Care and 

Maintenance

The Model CC2 Sprinklers must be 

maintained and serviced in accordance 

with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down the 

affected fire protection systems must 

be obtained from the proper authori ties 

and all personnel who may be affected 

by this action must be notified.
Sprinklers that are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush. 
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be re placed. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb. Refer to the Instal-

lation section for additional information.
The owner is responsible for the inspec-

tion, testing, and maintenance of their 

fire protection system and devices in 

compliance with this docu ment, as well 

as with the applicable standards of the 

NATIONAL FIRE PROTEC TION ASSO-

CIATION (e.g., NFPA 25), in addition to 

the standards of any other authorities 

having jurisdiction. Contact the install-

ing contractor or product manufacturer 

with any questions.
It is recommended that automatic 

sprinkler systems be inspected , tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and Part Number 

(P/N).

Sprinkler Assemblies with NPT 

Thread Connections

Specify: SIN (specify), K-factor 

(specify), Model CC2 Combustible 

Concealed Space Sprinkler, Specific 

Application, Upright, 175°F (79°C), 

P/N (specify):

TY2189, 4.2K . . . . . . . . . . . . . . . . . .51-311-1-175
TY3189, 5.6K . . . . . . . . . . . . . . . . . 51-301-1-175

Sprinkler Wrench:

Specify: W-Type 6 Sprinkler Wrench, 

P/N 56-000-6-387

Содержание tyco CC2

Страница 1: ...n dard spray sprinklers by design have an umbrella like spray pattern that poses a difficult challenge when trying to achieve effective coverage within a shallow space The Model CC2 Com bustible Conce...

Страница 2: ...4 1 2 in 114 mm Remote Area CPVC Pipe The remote area is 1000 ft 93 m NOTE The remote area does not include any additional sprinklers required for pro tection of BLAZE MASTER CPVC that is offset over...

Страница 3: ...DECK NON COMBUSTIBLE INSULATION 1 1 2 40 mm MINIMUM 6 152 mm MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN WHEN OFFSETT...

Страница 4: ...eatest and run parallel with the joist spaced at 31 ft 9 4 m width maximum to limit the area to a max imum of 1000 ft 93 m The draft curtain may be constructed of 1 4 in 6 4 mm plywood to prevent heat...

Страница 5: ...MAXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 54 1372 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6 152 mm MINIMUM 36 915 mm MAXIMUM M...

Страница 6: ...915 mm MAXIMUM UPPER DECK MODEL CC2 SPRINKLER CEILING FRAMING 54 1372 mm MAXIMUM CEILING TOP CHORD GREATER THAN 4 102 mm IN DEPTH 6 152 mm MINIMUM 36 915 mm MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INS...

Страница 7: ...e 9 for installation of the Model CC2 Sprinklers by applying the wrench to the sprinkler wrench flats only WRENCH RECESS USE END A ONLY 0 2 1 2 63 5 mm 3 1 2 88 9 mm 5 1 2 139 7 mm 7 1 2 190 5 mm 9 1...

Страница 8: ...should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before...

Отзывы: