SECTION 3 - CYCLING SHUTDOWNS

MESSAGE

DESCRIPTION

VSD – PRECHARGE – LOW 

DC BUS VOLTAGE 2

During Pre-charge, the DC bus voltage must exceed the minimum threshold which is 

determined by Line Voltage Setpoint (see the table below) within 12 seconds after the 

pre-charge signal has been commanded. If this condition is not met, this shutdown is 

generated. The VSD logic board shall wait 10 seconds before clearing the fault and 

allowing another pre-charge to start. The VFD’s fan(s) and water pump(s) shall remain 

energized during this time. The VSD logic board shall allow up to three consecutive pre-

charge-related faults to occur. After the third consecutive pre-charge-related fault, Safety 

Shutdown message “VSD – PRECHARGE LOCKOUT” is generated.

LINE VOLTAGE

MINIMUM THRESHOLD (VOLTS)

380/415

414

460

500

VSD – RUN SIGNAL

Redundant RUN signals are generated by the control center; one via TB6-24 and the 

second via the Serial Communications link. Upon receipt of either of the two RUN 

commands by the VSD, a 5 second timer shall commence timing. If the run signal 

on TB6-24 is not received by the VSD Logic Board within 5 seconds, a shutdown is 

performed and this message is displayed. This is generally indicative of a wiring problem 

between the control center and the VSD.

VSD – SERIAL RECEIVE

This shutdown is generated when the VSD logic board has not received a valid 

communications packet from the control center for 10 consecutive seconds.

VSD SHUTDOWN – 

REQUESTING FAULT DATA

The VSD has shut down the chiller and the control center has not yet received the cause 

of the fault from the VSD, via the serial communications link. The VSD shuts down the 

chiller by opening the Motor Controller VSD Stop Contacts. The control center then 

sends a request for the cause of the fault to the VSD over the serial link. Since serial 

communications are initiated every 2 seconds, this message is typically displayed for a 

few seconds and then replaced with one of the other VSD fault messages.

VSD – SINGLE PHASE INPUT 

POWER

The VSD monitors the input voltage of all three phases. If the input voltage of any one 

phase drops below the threshold value for the given input voltage range below, then this 

shutdown will occur.

INPUT VOLTAGE 

RANGE

INPUT VOLTAGE SINGLE PHASE SHUTDOWN 

VALUE (VOLTS)

380/415

264

460

295

VSD - STOP CONTACTS 

OPEN

Whenever the OSCD initiates a fault, it first opens the fault relay on the OSCD logic 

board. When the relay opens a message is sent to the OptiView panel microboard, 

detailing the cause of the fault. If this circuit ever opens without receiving an 

accompanying cause for the fault over the communication link within 20 seconds then this 

message will be displayed. This fault may be replaced with a Serial Communications fault 

if the serial link has failed.

TABLE 3 - 

CYCLING SHUTDOWN MESSAGE (CONT'D) 

Содержание YORK HYP1100A

Страница 1: ...415 VAC 371 06172 XXX 1300 HP 60 HZ 460 VAC 371 06172 XXX MODELS HYP1100A HYP1300A LIQUID COOLED OPTISPEED COMPRESSOR SPEED DRIVE OPERATION MANUAL Supersedes 160 00 O10 217 Form 160 00 O10 820 Issue...

Страница 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Страница 3: ...g and operating service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chill...

Страница 4: ...173 Retrofit Package YK Filter Model HYP1100RKC30B 50A 371 06172 175 Retrofit Package YK Filter Model 1100 HP 400 VAC HYP1100RKC30B 42A 371 06172 185 Retrofit Package YK Filter Model HYP1100RKC30B 50...

Страница 5: ...Demand Distortion 16 VSD Input Current Overload 16 VSD Input DCCT Offset Lockout 16 VSD Inverter Program Fault 16 VSD Line Voltage Phase Rotation 16 VSD Logic Board Hardware 16 VSD Logic Board Plug 1...

