SECTION 1 - INSTALLATION

CSV MODELS

CSV units that are 10–20 tons are factory wired; no 

field wiring is required. The 25-ton CSV unit ships 

split, and field wiring of evaporator fan motor con-

ductors to terminal block in electrical box is required. 

Connect low voltage wiring from VFD unit (10VDC) 

to the evaporator fan VFD relay RVFD (red wire to 

“C”; yellow wire to “NO”). The RVFD relay acts as 

a switch to turn on the VFD. The VFD switch runs on 

10VDC. See 

VFD Option Schematics on page 14

.

Do not cross 24VAC and 10VDC wiring.

VAV UNITS
Differential Pressure Transducer

FOR TECHNICAL SUPPORT, CALL: 877-329-7430

STK-VFD

VFD FACTORY PROGRAMMED

SET PARAMETER 4009 & 4011 PRIOR TO START-UP

JOHNSON CONTROLS, AJAX, CANADA

VFD PART #:

VFD APPLICATION:

DATE PROGRAMMED:

VFD-PTD-236HE-2

05/10/16

DRIVE FACTORY PROGRAMMED

VAV w/ PRESSURE TRANSDUCER

LD20871

FIGURE 1 - 

WARNING LABEL ON UNIT/VFD FOR 

VAV WITH PRESSURE TRANSDUCER

Units with a VAV option have a factory-wired differ-

ential pressure transducer mounted inside the VFD 

control box. The transducer senses gage pressure (stat-

ic) and converts this pressure difference to an analog 

signal. The unit is wired for 4-20mA output from the 

transducer. 
Transducer comes with two 1/4-inch OD pressure fit-

tings and accepts field provided 1/4-inch push-on tub-

ing for lengths of up to 300 feet. The positive (HIGH) 

and negative (LOW) pressure ports are indicated on 

the transducer. Connect unit RETURN AIR tubing to 

negative (LOW) fitting and SUPPLY AIR tubing to 

positive (HIGH) fitting.

• 

Only on 208/230-460 VAC units; not on 575 VAC

• 

Parameters 4009 and 4011 are factory set at  

0.5 ”WC. These are field adjusted points that need 

to be adjusted at start-up. These setpoints are 

based upon system requirements.

Example:

 If the Supply Duct Static Pressure was 

designed for 1.0 "WC, both Parameters 4009 and 

4011 need set to 1. Adjust Parameters 4009 and 

4011 up or down accordingly until the required 

setpoint is achieved. Once the setpoint is adjusted, 

please document Parameters 4009 and 4011 for 

future reference.

The VFD setpoint should never be ad-

justed to be greater than the duct system's 

or unit's maximum design pressures.

• 

The differential pressure transducer will provide a 

signal to the VFD, and the VFD will control to the 

setpoint parameters 4009 and 4011

• 

Only use the 24VDC from the VFD (Term. 9) to 

the differential pressure transducer (Term. Exc.)

• 

Term. 2 from the VFD will be wired to the differ-

ential pressure transducer (Term. COM)

• 

The Term. OUT on the differential pressure trans-

ducer is not wired

• 

The jumper on the VFD, AI1, needs to be set to 

4-20Ma

• 

The VFD is enabled by the Evaporator Fan VFD 

Relay (RVFD)

• 

If the VAV option is not selected, the unit will 

have Discrete 2 Speed Fan Control by default for 

all units 10 tons or larger

DISCRETE 2 SPEED FAN CONTROL

FOR TECHNICAL SUPPORT, CALL: 877-329-7430

STK-VFD

VFD FACTORY PROGRAMMED

NO FIELD PROGRAMMING REQUIRED

JOHNSON CONTROLS, AJAX, CANADA

VFD PART #:

VFD APPLICATION:

DATE PROGRAMMED:

VFD-2DS-236HE-2

05/10/16

DRIVE FACTORY PROGRAMMED

2 DISCRETE SPEED

LD20872

FIGURE 2 - 

WARNING LABEL ON UNIT/VFD FOR 

DISCRETE 2 SPEED FAN CONTROL

The Discrete 2 Speed Fan Control is available on all 

DSV and CSV units 10 tons or larger. For DSH units, it 

is only available on the 10-ton units.

Содержание VFD-2DS-234HE-2

Страница 1: ...E FOR D SERIES DSV DSH AIR COOLED SELF CONTAINED UNITS B STYLE AND C SERIES CSV WATER COOLED SELF CONTAINED UNITS B STYLE Issue Date October 6 2016 INDOOR PACKAGED EQUIPMENT INSTALLATION OPERATION NEW...

Страница 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Страница 3: ...controls com It is the responsibility of rigging lifting and operating service personnel to verify the applicability of these documents to the equipment If there is any question regarding the applicab...

Страница 4: ...tor 236HE 3 0 HP Motor 237HE 5 0 HP Motor 238HE 7 5 HP Motor 239HE 10 0 HP Motor 1 2 3 4 5 6 7 8 9 10 11 12 13 VFD PTD 234HE 2 A Product Category VFD VFD Program Parameter Set VFD Option PTD VAV with...

Страница 5: ...ntrol 8 FIGURE 3 VFD Keypad 9 FIGURE 4 VFD Keypad and Ethernet Connector 9 FIGURE 5 Connecting Negative and Positive Side Fittings 10 FIGURE 6 VFD Grille Cover 10 FIGURE 7 Input Output Diagram 11 FIGU...

Страница 6: ...JOHNSON CONTROLS 6 FORM 145 13 NO1 ISSUE DATE 10 06 2016 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 7: ...ided and routed from condenser to evaporator SECTION 1 INSTALLATION DO NOT enter Setup mode when power ing on the VFD There are two main VFD options Differ ential Pressure Transducer and Discrete 2 Sp...

Страница 8: ...fitting Only on 208 230 460 VAC units not on 575 VAC Parameters 4009 and 4011 are factory set at 0 5 WC These are field adjusted points that need to be adjusted at start up These setpoints are based...

Страница 9: ...60hz Set at parameter 1204 24 VDC applied to terminal 4 and 6 of VFD VFD KEYPAD VFD requires a keypad to program the VFD Once the VFD is programmed the keypad is not required in or der to operate the...

Страница 10: ...sure the tubes are secure inside duct and firmly con nected to transducer fitting otherwise unit will not op erate as intended INSTALL GRILLE COVER When unit is wired and push on tubing has been con n...

Страница 11: ...ner the setpoint value is displayed It goes from 0 to 100 That is the actual setpoint for the controller Setpoint can be 0 which is 0 0 WC or 100 which is 2 5 WC Example 20 corresponds to 0 5 WC setpo...

Страница 12: ...K SELECT 1 ACT1 4016 ACT1 INPUT 1 AI1 4018 ACT1 MIN 20 4019 ACT1 MAX 100 Table 2 FACTORY PARAMETERS FOR 2 SPEED APPLICATION 208 230 460 VAC ABB ACS320 PARAMETER DESCRIPTION VALUE GROUP 99 9901 LANGUAG...

Страница 13: ...T SPEED 2 35 See Note 1204 CONSTANT SPEED 3 0 1205 CONSTANT SPEED 4 60 NOTE If only one speed fan operation is wanted adjust to 60 Table 4 DRIVE DEPENDENT PARAMETERS GROUP 99 VFD PROGRAM PART AJAX MOT...

Страница 14: ...A1 6 575 3 60 2 30 VFD 2DS 236HE 2 MTR 236HE EM3211T ACS320 03U 10A8 2 208 230 3 60 3 00 8 50 1765 VFD 2DS 236HE 4 ACS320 03U 05A6 4 460 3 60 4 20 VFD 2DS 236HE 5 MTR 536HE EM3211T 5 ACS250 03U 04A1 6...

Страница 15: ...NO1 ISSUE DATE 10 06 2016 3 LD20867 Figure 9 EVAPORATOR VFD OPTION FOR DUCT STATIC PRESSURE WIRING SCHEMATIC 208 230V 460V 3PH 60HZ LD20868 Figure 10 EVAPORATOR VFD OPTION FOR DISCRETE 2 SPEED WIRING...

Страница 16: ...sylvania USA 17405 1592 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2016 www johnsoncontrols com ALL RIGHTS RESERVED Form 145 13 NO1 1016 Issue Date Octo...

Отзывы: