdown to occur DRIVE MODEL INPUT CURRENT OVERLOAD MAXIMUM SHUTDOWN VALUE 1100 1300 1305 Am...

Страница 17: ...unt of current is flowing to the motor If at the end of the 1 5 second time a minimum of 25 amps peak is not detected then this shutdown is generated VSD PHASE B MOTOR DCCT See VSD PHASE A MOTOR DCCT...

Страница 18: ...JOHNSON CONTROLS 18 FORM 160 00 O10 ISSUE DATE 8 24 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 19: ...ltage exceeds the value for the given model of drive then this shutdown will occur Typically this shutdown will occur when there is a sudden change in the input voltage due to storms utility power pro...

Страница 20: ...this fault There are several causes for an unsuccessful initialization as follows Serial data communications must be established Refer to VSD Serial Communications fault If communications between the...

Страница 21: ...message preceding VSD PHASE A INPUT GATE DRIVER The gate driver board for the input rectifier monitors the power supplies within the gate driver circuit and verifies that the input rectifier can be p...

Страница 22: ...IVE This shutdown is generated when the VSD logic board has not received a valid communications packet from the control center for 10 consecutive seconds VSD SHUTDOWN REQUESTING FAULT DATA The VSD has...

Страница 23: ...tice we have no objections as long as the OSCD is properly grounded Can I apply an OptiSpeed Compressor Drive to a generator Yes the OSCD can be applied to a generator No modi fications are required f...

Страница 24: ...ennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 00 O10 820 Issue Date Augus...

Отзывы: