Section 4: Programming Options
or 6 digits long. Program a 6-digit code only when using the
SIA reporting format. SIA uses this account number for all
partitions and system events. All other reporting formats use
a 4-digit system account number to report system main-
tenance (e.g., low battery, zone fault) and test transmission
events. To program a 4-digit system account number, enter
4 digits followed by FF.
Note:
This field is mandatory for communication with the
central monitoring station.
Default:
FFFFFF (disabled)
Valid range:
000001 to FFFFFF (Hexadecimal)
Event Reporting Format
This programming option is used to assign a communicator
format for transmitting zone alarms, tampers, faults and other
signals to the central monitoring station.
The following communicator formats are available:
Contact ID
Each of the digits indicate specific information about the sig-
nal. For example, if zone 1 is an entry/exit point, the event
code contains [34]. The central monitoring station would
receive the following:
*BURG - ENTRY/EXIT - 1 where the “1” indicates which
zone went into alarm.
SIA Format - Level 2 (Hard Coded)
The SIA communication format used in this product follows
the level 2 specifications of the SIA Digital Communication
Standard - October 1997. This format sends the account
code along with its data transmission. The transmission
appears similar to the following at the receiver:
N ri1 BA 01
N = New Event
ri1 = Partition /Area Identifier
BA = Burglary Alarm
01 = Zone 1
A system event uses the Area Identifier ri00.
Default:
SIA
Valid range:
SIA, CID
Bell Squawk on Arming
With this option enabled, the iotega chirps the sirens briefly
at full volume when the system is successfully armed. The
following options are provided to customize this option:
None: Sirens do not chirp when the system is armed.
All RF: Sirens chirp when armed by any wireless device.
RF Wireless Key: Sirens chirp only when armed by a wire-
less key.
RF Keypad: Sirens chirp only when armed by a wirefree
keypad.
Default:
RF Wireless Key
Valid range:
None, All RF, RF Wireless Key, RF Keypad
Chime on Zone Opening
When this option is enabled, the door chime sounds each
time an appropriately configured zone is opened.
The Door Chime attribute must be set to ON for every zone
that requires a chime on opening.
Default:
Enabled
Valid range:
Enabled, Disabled
Chime on Zone Closing
When this option is enabled, the door chime sounds each
time an appropriately configured zone is closed.
The Door Chime attribute must be set to ON for every zone
that requires a chime on opening.
Default:
Disabled
Valid range:
Enabled, Disabled
Trouble Beeps (Audible/ Auto-silent)
When this option is enabled, trouble beeps are not sounded
for any trouble condition except Fire/CO. For these, trouble
beeps sound every 10 seconds for the duration of the
trouble.
When this option is disabled, the system announces
troubles through the keypad buzzer every 10 seconds.
Pressing any key on the keypad silences the trouble beeps;
however, new troubles will restart trouble beeps. For
troubles that have been silenced but are still present, trouble
beeps restart daily at 7AM.
Default:
Enabled
Valid range:
Enabled, Disabled
Burglary Bell Time-out
This option determines the length of time the system siren
sounds for. System tampers follow this timer, but Fire alarms
and keypad buzzers do not.
Default:
4 Minutes
(Note: Burglary Bell Time-out shall be 4 minutes for UL/ULC)
Valid range:
0 to 255 Minutes
Fire Bell Time-Out
This option determines the maximum activation time for fire
alarm sirens. Each partition has a dedicated Fire Bell Time-
out timer.
Fire Bell Time-out takes priority over Burglary Bell Time-out.
Default:
5 Minutes (Note: Fire Bell Time-out shall be 5 minutes for UL/ULC)
Valid range: 0 to 255 Minutes
Audible Panic
This option is used to set internal buzzer behavior when the
Panic key is pressed. When set to Audible, pressing the
Panic key causes the buzzer to sound a series of 3 beeps to
acknowledge the alarm. The buzzer then sounds a steady
tone for the length of the bell time-out or until an access
code is entered.
When set to Silent, pressing the Panic key causes the
- 16 -