JOHNSON CONTROLS
13
SECTION 2 - OPERATION
FORM 145.13-NO1
ISSUE DATE: 10/06/2016
2
PARAMETER
DESCRIPTION
VALUE
GROUP 16
1608
START ENABLE 1
1:
(DI1)
1611
PARAMETER VIEW
3:
(LONG VIEW)
GROUP 20
2003
MAX CURRENT
DRIVE DEPENDENT
GROUP 34
3403
SIGNAL 1 MAX
60
3405
OUTPUT 1 UNIT
3:
(HZ)
3407
OUTPUT 1 MAX
60
3408
SIGNAL 2 PARAMETER
NOT SELECTED
3415
SIGNAL 3 PARAMETER
NOT SELECTED
*Note: If only one speed fan operation is wanted, adjust to 60.
TABLE 3 -
FACTORY PARAMETERS FOR 2 SPEED APPLICATION 575 VAC (ABB ACS250)
PARAMETER
DESCRIPTION
VALUE
GROUP 99
9902
APPLICATION MACRO
8
9905
MOTOR NOMINAL VOLTAGE
MOTOR NAMEPLATE
9906
MOTOR NOMINAL CURRENT
MOTOR NAMEPLATE
9907
MOTOR NOMINAL FREQUENCY
MOTOR NAMEPLATE
9908
MOTOR NOMINAL SPEED
MOTOR NAMEPLATE
GROUP 11
1103
PRIMARY COMMAND
0: TERMINAL CONTROL
GROUP 12
1202
CONSTANT SPEED 1
0
1203
CONSTANT SPEED 2
35 (* See Note)
1204
CONSTANT SPEED 3
0
1205
CONSTANT SPEED 4
60
*NOTE:
If only one speed fan operation is wanted, adjust to 60.
TABLE 4 -
DRIVE DEPENDENT PARAMETERS GROUP 99
VFD PROGRAM
PART #
AJAX MOTOR
(BALDOR MOTOR)
MODEL #
ABB VFD MODEL #
VOLTAGE
HP
MOTOR
NOMINAL
CURRENT FLA
MOTOR
NOMINAL
SPEED RPM
VFD-PTD-234HE-2
MTR-234HE
(EM3154T)
ACS320-03U-07A4-2 208-230/3/60
1.50
4.50
1755
VFD-PTD-234HE-4
ACS320-03U-03A3-4
460/3/60
2.20
VFD-PTD-235HE-2
MTR-235HE
(EM3157T)
ACS320-03U-07A4-2 208-230/3/60
2.00
5.80
1750
VFD-PTD-235HE-4
ACS320-03U-04A1-4
460/3/60
2.90
VFD-PTD-236HE-2
MTR-236HE
(EM3211T)
ACS320-03U-10A8-2 208-230/3/60
3.00
8.50
1765
VFD-PTD-236HE-4
ACS320-03U-05A6-4
460/3/60
4.20
VFD-PTD-237HE-2
MTR-237HE
(EM3218T)
ACS320-03U-19A4-2 208-230/3/60
5.00
14.00
1750
VFD-PTD-237HE-4
ACS320-03U-08A8-4
460/3/60
6.60
VFD-PTD-238HE-2
MTR-238HE
(EM3311T)
ACS320-03U-26A8-2 208-230/3/60
7.50
20.40
1770
VFD-PTD-238HE-4
ACS320-03U-12A5-4
460/3/60
9.70
TABLE 2
- FACTORY PARAMETERS FOR 2 SPEED APPLICATION 208/230 & 460 VAC (ABB ACS320) (CONT'D)