TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
42
Troubleshooting
Thermistor
(2.2k ohm)
Adjustable
8 in. (203 mm)
TE-6341A-1
Duct
8 in. (203 mm)
TE-6341P-1
Flange
4 in. (102 mm)
TE-634GV-2
8 in. (203 mm)
TE-6341V-2
Outside air
3 in. (76 mm)
TE-6343P-1
Wall
N/A
TE-6344P-1
Well
8 in. (203 mm)
TE-6342M-1
6 in. (152 mm)
TE-634AM-2
Thermistor
(10k ohm)
Type II
Adjustable
8 in. (203 mm)
TE-6361A-1
Duct
4 in. (102 mm)
TE-636GM-1
8 in. (203 mm)
TE-6361M-1
TE-6361P-1
18 in. (457 mm)
TE-636JM-1
Flange
4 in. (102 mm)
TE-636GV-2
8 in. (203 mm)
TE-6361V-2
Flush
N/A
TE-6360F-0
TE-6360F-1
Outside air
3 in. (76 mm)
TE-6363P-1
Strap-mount
3 in. (76 mm)
TE-636S-1
Well
6 in. (152 mm)
TE-636AM-2
8 in. (203 mm)
TE-6362M-1
1.
Two TE-6001-8 Element Holders come with the platinum-equivalent averaging sensors. Order separately to use with a
nickel averaging sensor.
2.
Order the TE-1800-9600 Mounting Hardware separately to mount the wall unit to a wallbox.
Table 12: Fault List (Part 1 of 3)
Faults
Probable Causes
Solutions
Remote Zone Temp Fail
The External Zone Temperature sensor
has been disconnected or has failed.
1. Check the wiring of the sensor.
2. If intentionally disconnected, reset sensors
through the menu.
3. Order replacement units and return the
affected devices to Johnson Controls under
the RMA program.
Supply Temp Fail
The External Supply Temperature
sensor has been disconnected or has
failed.
1. Check the wiring of the sensor.
2. If intentionally disconnected, reset sensors
through the menu.
3. If problems persist, order replacement units
and return the affected devices to Johnson
Controls under the RMA program.
Internal Sensor Fail
An internal sensor has failed on the
TEC.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
Table 11: TE-6300 Series Temperature Sensors (Order Separately) (Part 2 of 2)
Sensor Type
Mounting Style
Probe Length
Product
Code Number