TEC22x1-3 L
ON
W
ORKS
® Networked Single Stage Thermostats Installation Instructions
5
•
Use the
MENU
key to:
-
access the Main User Menu or to exit the menu
(See the
Main User Menu
section.)
-
access the Installer Configuration Menu or to
exit the menu (See the
Configuring the
TEC22x1-3 Thermostat
section.)
•
Use the
UP/DOWN
arrow keys to change the
configuration parameters and to activate a setpoint
adjustment.
Backlit Liquid Crystal Display (LCD)
The TEC22x1-3 thermostat includes a 2-line,
8-character backlit display. Low-level backlighting is
present during normal operation, and it brightens when
any user interface key is pressed. The backlight returns
to low level when the thermostat is left unattended for
45 seconds.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling:
•
The
FAN
LED is on when the fan is on.
•
The
HEAT
LED is on when heating is on.
•
The
COOL
LED is on when cooling is on.
Programming Overview
There are three menus used to view, program, and
configure the TEC22x1-3 thermostat.
The
Status Display Menu
is displayed during normal
thermostat operation. This menu continuously scrolls
through the following parameters:
•
Room Temperature
•
Clock (TEC2261-3 only)
•
System Mode
•
Occupancy Status – Occupied/Unoccupied/
Override
•
Outdoor Temperature – An outdoor air temperature
sensor must be connected.
•
Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Note:
Press the YES/SCROLL key to temporarily stop
this menu from scrolling.
The
Main User Menu
is used to access and change
the basic operating parameters of the thermostat.
Access this menu by pressing the
MENU
key during
normal thermostat operation.
The
Installer Configuration Menu
is used to set up
the thermostat for application-specific operation. To
access this menu, press and hold the
MENU
key for
approximately 8 seconds.
Configuring the TEC22x1-3 Thermostat
The TEC22x1-3 thermostat comes from the factory
with default settings for all configurable parameters.
The default settings are shown in Table 2. To
reconfigure the parameters via the thermostat, follow
the steps in this section.
1.
To access the Installer Configuration Menu, press
and hold the
MENU
key for approximately 8
seconds.
2.
Once the Installer Configuration Menu begins,
press the
NO
key to scroll through the parameters
listed in Table 2.
3.
When the desired parameter is displayed, use the
YES
key to choose the desired selection option.
4.
Press the
YES
key and then the
NO
key to
continue scrolling through the parameters.
When the thermostat is in the Installer Configuration
Menu and left unattended for approximately 8 seconds,
the thermostat reverts to the Status Display Menu.
To exit the Installer Configuration Menu any time, press
the
MENU
key, and at the exit prompt, press the
YES
key. To pass over a parameter without changing it,
press the
NO
key.
For additional information on commissioning and
configuring thermostats, adding thermostats to a
Network Automation Engine (NAE), thermostat
mapping, and remote themostat commanding, refer to
TEC226x-3 and TEC220x-3 Series L
ON
W
ORKS
®
Network Configurable Staged Thermostats Technical
Bulletin (LIT-12011197)
.
Configuring the Thermostat’s Neuron®
Identification
Press and hold the
UP/DOWN
arrow keys
simultaneously for 5 seconds to broadcast the
thermostat’s Neuron Identification on the L
ON
W
ORKS
network.
If the cover is removed, you can see a green LED
under the LON board flash when the thermostat
broadcasts the Neuron ID. The Neuron ID is on a label
on the Echelon® chip.
You cannot send the Neuron ID while in the Installer
Configuration menu.