background image

TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked

Multi-Stage Economizer Thermostat Controllers Installation Instructions

1

Applications

The TEC2604-4 and TEC2604-4+PIR Thermostat 
Controllers are BACnet® Master-Slave/
Token-Passing (MS/TP) networked devices that 
provide control of single- or multi-stage unitary rooftop 
units with economizers. The TEC2604-4+PIR 
Thermostat Controller provides advanced active 
occupancy logic that automatically switches occupancy 
from Occupied to Unoccupied as required by the 
presence of local activity. See the 

Occupancy Sensor 

Operation – TEC2604-4+PIR Thermostat Controller

 

section for more information.

The technologically advanced TEC2604-4 and 
TEC2604-4+PIR Thermostat Controllers feature a 
Building Automation System (BAS) BACnet MS/TP 
communication capability that enables remote 
monitoring and programming for efficient space 
temperature control.

The TEC2604-4 and TEC2604-4+PIR Thermostat 
Controllers feature an intuitive user interface with 
backlit display that makes setup and operation quick 
and easy. The thermostat controllers also employ a 
unique, Proportional-Integral (PI) time-proportioning 
algorithm that virtually eliminates temperature offset 
associated with traditional, differential-based 
thermostat controllers. Economizer functions include a 
0 to 10 VDC control signal, dry bulb changeover 
strategy, adjustable minimum position, and mixed air 
setpoint control. 

North American Emissions Compliance

United States 

Canada 

Installation

Location Considerations

Locate the TEC2604-4 or TEC2604-4+PIR Thermostat 
Controller:

on a partitioning wall, approximately 5 ft (1.5 m) 
above the floor in a location of average 
temperature

away from direct sunlight, radiant heat, outside 
walls, outside doors, air discharge grills, or 
stairwells, and from behind doors

away from steam or water pipes, warm air stacks, 
unconditioned areas (not heated or cooled), or 
sources of electrical interference

For integrated Passive Infrared (PIR) models, be sure 
that the thermostat controller is located centrally, where 
occupant movement is frequent.

IMPORTANT:

The TEC2604-4 and 

TEC2604-4+PIR Thermostat Controllers are 
intended to provide an input to equipment under 
normal operating conditions. Where failure or 
malfunction of the thermostat could lead to personal 
injury or property damage to the controlled 
equipment or other property, additional precautions 
must be designed into the control system. 
Incorporate and maintain other devices, such as 
supervisory or alarm systems or safety or limit 
controls, intended to warn of or protect against 
failure or malfunction of the thermostat. 

This equipment has been tested and found to 
comply with the limits for a Class A digital device 
pursuant to Part 15 of the FCC Rules. These limits 
are designed to provide reasonable protection 
against harmful interference when this equipment is 
operated in a commercial environment. This 
equipment generates, uses, and can radiate radio 
frequency energy and, if not installed and used in 
accordance with the instruction manual, may cause 
harmful interference to radio communications. 
Operation of this equipment in a residential area is 
likely to cause harmful interference, in which case 
the user will be required to correct the interference 
at his/her own expense.

This Class (A) digital apparatus meets all the 
requirements of the Canadian Interference-Causing 
Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte 
toutes les exigences du Règlement sur le matériel 
brouilleur du Canada.

TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked 
Multi-Stage Economizer Thermostat Controllers

Installation Instructions

TEC2604-4 and TEC2604-4+PIR

Part No. 24-9890-1079, Rev. B

Issued June 22, 2010

Supersedes January 27, 20

10

Содержание TEC2604-4

Страница 1: ...airwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infrared PIR models...

Страница 2: ...roller mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermosta...

Страница 3: ...nications Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 2 Carefully push any excess wire back into the wall Note Seal the hole in the wall with fireproof material to preven...

Страница 4: ...or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators Figure 5 Wiring the TEC2604 4 or TEC2604 4 PIR Thermostat Controller 24 VAC Thermo...

Страница 5: ...Short Indicates that the thermostat controller is scanning for the correct baud rate and that there is no communication Off Indicates that there is no power to the thermostat controller or that the M...

Страница 6: ...m Mode Schedule Status Occupied Unoccupied Override PIR Models Outside Temperature An outside air temperature sensor must be installed and connected Applicable Alarms The backlight lights up as an ala...

Страница 7: ...s in this section 1 To access the Installer Configuration Menu press and hold the MENU key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat...

Страница 8: ...which provides an alarm if a malfunction occurs Fan lock A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized This alarm is used in conjunction w...

Страница 9: ...mum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat controller Default off on Enabled off Disabled Heat max2 Sets the Occupied and Unoccupied maximum Heat...

Страница 10: ...activated by the equipment fan and limit control Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off on Extends fan operation by 60 seconds after a heating...

Страница 11: ...le in 5F 5C increments Unocc TM Sets the time delay between the moment when the thermostat controller toggles from the Occupied mode to the Unoccupied mode after the last motion is detected by the occ...

Страница 12: ...ed mode When the schedule is in the Unoccupied mode the minimum position is 0 Default 0 0 Range 0 0 to 100 0 equals 0 to 10 VDC output range OA Setting for 0 to 10 VDC Actuator Setting for 2 to 10 VDC...

Страница 13: ...ints Part 1 of 2 Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt ap...

Страница 14: ...on the display Press the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES...

Страница 15: ...ce with a programmable Digital Input Table 5 Troubleshooting Details1 Part 1 of 2 Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring A device may have been added or change...

Страница 16: ...TP Networked Multi Stage Economizer Thermostat Controllers Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay...

Страница 17: ...stry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that the BACnet Thermostats are in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004...

Отзывы: