JOHNSON CONTROLS
12
FORM 145.13-NO1
ISSUE DATE: 10/06/2016
SECTION 2 - OPERATION
PARAMETER
DESCRIPTION
VALUE
GROUP 20
2003
MAX CURRENT
DRIVE DEPENDENT
2007
MINIMUM FREQUENCY
30 HZ
GROUP 34
3403
SIGNAL 1 MAX
60 HZ
3405
OUTPUT 1 UNIT
3:
(HZ)
3407
OUTPUT 1 MAX
60
3416
SIGNAL 3 MIN
20
3419
OUTPUT 3 UNIT
59:
(in WC)
3421
OUTPUT 3 MAX
2.5
GROUP 40
4006
UNITS
59:
(in WC)
4007
UNIT SCALE
2
4008
0% VALUE
0
4009
100% VALUE
FIELD SET (DEFAULT 0.5)
4010
SETPOINT SELECTION
19:
(INTERNAL)
4011
INTERNAL SETPOINT
FIELD SET (DEFAULT 0.5)
4012
SETPOINT MIN
0
4013
SETPOINT MAX
100
4014
FBK SELECT
1:
(ACT1)
4016
ACT1 INPUT
1:
(AI1)
4018
ACT1 MIN
20
4019
ACT1 MAX
100
TABLE 2 -
FACTORY PARAMETERS FOR 2 SPEED APPLICATION 208/230 & 460 VAC (ABB ACS320)
PARAMETER
DESCRIPTION
VALUE
GROUP 99
9901
LANGUAGE
0:
(ENGLISH)
9902
APPLICATION MACRO
1:
(HVAC DEFAULT)
9905
MOTOR NOMINAL VOLTAGE
MOTOR NAMEPLATE
9906
MOTOR NOMINAL CURRENT
MOTOR NAMEPLATE
9907
MOTOR NOMINAL FREQUENCY
MOTOR NAMEPLATE
9908
MOTOR NOMINAL SPEED
MOTOR NAMEPLATE
9909
MOTOR NOMINAL POWER
MOTOR NAMEPLATE
GROUP 10
1002
EXT2 COMMANDS
0:
(NOT SELECTED)
GROUP 11
1103
REF 1 SELECT
0:
(KEYPAD)
1106
REF 2 SELECT
0:
(KEYPAD)
GROUP 12
1201
CONSTANT SPEED SEL
7:
(DI1,DI2)
1202
CONSTANT SPEED 1
35 (*See Note)
1204
CONSTANT SPEED 2
60
TABLE 1
- VFD FACTORY PARAMETERS FOR VAV APPLICATION 208/230 & 460 VAC (ABB ACS320) (CONT'D)