SECTION 2 - OPERATION

FORM 145.13-NO1 

ISSUE DATE: 10/06/2016

2

PARAMETER

DESCRIPTION

VALUE

GROUP 16

1608

START ENABLE 1

1:

 (DI1) 

1611

PARAMETER VIEW

3: 

(LONG VIEW)

GROUP 20

2003

MAX CURRENT

DRIVE DEPENDENT

GROUP 34

3403

SIGNAL 1 MAX

60

3405

OUTPUT 1 UNIT

3: 

(HZ)

3407

OUTPUT 1 MAX

60

3408

SIGNAL 2 PARAMETER

NOT SELECTED

3415

SIGNAL 3 PARAMETER

NOT SELECTED

*Note: If only one speed fan operation is wanted, adjust to 60.

TABLE 3 - 

FACTORY PARAMETERS FOR 2 SPEED APPLICATION 575 VAC (ABB ACS250)

PARAMETER

DESCRIPTION

VALUE

GROUP 99

9902

APPLICATION MACRO

8

9905

MOTOR NOMINAL VOLTAGE

MOTOR NAMEPLATE

9906

MOTOR NOMINAL CURRENT

MOTOR NAMEPLATE

9907

MOTOR NOMINAL FREQUENCY

MOTOR NAMEPLATE

9908

MOTOR NOMINAL SPEED

MOTOR NAMEPLATE

GROUP 11

1103

PRIMARY COMMAND

0: TERMINAL CONTROL

GROUP 12

1202

CONSTANT SPEED 1

0

1203

CONSTANT SPEED 2

35 (* See Note)

1204

CONSTANT SPEED 3

0

1205

CONSTANT SPEED 4

60

*NOTE: 

If only one speed fan operation is wanted, adjust to 60.

TABLE 4 - 

DRIVE DEPENDENT PARAMETERS GROUP 99

VFD PROGRAM 

PART #

AJAX MOTOR 

(BALDOR MOTOR) 

MODEL #

ABB VFD MODEL #

VOLTAGE

HP

MOTOR 

NOMINAL 

CURRENT FLA

MOTOR 

NOMINAL 

SPEED RPM

VFD-PTD-234HE-2

MTR-234HE 

(EM3154T)

ACS320-03U-07A4-2 208-230/3/60

1.50

4.50

1755

VFD-PTD-234HE-4

ACS320-03U-03A3-4

460/3/60

2.20

VFD-PTD-235HE-2

MTR-235HE 

(EM3157T)

ACS320-03U-07A4-2 208-230/3/60

2.00

5.80

1750

VFD-PTD-235HE-4

ACS320-03U-04A1-4

460/3/60

2.90

VFD-PTD-236HE-2

MTR-236HE 

(EM3211T)

ACS320-03U-10A8-2 208-230/3/60

3.00

8.50

1765

VFD-PTD-236HE-4

ACS320-03U-05A6-4

460/3/60

4.20

VFD-PTD-237HE-2

MTR-237HE 

(EM3218T)

ACS320-03U-19A4-2 208-230/3/60

5.00

14.00

1750

VFD-PTD-237HE-4

ACS320-03U-08A8-4

460/3/60

6.60

VFD-PTD-238HE-2

MTR-238HE 

(EM3311T)

ACS320-03U-26A8-2 208-230/3/60

7.50

20.40

1770

VFD-PTD-238HE-4

ACS320-03U-12A5-4

460/3/60

9.70

TABLE 2 

- FACTORY PARAMETERS FOR 2 SPEED APPLICATION 208/230 & 460 VAC (ABB ACS320) (CONT'D)

Содержание VFD-2DS-234HE-2

Страница 1: ...E FOR D SERIES DSV DSH AIR COOLED SELF CONTAINED UNITS B STYLE AND C SERIES CSV WATER COOLED SELF CONTAINED UNITS B STYLE Issue Date October 6 2016 INDOOR PACKAGED EQUIPMENT INSTALLATION OPERATION NEW...

Страница 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Страница 3: ...controls com It is the responsibility of rigging lifting and operating service personnel to verify the applicability of these documents to the equipment If there is any question regarding the applicab...

Страница 4: ...tor 236HE 3 0 HP Motor 237HE 5 0 HP Motor 238HE 7 5 HP Motor 239HE 10 0 HP Motor 1 2 3 4 5 6 7 8 9 10 11 12 13 VFD PTD 234HE 2 A Product Category VFD VFD Program Parameter Set VFD Option PTD VAV with...

Страница 5: ...ntrol 8 FIGURE 3 VFD Keypad 9 FIGURE 4 VFD Keypad and Ethernet Connector 9 FIGURE 5 Connecting Negative and Positive Side Fittings 10 FIGURE 6 VFD Grille Cover 10 FIGURE 7 Input Output Diagram 11 FIGU...

Страница 6: ...JOHNSON CONTROLS 6 FORM 145 13 NO1 ISSUE DATE 10 06 2016 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 7: ...ided and routed from condenser to evaporator SECTION 1 INSTALLATION DO NOT enter Setup mode when power ing on the VFD There are two main VFD options Differ ential Pressure Transducer and Discrete 2 Sp...

Страница 8: ...fitting Only on 208 230 460 VAC units not on 575 VAC Parameters 4009 and 4011 are factory set at 0 5 WC These are field adjusted points that need to be adjusted at start up These setpoints are based...

Страница 9: ...60hz Set at parameter 1204 24 VDC applied to terminal 4 and 6 of VFD VFD KEYPAD VFD requires a keypad to program the VFD Once the VFD is programmed the keypad is not required in or der to operate the...

Страница 10: ...sure the tubes are secure inside duct and firmly con nected to transducer fitting otherwise unit will not op erate as intended INSTALL GRILLE COVER When unit is wired and push on tubing has been con n...

Страница 11: ...ner the setpoint value is displayed It goes from 0 to 100 That is the actual setpoint for the controller Setpoint can be 0 which is 0 0 WC or 100 which is 2 5 WC Example 20 corresponds to 0 5 WC setpo...

Страница 12: ...K SELECT 1 ACT1 4016 ACT1 INPUT 1 AI1 4018 ACT1 MIN 20 4019 ACT1 MAX 100 Table 2 FACTORY PARAMETERS FOR 2 SPEED APPLICATION 208 230 460 VAC ABB ACS320 PARAMETER DESCRIPTION VALUE GROUP 99 9901 LANGUAG...

Страница 13: ...T SPEED 2 35 See Note 1204 CONSTANT SPEED 3 0 1205 CONSTANT SPEED 4 60 NOTE If only one speed fan operation is wanted adjust to 60 Table 4 DRIVE DEPENDENT PARAMETERS GROUP 99 VFD PROGRAM PART AJAX MOT...

Страница 14: ...A1 6 575 3 60 2 30 VFD 2DS 236HE 2 MTR 236HE EM3211T ACS320 03U 10A8 2 208 230 3 60 3 00 8 50 1765 VFD 2DS 236HE 4 ACS320 03U 05A6 4 460 3 60 4 20 VFD 2DS 236HE 5 MTR 536HE EM3211T 5 ACS250 03U 04A1 6...

Страница 15: ...NO1 ISSUE DATE 10 06 2016 3 LD20867 Figure 9 EVAPORATOR VFD OPTION FOR DUCT STATIC PRESSURE WIRING SCHEMATIC 208 230V 460V 3PH 60HZ LD20868 Figure 10 EVAPORATOR VFD OPTION FOR DISCRETE 2 SPEED WIRING...