Table 4: Launch Issues Troubleshooting Information
Problem
Resolution
When I connect a MAP
Gateway to an LC IOM, it
does not power on.
Reason
The MAP Gateway requires an external power supply. The LC
IOM2723, IOM3733, and IOM3723 only have a 4 pin plug terminal
that does not provide power.
Resolution
• Connect the MAP gateway through the SA or FC bus when
connecting the IOM to a field controller.
• Use an external power source for any MAP Gateway that you
are connecting to the IOM.
Accessories
Table 5: MAP Gateway Accessories
Code
Description
MP-PRTKIT
Portable Kit (Includes MAP Gateway, RJ-12 cable, shell, and lanyard.)
MP-STAKIT-0
Stationary Cradle Only (Includes mounting bracket and field bus
adapter.)
MP-STAKIT-0Hx
Stationary Cradle Kit (Includes mounting bracket, field bus adapter,
and 100–240 VAC line voltage power supply.)
MP-STAFBA-0
Field Bus Adapter (Includes RJ-12 to 4-position Terminal Block
Adapter. Used for interfacing directly to MS/TP Field Bus.)
TL-PWRKIT-0A
Optional power supply (A = US and Canada).
TL-PWRKIT-0B
Optional power. (B = Australia, New Zealand, China, Turkey,
Germany, Hong Kong, Netherlands, Qatar, Saudi Arabia, Thailand,
UAE, UK).
TL-PWRKIT-0D
Optional power supply with interchangeable input blades for North
America, Europe, UK, Australia, and China. Input: 90 to 264 VAC,
50/60 Hz.
Note:
TL-PWRKIT-0A and TL-PWRKIT-0B are not rated for outdoor temperatures.
27
Mobile Access Portal Gateway Installation Guide