background image

TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat 
Controllers Installation Instructions

16

Technical Specifications     

Thermostat Does 
Not Come Online

See the probable causes listed previously in the 

Multiple Symptoms

 section of this table.

A thermostat controller may be connected to the wrong bus.

A baud rate may be specified in the new thermostat controller that is incompatible with the running 
network.

No device on the network is configured to use a specific baud rate (normally the NAE), but all devices 
are set to use auto baud. At least one device, typically the bus supervisor (NAE), must have an 
assigned baud rate. Set the baud rate in the bus supervisor and set all other devices to auto baud.

1.

For common MS/TP troubleshooting information, refer to the 

MS/TP Communications Bus Technical Bulletin 

(LIT-12011034).

Table 5:  Troubleshooting Details

1

 (Part 2 of 2)

Symptom

Probable Causes

TEC2604-4 and TEC2604-4+PIR BACnet MS/TP Networked Multi-Stage Economizer Thermostat 
Controllers  (Part 1 of 2)

Power Requirements

19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or 
Safety Extra-Low Voltage (SELV)

Relay Contact Rating (Y1, Y2, G, W1, 
W2, and AUX)

19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A Inrush, Class 2 or SELV

Digital Inputs

Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2

Analog Inputs

Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative 
Temperature Coefficient (NTC) Thermistor Sensors

Wire Size

18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended

Temperature Sensor Type

Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC) 
Thermistor Sensor

Temperature Range

Backlit 
Display

-40.0°F/-40.0°C to 122.0°F/ 50.0°C in 0.5° Increments

Heating 
Control

40.0°F/4.5°C to 90.0°F/32.0°C

Cooling 
Control

54.0°F/12.0°C to 100.0°F/38.0°C

Accuracy

Temperature

±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated

Minimum Deadband

2F°/1C° between Heating and Cooling

Ambient Conditions

Operating

32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing

Storage

-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing

Содержание TEC2604-4

Страница 1: ...airwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infrared PIR models...

Страница 2: ...roller mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermosta...

Страница 3: ...nications Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 2 Carefully push any excess wire back into the wall Note Seal the hole in the wall with fireproof material to preven...

Страница 4: ...or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators Figure 5 Wiring the TEC2604 4 or TEC2604 4 PIR Thermostat Controller 24 VAC Thermo...

Страница 5: ...Short Indicates that the thermostat controller is scanning for the correct baud rate and that there is no communication Off Indicates that there is no power to the thermostat controller or that the M...

Страница 6: ...m Mode Schedule Status Occupied Unoccupied Override PIR Models Outside Temperature An outside air temperature sensor must be installed and connected Applicable Alarms The backlight lights up as an ala...

Страница 7: ...s in this section 1 To access the Installer Configuration Menu press and hold the MENU key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat...

Страница 8: ...which provides an alarm if a malfunction occurs Fan lock A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized This alarm is used in conjunction w...

Страница 9: ...mum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat controller Default off on Enabled off Disabled Heat max2 Sets the Occupied and Unoccupied maximum Heat...

Страница 10: ...activated by the equipment fan and limit control Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off on Extends fan operation by 60 seconds after a heating...

Страница 11: ...le in 5F 5C increments Unocc TM Sets the time delay between the moment when the thermostat controller toggles from the Occupied mode to the Unoccupied mode after the last motion is detected by the occ...

Страница 12: ...ed mode When the schedule is in the Unoccupied mode the minimum position is 0 Default 0 0 Range 0 0 to 100 0 equals 0 to 10 VDC output range OA Setting for 0 to 10 VDC Actuator Setting for 2 to 10 VDC...

Страница 13: ...ints Part 1 of 2 Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt ap...

Страница 14: ...on the display Press the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES...

Страница 15: ...ce with a programmable Digital Input Table 5 Troubleshooting Details1 Part 1 of 2 Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring A device may have been added or change...

Страница 16: ...TP Networked Multi Stage Economizer Thermostat Controllers Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay...

Страница 17: ...stry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that the BACnet Thermostats are in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004...

Отзывы: