TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
46
Repair Information
If the TEC3000 Series Thermostat Controller fails to operate within its specifications, replace the unit. For a
replacement thermostat controller, contact the nearest Johnson Controls representative.
The controller is unable to access a
USB drive.
The drive is formatted as NTFS or
another unsupported format. The TEC
supports FAT16 and FAT32 formats
only.
Reformat the USB drive, or try a
different USB drive with a supported
format.
The USB drive is defective.
Try a different USB drive.
The controller displays
Board
Mismatch
.
The I/O board that the display board is
currently attached to does not match
the one that initially shipped with the
display board.
Attach the display board to the correct
I/O board.
A hardware failure is causing the two
boards to incorrectly identify
themselves.
Order replacement units and return the
affected devices to Johnson Controls
under the RMA program.
The controller displays
Controller
Fault
.
An internal fault was detected and the
controller was unable to recover.
Order replacement units and return the
affected devices to Johnson Controls
under the RMA program.
The Bell icon is displayed on the TEC
home page.
The fault has been detected on the
TEC.
See Table 12 for TEC fault causes and
resolution.
Partial Restore Complete
is displayed
when trying to restore settings from a
backup file.
Not all of the items in the backup file
have been restored. This error can be
caused by a value being out of the
minimum or maximum range in the
backup file. It may also occur if there
are inconsistencies in the reliability of a
setting in the backup file and on the
TEC device.
1. Create a Backup file on a USB
drive for the TEC that is showing
the issue.
2. Edit the backup file created in the
previous step on a computer to
reflect the preferred settings.
3. Verify that the modified values are
within minimum and maximum
range in the backup file.
4. Restore the settings from the newly
edited backup file on the TEC.
The temperature displayed is lower
than the actual room temperature.
Cold air drafts are entering the back of
the TEC.
Seal any holes behind the TEC to
reduce drafts.
Air is being forced through the TEC
from a nearby vent.
Move the location of the TEC or
change the venting to prevent air from
being forced through the TEC.
Supervisory Status = Offline
The supervisory controller is not
communicating with the TEC. The TEC
is not mapped to a JCI Supervisory
System. The WNC Gateway is not
communicating with the TEC.
1. Map the TEC into a JCI
Supervisory system.
2. Verify that the PAN’s WNC
Gateway is online.
3. Add ZFR Pro Routers/Repeaters
into the wireless system.
Some icons are hidden.
Lockout levels are used or the icons
are hidden due to the display settings.
See Table 5 for lockout levels and
access details.
1.
For ZFR Pro Wireless information, refer to the
WNC1800/ZFR182x Pro Series Wireless Field Bus System Technical
Bulletin (LIT-12012356).
Table 13: Troubleshooting Details
1
(Part 2 of 2)
Symptom
Probable Causes
Solutions