Страница 6: ...B Input Gate Driver 21 VSD Phase C Input Gate Driver 21 VSD Phase A Motor Gate Driver 21 VSD Phase B Motor Gate Driver 21 VSD Phase C Motor Gate Driver 21 VSD Precharge Low DC Bus Voltage 1 21 VSD Pre...

Страница 7: ...power devices required for one phase of input and output In other words the rectifier and inverter are integrated into one power unit This design has 2 methods of detecting a ground fault The circuit...

Страница 8: ...COMPRESSOR DRIVE DETAILS The 1300 HP drive contains 3 power assemblies Each power assembly contains 2 capacitors with the rectifier of the left side of the power assembly and the inverter on the righ...

Страница 9: ...OSCD to provide input current limit ground fault detection and information for the harmonic current filtering The bus voltage is moni tored to verify that bus voltage is present The line volt age is...

Страница 10: ...SSUE DATE 8 24 2020 SECTION 1 GENERAL INFORMATION Figure 1 HYP1100A HYP1300A HP COMPLETE DRIVE CABINET Cooling Coil Supply Contactor Fan Assembly A Phase Power Assembly B Phase Power Assembly BUS Stru...

Страница 11: ...RMATION FORM 160 00 O10 ISSUE DATE 8 24 2020 1 Figure 2 LEFT SIDE OF HYP1100A HYP1300A HP DRIVE CABINET Voltage Transient Board Line Voltage Isolation Board Drive Logic Board Cooling Fans Cooling Coil...

Страница 12: ...JOHNSON CONTROLS 12 FORM 160 00 O10 ISSUE DATE 8 24 2020 SECTION 1 GENERAL INFORMATION Figure 3 RIGHT SIDE OF HYP1100A HYP1300A HP DRIVE CABINET Inlet Coolant Hose Step Down Transformers LD21854...

Страница 13: ...JOHNSON CONTROLS 13 SECTION 1 GENERAL INFORMATION FORM 160 00 O10 ISSUE DATE 8 24 2020 1 Figure 4 DRIVE LOGIC BOARD LD16293 Figure 5 RECTIFIER SIDE OF THE POWER UNIT HYP1100A AND HYP1300A LD16292...

Страница 14: ...ogether through a ModBus communication link Data such as output currents baseplate temperatures and input voltage are communicated from the OSCD to the microboard for display through the ModBus commun...

Страница 15: ...pre charge to start The unit s fan s and water pump s shall remain energized during this wait time The VSD shall allow up to three consecutive pre regulation related faults i e VSD DC BUS PRE REGULAT...

Страница 16: ...he input current overload value must be greater than the shutdown value for 10 continuous seconds for this shutdown to occur DRIVE MODEL INPUT CURRENT OVERLOAD MAXIMUM SHUTDOWN VALUE 1100 1300 1305 Am...

Страница 17: ...unt of current is flowing to the motor If at the end of the 1 5 second time a minimum of 25 amps peak is not detected then this shutdown is generated VSD PHASE B MOTOR DCCT See VSD PHASE A MOTOR DCCT...

Страница 18: ...JOHNSON CONTROLS 18 FORM 160 00 O10 ISSUE DATE 8 24 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 19: ...ltage exceeds the value for the given model of drive then this shutdown will occur Typically this shutdown will occur when there is a sudden change in the input voltage due to storms utility power pro...

Страница 20: ...this fault There are several causes for an unsuccessful initialization as follows Serial data communications must be established Refer to VSD Serial Communications fault If communications between the...

Страница 21: ...message preceding VSD PHASE A INPUT GATE DRIVER The gate driver board for the input rectifier monitors the power supplies within the gate driver circuit and verifies that the input rectifier can be p...

Страница 22: ...IVE This shutdown is generated when the VSD logic board has not received a valid communications packet from the control center for 10 consecutive seconds VSD SHUTDOWN REQUESTING FAULT DATA The VSD has...

Страница 23: ...tice we have no objections as long as the OSCD is properly grounded Can I apply an OptiSpeed Compressor Drive to a generator Yes the OSCD can be applied to a generator No modi fications are required f...

Страница 24: ...ennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 00 O10 820 Issue Date Augus...

Отзывы: