Installation

The Model CC2 Sprinklers must be 

installed in accordance with this 

section.

General Instructions

The Model CC2 Sprinklers are to be 

installed upright and with their frame 

arms (Ref. Figure 1) in-line with the 

pipe run (Ref. Figures 2 through 7, as 

applicable).
Do not install any bulb type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in.  

(1,6 mm) for the 175°F (79°C) tempera-

ture rating.
A leak-tight 1/2 in. NPT sprinkler joint 

should be obtained with a torque of 7 to 

14 lb-ft (9,5 to 19,0 N

m). Higher levels 

of torque may distort the sprinkler inlet 

with consequent leakage or impairment 

of the sprinkler.
The Model CC2 Sprinklers must only 

be installed in the upright position with 

the deflector parallel to the upper deck. 

With pipe thread sealant applied to the 

pipe threads, use only the W-Type 6 

(End A) Sprinkler Wrench (Ref. Figure 

9) for installation of the Model CC2 

Sprinklers by applying the wrench to 

the sprinkler wrench flats only.

WRENCH RECESS

(USE END "A"

ONLY)

0"

2-1/2"

(63,5 mm)

3-1/2"

(88,9 mm)

5-1/2"

(139,7 mm)

7-1/2"

(190,5 mm)

9-1/2"

(241,3 mm)

12"

(304,8 mm)

14"

(355,6 mm)

16-1/2"

(419,1 mm)

(0 mm)

Maximum Allowable

Distance of Deflector

Above Bottom of

Obstruction

(B)

Distance from

Centerline of

Sprinkler to Side

of Obstruction

(A)

A≥3C or 3D

A≤24" (609,6 mm)

(Use dimension C or D, whichever is greater)

<12"
<(304,8 mm)
12" to <18"
(304,8 mm to <457,2 mm)
18" to <24"

(457,2 mm to <609,6 mm)
24" to <30"

(609,6 mm to <762,0 mm)
30" to <36"

(762,0 mm to <914,4 mm)
36" to <42"

(914,4 mm to <1066,8 mm)
42" to <48"
(1066,8 mm to <1219,2 mm)
48" to <54"
(1219,2 mm to <1371,6 mm)
54" to <60"
(1371,6 mm to <1524,0 mm)

NOTE:
WEB MEMBERS AND GUSSETS

SHALL NOT BE CONSIDERED

OBSTRUCTIONS PROVIDED THE

MINIMUM 4-1/2 INCH LATERAL

DISTANCE (FIG. 2) REQUIRED

BY THE SPECIFIC APPLICATION

LISTING IS MAINTAINED.

OBSTRUCTION

MODEL CC2

SPRINKLER

C

D

A

OBSTRUCTION

UPPER

DECK

LOWER

DECK

A

MODEL CC2

SPRINKLER

MODEL CC2

SPRINKLER

A

UPPER DECK

OR BOTTOM OF

NON-COMUSTIBLE

INSULATION

B

ELEVATION VIEW

PLAN VIEW

C

D

OBSTRUCTION

FIGURE 9 

W-TYPE 6 SPRINKLER 

WRENCH

FIGURE 8 

NFPA 13 OBSTRUCTION TO WATER DISTRIBUTION CRITERIA 

(REFERENCE)

Содержание tyco CC2

Страница 1: ...n dard spray sprinklers by design have an umbrella like spray pattern that poses a difficult challenge when trying to achieve effective coverage within a shallow space The Model CC2 Com bustible Conce...

Страница 2: ...4 1 2 in 114 mm Remote Area CPVC Pipe The remote area is 1000 ft 93 m NOTE The remote area does not include any additional sprinklers required for pro tection of BLAZE MASTER CPVC that is offset over...

Страница 3: ...DECK NON COMBUSTIBLE INSULATION 1 1 2 40 mm MINIMUM 6 152 mm MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN WHEN OFFSETT...

Страница 4: ...eatest and run parallel with the joist spaced at 31 ft 9 4 m width maximum to limit the area to a max imum of 1000 ft 93 m The draft curtain may be constructed of 1 4 in 6 4 mm plywood to prevent heat...

Страница 5: ...MAXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 54 1372 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6 152 mm MINIMUM 36 915 mm MAXIMUM M...

Страница 6: ...915 mm MAXIMUM UPPER DECK MODEL CC2 SPRINKLER CEILING FRAMING 54 1372 mm MAXIMUM CEILING TOP CHORD GREATER THAN 4 102 mm IN DEPTH 6 152 mm MINIMUM 36 915 mm MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INS...

Страница 7: ...e 9 for installation of the Model CC2 Sprinklers by applying the wrench to the sprinkler wrench flats only WRENCH RECESS USE END A ONLY 0 2 1 2 63 5 mm 3 1 2 88 9 mm 5 1 2 139 7 mm 7 1 2 190 5 mm 9 1...

Страница 8: ...should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before...

Отзывы: