background image

TFP632

Page 6 of 8

4" (102 mm)

MAXIMUM

FRAME ARMS OF SPRINKLER

MUST BE INSTALLED

IN-LINE WITH PIPE RUN

UPPER

DECK

MODEL CC2

SPRINKLER

CEILING

FRAMING

2x FLOOR SOLID

WOOD JOISTS

NON-COMBUSTIBLE

INSULATION

COMPOSITE

WOOD JOISTS

1-1/2" (38 mm)

MINIMUM

CEILING

54" (1372 mm)

MAXIMUM

6" (152 mm)

MINIMUM

36" (915 mm)

MAXIMUM

UPPER

DECK

MODEL CC2

SPRINKLER

CEILING

FRAMING

54" (1372 mm)

MAXIMUM

CEILING

TOP CHORD GREATER

THAN 4" (102 mm) IN DEPTH

6" (152 mm)

MINIMUM

36" (915 mm)

MAXIMUM

FRAME ARMS OF SPRINKLER

MUST BE INSTALLED

IN-LINE WITH PIPE RUN

1-1/2" (38 mm)

MINIMUM

2" (51 mm)

MAXIMUM

FIGURE 6 

NON-COMBUSTIBLE INSULATION-FILLED UPPER DECK 

 SOLID WOOD OR COMPOSITE WOOD JOIST CONSTRUCTION 

CROSS SECTION ELEVATION VIEW 

STEEL PIPE

FIGURE 7 

OBSTRUCTED WOOD TRUSS CONSTRUCTION 

CROSS SECTION ELEVATION VIEW 

STEEL PIPE

Содержание tyco CC2

Страница 1: ...n dard spray sprinklers by design have an umbrella like spray pattern that poses a difficult challenge when trying to achieve effective coverage within a shallow space The Model CC2 Com bustible Conce...

Страница 2: ...4 1 2 in 114 mm Remote Area CPVC Pipe The remote area is 1000 ft 93 m NOTE The remote area does not include any additional sprinklers required for pro tection of BLAZE MASTER CPVC that is offset over...

Страница 3: ...DECK NON COMBUSTIBLE INSULATION 1 1 2 40 mm MINIMUM 6 152 mm MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN WHEN OFFSETT...

Страница 4: ...eatest and run parallel with the joist spaced at 31 ft 9 4 m width maximum to limit the area to a max imum of 1000 ft 93 m The draft curtain may be constructed of 1 4 in 6 4 mm plywood to prevent heat...

Страница 5: ...MAXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 54 1372 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6 152 mm MINIMUM 36 915 mm MAXIMUM M...

Страница 6: ...915 mm MAXIMUM UPPER DECK MODEL CC2 SPRINKLER CEILING FRAMING 54 1372 mm MAXIMUM CEILING TOP CHORD GREATER THAN 4 102 mm IN DEPTH 6 152 mm MINIMUM 36 915 mm MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INS...

Страница 7: ...e 9 for installation of the Model CC2 Sprinklers by applying the wrench to the sprinkler wrench flats only WRENCH RECESS USE END A ONLY 0 2 1 2 63 5 mm 3 1 2 88 9 mm 5 1 2 139 7 mm 7 1 2 190 5 mm 9 1...

Страница 8: ...should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before...

Отзывы: