TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat

Controllers Installation Instructions

7

PIR Diagnostic LEDs

The diagnostic LEDs inside the PIR lens brighten when 
movement is detected within the first 30 minutes after 
powerup. The LEDs do not light up or brighten after the 
initial 30-minute period.

Setpoints

The installer must be certain that the difference 
between the Occupied and Unoccupied setpoints can 
be recovered within a timely fashion to ensure 
occupancy comfort. In addition, the difference between 
the two setpoints must be large enough to warrant 
maximum energy savings.

These setpoints and Unoccupied time are adjustable to 
allow for customization, as dictated by the individual 
space requirements. See Figure 7 for an example of 
increasing room temperature setpoints.  

Configuring the TEC2604-4 or TEC2604-4+PIR 
Thermostat Controller

The TEC2604-4 and TEC2604-4+PIR Thermostat 
Controllers ship from the factory with default settings 
for all configurable parameters. The default settings are 
shown in Table 1. To reconfigure the parameters via the 
thermostat controller, follow the steps in this section.

1.

To access the Installer Configuration Menu, press 
and hold the 

MENU

 key for approximately 

8 seconds. 

Note:

If the 

Password

 parameter is configured, 

Password 0 appears on the thermostat controller 
display indicating that the configured password is 
required to proceed. Use the 

UP/DOWN

 arrow 

keys to indicate the configured password, then 
press the 

MENU

 key to proceed through the 

Installer Configuration Menu parameters.

2.

Once the Installer Configuration Menu begins, 
release and press the 

NO

 key to scroll through the 

parameters listed in Table 1. 

3.

When the desired parameter is displayed, use the 

YES

 key to choose the desired selection option. 

4.

Press the 

YES

 key and then the 

NO

 key to 

continue scrolling through the parameters.

When the thermostat controller is in the Installer 
Configuration Menu and left unattended for 
approximately 8 seconds, the thermostat controller 
reverts to the Status Display Menu.

Configuring Inputs DI1 and DI2

When DI1 and DI2 are configured for an alarm 
condition, an alarm condition is displayed locally when 
the input is closed. An alarm message is included on 
the scrolling Status Display Menu and when the 
message is displayed, the backlight momentarily 
lights up.

Figure 7: Increasing Room Temperature Setpoints

Occ Heat

= 72°F

Occ Cool

= 75°F

Unocc Heat

= 65°F

Room Temperature

FI

G

:r

m

_t

m

p

Содержание TEC2604-4

Страница 1: ...airwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infrared PIR models...

Страница 2: ...roller mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermosta...

Страница 3: ...nications Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 2 Carefully push any excess wire back into the wall Note Seal the hole in the wall with fireproof material to preven...

Страница 4: ...or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators Figure 5 Wiring the TEC2604 4 or TEC2604 4 PIR Thermostat Controller 24 VAC Thermo...

Страница 5: ...Short Indicates that the thermostat controller is scanning for the correct baud rate and that there is no communication Off Indicates that there is no power to the thermostat controller or that the M...

Страница 6: ...m Mode Schedule Status Occupied Unoccupied Override PIR Models Outside Temperature An outside air temperature sensor must be installed and connected Applicable Alarms The backlight lights up as an ala...

Страница 7: ...s in this section 1 To access the Installer Configuration Menu press and hold the MENU key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat...

Страница 8: ...which provides an alarm if a malfunction occurs Fan lock A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized This alarm is used in conjunction w...

Страница 9: ...mum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat controller Default off on Enabled off Disabled Heat max2 Sets the Occupied and Unoccupied maximum Heat...

Страница 10: ...activated by the equipment fan and limit control Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off on Extends fan operation by 60 seconds after a heating...

Страница 11: ...le in 5F 5C increments Unocc TM Sets the time delay between the moment when the thermostat controller toggles from the Occupied mode to the Unoccupied mode after the last motion is detected by the occ...

Страница 12: ...ed mode When the schedule is in the Unoccupied mode the minimum position is 0 Default 0 0 Range 0 0 to 100 0 equals 0 to 10 VDC output range OA Setting for 0 to 10 VDC Actuator Setting for 2 to 10 VDC...

Страница 13: ...ints Part 1 of 2 Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt ap...

Страница 14: ...on the display Press the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES...

Страница 15: ...ce with a programmable Digital Input Table 5 Troubleshooting Details1 Part 1 of 2 Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring A device may have been added or change...

Страница 16: ...TP Networked Multi Stage Economizer Thermostat Controllers Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay...

Страница 17: ...stry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that the BACnet Thermostats are in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004...

Отзывы: