background image

TFP632

Page 5 of 8

MODEL CC2

SPRINKLER

36" (915 mm)

MAXIMUM

FRAME ARMS OF

SPRINKLER MUST

BE INSTALLED

IN-LINE WITH

PIPE RUN

4-1/2" (114 mm) MINIMUM

FROM FACE OF WOOD TRUSS

OR TOP CHORD OF BAR JOIST

TOP CHORD

4" (102 mm)

OR LESS

12" (305 mm)

MINIMUM

1-1/2" (40 mm)

MINIMUM

4" (102 mm)

MAXIMUM

CEILING

UPPER DECK

FRAME ARMS OF SPRINKLER

MUST BE INSTALLED

IN-LINE WITH PIPE RUN

UPPER

DECK

CEILING

FRAMING

54" (1372 mm)

MAXIMUM

2x FLOOR SOLID

WOOD JOISTS

6" (152 mm)

MINIMUM

36" (915 mm)

MAXIMUM

MODEL CC2

SPRINKLER

1-1/2" (38 mm)

MINIMUM

2" (51 mm)

MAXIMUM

CEILING

FIGURE 4 

UNOBSTRUCTED WOOD TRUSS CONSTRUCTION  

OR UNOBSTRUCTED BAR JOIST CONSTRUCTION 

CROSS SECTION ELEVATION VIEW 

STEEL PIPE

FIGURE 5 

SOLID WOOD JOIST CONSTRUCTION  

CROSS SECTION ELEVATION VIEW 

STEEL PIPE

Содержание tyco CC2

Страница 1: ...n dard spray sprinklers by design have an umbrella like spray pattern that poses a difficult challenge when trying to achieve effective coverage within a shallow space The Model CC2 Com bustible Conce...

Страница 2: ...4 1 2 in 114 mm Remote Area CPVC Pipe The remote area is 1000 ft 93 m NOTE The remote area does not include any additional sprinklers required for pro tection of BLAZE MASTER CPVC that is offset over...

Страница 3: ...DECK NON COMBUSTIBLE INSULATION 1 1 2 40 mm MINIMUM 6 152 mm MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN WHEN OFFSETT...

Страница 4: ...eatest and run parallel with the joist spaced at 31 ft 9 4 m width maximum to limit the area to a max imum of 1000 ft 93 m The draft curtain may be constructed of 1 4 in 6 4 mm plywood to prevent heat...

Страница 5: ...MAXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 54 1372 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6 152 mm MINIMUM 36 915 mm MAXIMUM M...

Страница 6: ...915 mm MAXIMUM UPPER DECK MODEL CC2 SPRINKLER CEILING FRAMING 54 1372 mm MAXIMUM CEILING TOP CHORD GREATER THAN 4 102 mm IN DEPTH 6 152 mm MINIMUM 36 915 mm MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INS...

Страница 7: ...e 9 for installation of the Model CC2 Sprinklers by applying the wrench to the sprinkler wrench flats only WRENCH RECESS USE END A ONLY 0 2 1 2 63 5 mm 3 1 2 88 9 mm 5 1 2 139 7 mm 7 1 2 190 5 mm 9 1...

Страница 8: ...should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before...

Отзывы: