TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
24
Configuring Occupancy
To adapt to nearly any application, the TEC3000 controller supports a wide variety of occupancy sources, such as:
•
Local stand-alone weekly scheduler
•
External schedule from the BAS
•
Occupancy sensor (internal or remote)
•
Occupancy binary input (configurable)
•
Manual occupancy override
•
Temporary occupancy (by interacting with the screen while unoccupied)
•
Temporary occupancy binary input
Occupancy is determined using a top-down decision matrix as shown in Table 7.
Occ Setpoint Select =
Setpoint Offset and
Heat Cool Setpoint Mode =
Common Setpoint
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
also a common Setpoint Offset (warmer/cooler adjust) that is only applied to Common
Setpoint. Otherwise, this setting works the same as when Occ Setpoint Select = Setpoint
Offset and Heat Cool Setpoint Mode = Individual Setpoints.
Occ Setpoint Select = Min
and Max Setpoints and
Heat Cool Setpoint Mode =
Common Setpoint
In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
a configurable range for Common Setpoint, Min Setpoint, and Max Setpoint.
Table 6: Setpoint Operation
Mode of Setpoint
Operation
Details