JOHNSON CONTROLS
11
FORM 145.13-NO1
ISSUE DATE: 10/06/2016
2
SECTION 2 - OPERATION
INPUT/OUTPUT
Jumper required between 10, 11
FIGURE 7 -
INPUT/OUTPUT DIAGRAM
PARAMETER TABLES
In the parameter menu, set the following parameters
listed in the parameters tables in order to operate the
VFD controller correctly. For troubleshooting, check
that the parameters match.
DISPLAY
In AUTO MODE, the following parameters will be
displayed on control display:
1. 30–60Hz is the output frequency to the motor.
Minimum factory set frequency allowed is 30 Hz.
2. 0.0 to Nominal Motor Amps. Maximum amps
draw is factory set, and it is set to nominal amp
draw of motor used.
3. 0.0-2.5 "WC is the actual reading from the pres-
sure transducer.
4. Located in the upper-right corner, the setpoint
value is displayed. It goes from 0% to 100%. That
is the actual setpoint for the controller. Setpoint
can be 0%, which is 0.0 "WC or 100%, which is
2.5 "WC.
Example:
20% corresponds to 0.5 "WC setpoint.
Setpoint can be updated using parameter 4011.
Transducer
(-COM)
Jumper set
to 4-20mA
Transducer
(+EXC) 24VDC
TABLE 1 -
VFD FACTORY PARAMETERS FOR VAV APPLICATION 208/230 & 460 VAC (ABB ACS320)
PARAMETER
DESCRIPTION
VALUE
GROUP 99: START-UP DATA
9901
LANGUAGE
0:
(ENGLISH)
9902
APPLICATION MACRO
1:
(HVAC DEFAULT)
9905
MOTOR NOMINAL VOLTAGE
MOTOR NAMEPLATE
9906
MOTOR NOMINAL CURRENT
MOTOR NAMEPLATE
9907
MOTOR NOMINAL FREQUENCY
MOTOR NAMEPLATE
9908
MOTOR NOMINAL SPEED
MOTOR NAMEPLATE
9909
MOTOR NOMINAL POWER
MOTOR NAMEPLATE
GROUP 10
1003
DIRECTION
1:
(FORWARD)
GROUP 11
1102
EXT1/EXT2/SELECTION
7:
(EXT2)
1103
REF1 SELECT
0:
(KEYPAD)
GROUP 13
1301
MINIMUM AI1
0%
GROUP 16
1601
RUN ENABLE
1:
(DI1)
1608
START ENABLE 1
0:
(NOT SELECTED)
1611
PARAMETER VIEW
3:
(LONG VIEW)