TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
37
Network Setup
FC Comm Mode
Wireless Field Bus
—
BACnet Instance ID*
1
0 to 4,914,302
* BACnet/MSTP communication mode
BACnet Device Address*
4
4 to 127
* BACnet/MSTP communication mode
BACnet Encoding Type
BACnet/MSTP Communication Mode
ISO 10646
(UCS-2)
ISO 10646 (UCS-2), ANSI X3.4
(US-ASCII)
Pan ID
65535
0 to 127
Equipment Setup
General
Unit Type
4-Pipe
2-Pipe, 4-Pipe, VAV
Valve Open Voltage
10 VDC
0 to 10 VDC
Valve Closed Voltage
0 VDC
0 to 10 VDC
Unoccupied Off Delay
10 minutes
0 to 10 minutes
Supply Fan
Supply Fan Type*
Single Speed
Single Speed, Multi-speed, Variable
Speed
* Fan coil units only
Start Voltage*
2 VDC
0 to 10 VDC
* Fan coil units only, variable speed fan
Full Speed Voltage*
10 VDC
0 to 10 VDC, proportional
* Fan coil units only, variable speed fan
Min Command*
20%
0 to 100%
* Fan coil units only, variable speed fan
Med Fan Speed On Cmd*
33%
0 to 100%
* Fan coil units only, multi-speed fan
High Fan Speed On Cmd*
66%
0 to 100%
* Fan coil units only, multi-speed fan
Reheat
Reheat Installed
No
Yes (True) or No (False)
Reheat Min Damper Position*
20%
0 to 100%
* VAV units with reheat installed
Reheat Fan Required*
No
Yes or No
* Fan coil units with reheat installed
Reheat Min On Time*
180 seconds
0 to 360 second
* Reheat installed
Reheat Min Off Time*
180 seconds
0 to 360 seconds
* Reheat installed
Changeover
Changeover Mode*
Auto
Auto, Cooling, or Heating
* Non 4-Pipe units
Supply Temp Type*
Analog Sensor
Analog Sensor, Heating NC, Cooling NC
* Changeover Mode = Auto
Changeover Setpoint*
55°F
40 to 200°F (4 to 93°C)
* Supply temp type = analog sensor
Table 10: Menus and Submenus (Part 5 of 8)
Level 1
Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1