background image

TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat

Controllers Installation Instructions

15

Table 3:  Accessories (Order Separately)

Code Number

Description

SEN-600-1

Remote Indoor Air Temperature Sensor

SEN-600-4

Remote Indoor Air Temperature Sensor with Occupancy Override and LED

TE-6361M-1

1

Duct Mount Air Temperature Sensor

TE-6363P-1

1

Outside Air Temperature Sensor

TEC-3-PIR

2

Cover with Occupancy Sensor

1.

Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the 

TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320)

 for more details.

2.

The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC2604-4 Thermostat 
Controller to provide occupancy sensing capability.

Table 4:  Alarm Messages

Display

Function

Frost

Indicates that the heating is energized by the low limit frost protection room temperature setpoint 5.6°C (42°F).

Fan Lock

Indicates that the heating and cooling action are locked out due to a defective fan operation.

Service

Indicates that there is a service alarm in accordance with a programmable Digital Input.

Filter

Indicates that the filter(s) is dirty in accordance with a programmable Digital Input.

Table 5:  Troubleshooting Details

1

 (Part 1 of 2)

Symptom

Probable Causes

Multiple 
Symptoms

Excessive bus errors may be occurring.

A device may have been added or changed with a duplicate address (may not be the same address as 
some devices having problems, and may have happened sometime before the problem was noticed).

Wiring errors or wire problems may exist.

The baud rate may have been changed on some devices on the network but not all devices.

Max_Master may have been changed incorrectly (may have happened sometime before the problem 
was noticed).

A download may be in progress.

There may be a fault at a device.

A repeater may be needed or may be configured incorrectly.

There may be a duplicate device object name or instance.

Poor Performance

See the probable causes listed previously in the 

Multiple Symptoms

 section of this table.

Excessive bus traffic may exist (bus overload).

The baud rate may be set too low.

There may be too many devices on the network.

There may be unaccounted devices on the network (not mapped to the NAE).

There may be unusually slow devices on the network or devices that are slow to respond.

Thermostat Goes 
Offline

See the probable causes listed previously in the 

Multiple Symptoms

 section of this table.

A power failure or other failure may have occurred at the thermostat controller.

Communication may have been disabled at the thermostat controller.

Содержание TEC2604-4

Страница 1: ...airwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infrared PIR models...

Страница 2: ...roller mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermosta...

Страница 3: ...nications Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 2 Carefully push any excess wire back into the wall Note Seal the hole in the wall with fireproof material to preven...

Страница 4: ...or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators Figure 5 Wiring the TEC2604 4 or TEC2604 4 PIR Thermostat Controller 24 VAC Thermo...

Страница 5: ...Short Indicates that the thermostat controller is scanning for the correct baud rate and that there is no communication Off Indicates that there is no power to the thermostat controller or that the M...

Страница 6: ...m Mode Schedule Status Occupied Unoccupied Override PIR Models Outside Temperature An outside air temperature sensor must be installed and connected Applicable Alarms The backlight lights up as an ala...

Страница 7: ...s in this section 1 To access the Installer Configuration Menu press and hold the MENU key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat...

Страница 8: ...which provides an alarm if a malfunction occurs Fan lock A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized This alarm is used in conjunction w...

Страница 9: ...mum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat controller Default off on Enabled off Disabled Heat max2 Sets the Occupied and Unoccupied maximum Heat...

Страница 10: ...activated by the equipment fan and limit control Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off on Extends fan operation by 60 seconds after a heating...

Страница 11: ...le in 5F 5C increments Unocc TM Sets the time delay between the moment when the thermostat controller toggles from the Occupied mode to the Unoccupied mode after the last motion is detected by the occ...

Страница 12: ...ed mode When the schedule is in the Unoccupied mode the minimum position is 0 Default 0 0 Range 0 0 to 100 0 equals 0 to 10 VDC output range OA Setting for 0 to 10 VDC Actuator Setting for 2 to 10 VDC...

Страница 13: ...ints Part 1 of 2 Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt ap...

Страница 14: ...on the display Press the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES...

Страница 15: ...ce with a programmable Digital Input Table 5 Troubleshooting Details1 Part 1 of 2 Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring A device may have been added or change...

Страница 16: ...TP Networked Multi Stage Economizer Thermostat Controllers Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay...

Страница 17: ...stry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that the BACnet Thermostats are in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004...

Отзывы: