background image

TEC22x1-3 L

ON

W

ORKS

® Networked Single Stage Thermostats Installation Instructions

8

TOccTime

Sets the duration of the Temporary 
Occupancy Time (when the 
thermostat is in the Unoccupied 
mode) when a Schedule Override 
Function is enabled using either the 
Main User Menu or DI1 or DI2 
configured as a temporary override 
remote contact (RemOVR).
Sets the effective duration of the 
Temporary heating or cooling 
setpoints set using the up/down 
arrow keys.
default: 

3.0 hrs

Range: 

0.0

 to 

12.0 hrs

 adjustable in 1-hour increments

Cal RS

Sets the desired room air 
temperature sensor calibration 
(offset). The offset can be added to 
or subtracted from the actual 
displayed room temperature.
Default: 

0.0F°/0.0C°C

Range: 

-5.0F°/-2.5C°

 to 

5.0F°/2.5C°

 adjustable in 1.0F°/0.5C° 

increments

Cal OS

Sets the desired outdoor air 
temperature sensor calibration 
(offset). The offset can be added to 
or subtracted from the actual 
displayed room temperature.
Default: 

0.0F°/0.0C°

Range: 

-5.0F°/-2.5C°

 to 

5.0F°2.5C°

 adjustable in 1.0F°/0.5C° 

increments

H lock

Discontinues heating operation in 
response to the outdoor air 
temperature. Requires that an 
outdoor air temperature sensor be 
installed and connected.
Default: 

120°F/49°C

Range: 

-15°F/-26°C

 to 

120°F/49°C

 adjustable in 5F°/5C° increments

C lock

Discontinues cooling operation in 
response to the outdoor air 
temperature. Requires that an 
outdoor air temperature sensor be 
installed and connected.
Default: 

-40°F/-40°C

Range: 

-40°F/-40°C

 to 

95°F/35°C

 adjustable in 5F°/5C° increments

2/4event

4

Sets the number of events within a 
24-hour period.
Default: 

2.0

(2.0):

 Two events (one occupied and one unoccupied) within a 

24-hour period

(4.0):

 Four events (two occupied and two unoccupied) within a 

24-hour period

Aux cont

Energizes peripheral devices 
(lighting equipment, exhaust fans, 
and economizers).
Default: 

n.o.

(n.c.):

 Contact open = Occupied; contact closed = Unoccupied

(n.o.):

 Contact closed = Occupied; contact open = Unoccupied

The contact toggles with the internal Occupied/Unoccupied 
schedule (or the NSB contact on one of the digital inputs, if used).

Prog rec

4

Provides the desired occupied 
temperature either at the start of the 
occupied schedule or after the 
occupied schedule begins.

Note:

Progressive recovery is 
disabled if either DI1 or DI2 
is configured as remote 
NSB.

Default: 

off

(on):

 Enabled (provides the desired occupied temperature at the 

start of the occupied schedule)

(off):

 Disabled (provides the desired occupied temperature after the 

occupied schedule begins)

Table 2:  Installer Configuration Menu  (Part 3 of 3)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC22x1-3 LONWORKS

Страница 1: ...ions Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x1 3 thermostat on a par...

Страница 2: ...lly snap it into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing...

Страница 3: ...Bottom Connector MS OS Aux FIG trm_TEC22x1_3 L W Bus Terminals ON ORKS 2 3 4 5 6 7 11 12 13 14 15 16 10 Figure 6 Wiring the TEC22x1 3 Thermostat Cool 1 24 VAC Thermostat Power Heat 1 Y1 RC C RH W1 DI1...

Страница 4: ...segment a segment is a physically continuous length of wire The thermostat is not equipped with the ability to provide this termination therefore it cannot be located at the physical end of a LONWORK...

Страница 5: ...figuration Menu is used to set up the thermostat for application specific operation To access this menu press and hold the MENU key for approximately 8 seconds Configuring the TEC22x1 3 Thermostat The...

Страница 6: ...ostat RemNSB Remote Night Setback NSB via a time clock input an occupancy sensor or from a voltage free contact Contact open Occupied contact closed Unoccupied DI21 Configuration of Digital Input 2 De...

Страница 7: ...er Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cyc...

Страница 8: ...ge 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Discontinues cooling operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed...

Страница 9: ...the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied overri...

Страница 10: ...ress the YES key to change the occupied heating setpoint Press the NO key to advance to the unoccupied cooling setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to st...

Страница 11: ...the desired fan mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the fan mode selection menu Selecting Schedule TEC2261 3 Only Programming the Daily Sche...

Страница 12: ...for all the days of the week following the last entry for Sunday press the YES key to return to the Status Display Menu or press the NO key to start again at Monday Table 4 Programming the Daily Sched...

Страница 13: ...y to copy the schedule from the previous day Press the NO key to set a different schedule If the YES key was pressed the next prompt is for Wednesday Repeat the procedure for all days of the week Afte...

Страница 14: ...lacement thermostat contact the nearest Johnson Controls representative Table 7 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Ind...

Страница 15: ...equipment can start Cooling setpoint is satisfied Lower the cooling setpoint Cooling lockout attained Mode is locked out based on outside air temperature Change configuration parameter C Lock to valu...

Страница 16: ...to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditio...

Страница 17: ...ished in U S A www johnsoncontrols com TEC22x1 3 LONWORKS Networked Single Stage Thermostats Installation Instructions 17 Controls Group 507 E Michigan Street Milwaukee WI 53202 2006 Johnson Controls...

Отзывы: