background image

TEC2604-4 and TEC2604-4+PIR BACnet® MS/TP Networked Multi-Stage Economizer Thermostat 
Controllers Installation Instructions

8

Both inputs can be configured to the Selection Options 
included in Table 1.

 

 

Table 1:  Installer Configuration Menu  (Part 1 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Pswrd

Sets the protective access 
password to prevent unauthorized 
access to the Installer Configuration 
Menu.
Default: 

0

Note:

The default setting does not 

lock out access to the Installer 
Configuration Menu.

Range: 

0

 to 

1,000

Com addr

MS/TP address at the thermostat 
controller; coincides with the 
address assigned at the supervisory 
controller.
Default: 

254

Range: 

004 to 127

DI1

Configuration of Digital Input 1.
Default: 

None

(None):

 No function is associated with an input.

(RemNSB):

 Remote Night Setback (NSB) via a time clock input, an 

occupancy sensor, or from a voltage-free contact. 
Contact open = Occupied; contact closed = Unoccupied.

(RemOVR):

 Temporary occupancy request via a remote input. This 

override function is controlled by a manual remote occupancy 
override. When enabled, this condition disables the override 
capability of the thermostat controller.

(Filter):

 A Filter alarm is displayed. This alarm can be connected to 

a differential pressure switch that monitors a filter.

(Service): 

A Service alarm is displayed on the thermostat controller 

when the input is energized. Tie this input into the air conditioning 
unit control card, which provides an alarm if a malfunction occurs.

(Fan lock):

 A backlit flashing Fan lock alarm is displayed on the 

thermostat controller when the input is not energized. This alarm is 
used in conjunction with a local airflow sensor connected to the 
input. The thermostat controller heating or cooling action is locked 
out if no airflow is detected 10 seconds after the fan (Terminal G) is 
energized. Contact open = no airflow; contact closed = airflow 
present.

DI2

Configuration of Digital Input 2.
Default: 

None

(None):

 No function is associated with an input.

(RemNSB):

 Remote Night Setback (NSB) via a time clock input, an 

occupancy sensor, or from a voltage-free contact. 
Contact open = Occupied; contact closed = Unoccupied.

(RemOVR):

 Temporary occupancy request via a remote input. This 

override function is controlled by a manual remote occupancy 
override. When enabled, this condition disables the override 
capability of the thermostat controller.

(Filter):

 A Filter alarm is displayed. This alarm can be connected to 

a differential pressure switch that monitors a filter.

(Service): 

A Service alarm is displayed on the thermostat controller 

when the input is energized. Tie this input into the air conditioning 
unit control card, which provides an alarm if a malfunction occurs.

(Fan lock):

 A backlit flashing Fan lock alarm is displayed on the 

thermostat controller when the input is not energized. This alarm is 
used in conjunction with a local airflow sensor connected to the 
input. The thermostat controller heating or cooling action is locked 
out if no airflow is detected 10 seconds after the fan (Terminal G) is 
energized. Contact open = no airflow; contact closed = airflow 
present.

Содержание TEC2604-4

Страница 1: ...airwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infrared PIR models...

Страница 2: ...roller mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermosta...

Страница 3: ...nications Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 2 Carefully push any excess wire back into the wall Note Seal the hole in the wall with fireproof material to preven...

Страница 4: ...or above or other wiring that switches power to highly inductive loads such as contactors coils motors or generators Figure 5 Wiring the TEC2604 4 or TEC2604 4 PIR Thermostat Controller 24 VAC Thermo...

Страница 5: ...Short Indicates that the thermostat controller is scanning for the correct baud rate and that there is no communication Off Indicates that there is no power to the thermostat controller or that the M...

Страница 6: ...m Mode Schedule Status Occupied Unoccupied Override PIR Models Outside Temperature An outside air temperature sensor must be installed and connected Applicable Alarms The backlight lights up as an ala...

Страница 7: ...s in this section 1 To access the Installer Configuration Menu press and hold the MENU key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat...

Страница 8: ...which provides an alarm if a malfunction occurs Fan lock A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized This alarm is used in conjunction w...

Страница 9: ...mum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat controller Default off on Enabled off Disabled Heat max2 Sets the Occupied and Unoccupied maximum Heat...

Страница 10: ...activated by the equipment fan and limit control Fan del Fan delay extends fan operation after a heating or cooling cycle has ended Default off on Extends fan operation by 60 seconds after a heating...

Страница 11: ...le in 5F 5C increments Unocc TM Sets the time delay between the moment when the thermostat controller toggles from the Occupied mode to the Unoccupied mode after the last motion is detected by the occ...

Страница 12: ...ed mode When the schedule is in the Unoccupied mode the minimum position is 0 Default 0 0 Range 0 0 to 100 0 equals 0 to 10 VDC output range OA Setting for 0 to 10 VDC Actuator Setting for 2 to 10 VDC...

Страница 13: ...ints Part 1 of 2 Thermostat Display Description Press the MENU key while in the Status Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt ap...

Страница 14: ...on the display Press the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES...

Страница 15: ...ce with a programmable Digital Input Table 5 Troubleshooting Details1 Part 1 of 2 Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring A device may have been added or change...

Страница 16: ...TP Networked Multi Stage Economizer Thermostat Controllers Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay...

Страница 17: ...stry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that the BACnet Thermostats are in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004...

Отзывы: