® Networked Single Stage Thermostats Installation Instructions 

7

Pwr del

2

Sets the delay time period at 
thermostat power up, or at each 
time power is removed and 
reapplied, before any operation 
(fan, heating, or cooling) is 
authorized. Also can be used to 
sequence the startup of multiple 
units in one location.
Default: 

10.0 sec

Range: 

10.0

 to 

120.0 sec

Frost pr

Provides a minimum heating 
setpoint of 42.0°F/5.5°C to prevent 
freezing in the zone controlled by 
the thermostat. 
Default: 

off

(on):

 Enabled

(off):

 Disabled

Heat max

3

Sets the Occupied and Unoccupied 
maximum Heating setpoint values.
Default: 

90.0°F/32.0°C

Range: 

40.0°F/4.5°C

 to 

90.0°F/32.0°C

Cool min

3

Sets the Occupied and Unoccupied 
minimum Cooling setpoint values.
Default: 

54.0°F/12.0°C

Range: 

54.0°F/12.0°C

 to 

100.0°F/37.5°C

Anticycl

Anti-Short Cycle timer sets the 
minimum on/off times for heating 
and cooling stages.
Default: 

2.0 min

Range: 

0.0

 to 

5.0 min

 adjustable in 1-minute increments

Set the anti-short cycle timer to 

0.0 min

 for equipment that already 

has its own anti-short cycle timer.

Heat cph

Sets the maximum number of 
Heating cycles per hour.
Default: 

4.0

Range: 

3.0

 to 

8.0

 cycles per hour

Cool cph

Sets the maximum number of 
Cooling cycles per hour.
Default: 

4.0

Range: 

3.0

 or 

4.0

 cycles per hour

Deadband

Sets the minimum deadband 
between the heating and cooling 
setpoints.
Default: 

2.0F°/1.0C°

Range: 

2.0F°/1.0C°

 to 

4.0F°/2.0C°

 adjustable in 1.0F°/0.5C° 

increments

Fan cont

Determines how the fan is activated 
in response to a call for heating.  
Fan cont applies to W1 and W2 and 
Fan Mode auto only.  Fan cont does 
not affect fan operation on a call for 
cooling (Y1 and Y2).
Default: 

on

(off):

  The thermostat will not activate the fan in response to a call 

for heating.  The fan is activated by the equipment fan and limit 
control.

(on):

 Enables the thermostat to activate the fan in response to a call 

for heating or cooling.

Fan del

Fan delay extends fan operation 
after a heating or cooling cycle has 
ended.
Default 

off

(on):

 Extends fan operation by 60 seconds after a heating or cooling 

cycle has ended.

(off):

 No extension of fan operation after a heating or cooling cycle 

has ended.
The fan delay is only active when the fan is in the Auto mode.

Table 2:  Installer Configuration Menu  (Part 2 of 3)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC22x1-3 LONWORKS

Страница 1: ...ions Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x1 3 thermostat on a par...

Страница 2: ...lly snap it into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing...

Страница 3: ...Bottom Connector MS OS Aux FIG trm_TEC22x1_3 L W Bus Terminals ON ORKS 2 3 4 5 6 7 11 12 13 14 15 16 10 Figure 6 Wiring the TEC22x1 3 Thermostat Cool 1 24 VAC Thermostat Power Heat 1 Y1 RC C RH W1 DI1...

Страница 4: ...segment a segment is a physically continuous length of wire The thermostat is not equipped with the ability to provide this termination therefore it cannot be located at the physical end of a LONWORK...

Страница 5: ...figuration Menu is used to set up the thermostat for application specific operation To access this menu press and hold the MENU key for approximately 8 seconds Configuring the TEC22x1 3 Thermostat The...

Страница 6: ...ostat RemNSB Remote Night Setback NSB via a time clock input an occupancy sensor or from a voltage free contact Contact open Occupied contact closed Unoccupied DI21 Configuration of Digital Input 2 De...

Страница 7: ...er Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cyc...

Страница 8: ...ge 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Discontinues cooling operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed...

Страница 9: ...the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied overri...

Страница 10: ...ress the YES key to change the occupied heating setpoint Press the NO key to advance to the unoccupied cooling setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to st...

Страница 11: ...the desired fan mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the fan mode selection menu Selecting Schedule TEC2261 3 Only Programming the Daily Sche...

Страница 12: ...for all the days of the week following the last entry for Sunday press the YES key to return to the Status Display Menu or press the NO key to start again at Monday Table 4 Programming the Daily Sched...

Страница 13: ...y to copy the schedule from the previous day Press the NO key to set a different schedule If the YES key was pressed the next prompt is for Wednesday Repeat the procedure for all days of the week Afte...

Страница 14: ...lacement thermostat contact the nearest Johnson Controls representative Table 7 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Ind...

Страница 15: ...equipment can start Cooling setpoint is satisfied Lower the cooling setpoint Cooling lockout attained Mode is locked out based on outside air temperature Change configuration parameter C Lock to valu...

Страница 16: ...to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditio...

Страница 17: ...ished in U S A www johnsoncontrols com TEC22x1 3 LONWORKS Networked Single Stage Thermostats Installation Instructions 17 Controls Group 507 E Michigan Street Milwaukee WI 53202 2006 Johnson Controls...

Отзывы: