Appendix 3: Regulatory Information
SIA Feature
Programming Section
Comments
Range/Default
Requirement
Entry delay(s)
Panel Settings>Panel Con-
figuration>Partition Configuration
> Entry Delay
(select 30s, 45s, 60s, 2mins,
3mins or 4mins)
Access to Entry and Exit delays and Bell
Time Out for the system
Note: Combined Entry delay and Com-
munications Delay (Abort Window) shall
not exceed 60s
Range: 30 sec. to 4 min.
Default: 30 sec.
Required
(programmable)
Abort Window for Non-Fire zones
Transmission Delay zone attribute must
be enabled
May be disabled by zone
or zone type Default:
Enabled
Required
Abort Window Time for Non-Fire
zones
Panel Settings>Panel Con-
figuration>System Configuration
> Communication Delay
Access to the programmable delay
before communicating alarms
Note:
Combined Entry delay and Com-
munications Delay (Abort Window) shall
not exceed 60s
Range: up to 45 sec.
Default: 30 sec.
Required
(programmable)
Abort Annunciation
An audible tone is generated when an
alarm is aborted during the Abort window
Annunciate that no alarm
was transmitted Default:
Enabled
Required
Communications Canceled Win-
dow
Panel Settings>Panel Con-
figuration>System Con-
figuration>Communication
Cancel Window
Access to the programmable Cancel Win-
dow.
Range: minimum 5 min.
Default: 5 min.
Note: minimum 5 min. for
UL installations
Required
Cancel Annunciation
Panel Settings>Panel Con-
figuration>System Configuration>
> Reporting
Access to the reporting code for Alarm
Canceled
Annunciate that a Cancel
was transmitted. Default:
Enabled
Required
Duress Feature
Do not derive code from an existing
Master/User code (e.g., Master code is
1234, the duress code should not be
1233 or 1235)
No automatic derivative of
another user code. No
duplicates with other user
codes
Default: Disabled
Allowed
Cross Zone Timer
Panel Settings>Panel Con-
figuration>Partition Configuration
>Cross Zone Delay
Access to the programmable Cross Zone
timer
May program Range: 001-
255 seconds. Default: 0
seconds
Allowed
Swinger Shutdown for Alarms
Panel Settings>Zones> Swinger
Shutdown
Access to the swinger shutdown limit for
zone alarms.
For all non-fire zones shut-
down at 1 or 6 trips
Default: 2 trips
Required
(programmable)
24 hour auto verified Fire
Access to 24 hour auto verified Fire
Activates If a restore is Not
received within the spe-
cified time Default: dis-
abled
Required
System Test:
Panel Settings> Dia-
gnostics> Sys-
tem>System Test
The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad lights turn
on. Refer to the User Manual.