TEC22x1-3 L
ON
W
ORKS
® Networked Single Stage Thermostats Installation Instructions
8
TOccTime
Sets the duration of the Temporary
Occupancy Time (when the
thermostat is in the Unoccupied
mode) when a Schedule Override
Function is enabled using either the
Main User Menu or DI1 or DI2
configured as a temporary override
remote contact (RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the up/down
arrow keys.
default:
3.0 hrs
Range:
0.0
to
12.0 hrs
adjustable in 1-hour increments
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0F°/0.0C°C
Range:
-5.0F°/-2.5C°
to
5.0F°/2.5C°
adjustable in 1.0F°/0.5C°
increments
Cal OS
Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0F°/0.0C°
Range:
-5.0F°/-2.5C°
to
5.0F°2.5C°
adjustable in 1.0F°/0.5C°
increments
H lock
Discontinues heating operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default:
120°F/49°C
Range:
-15°F/-26°C
to
120°F/49°C
adjustable in 5F°/5C° increments
C lock
Discontinues cooling operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default:
-40°F/-40°C
Range:
-40°F/-40°C
to
95°F/35°C
adjustable in 5F°/5C° increments
2/4event
4
Sets the number of events within a
24-hour period.
Default:
2.0
(2.0):
Two events (one occupied and one unoccupied) within a
24-hour period
(4.0):
Four events (two occupied and two unoccupied) within a
24-hour period
Aux cont
Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default:
n.o.
(n.c.):
Contact open = Occupied; contact closed = Unoccupied
(n.o.):
Contact closed = Occupied; contact open = Unoccupied
The contact toggles with the internal Occupied/Unoccupied
schedule (or the NSB contact on one of the digital inputs, if used).
Prog rec
4
Provides the desired occupied
temperature either at the start of the
occupied schedule or after the
occupied schedule begins.
Note:
Progressive recovery is
disabled if either DI1 or DI2
is configured as remote
NSB.
Default:
off
(on):
Enabled (provides the desired occupied temperature at the
start of the occupied schedule)
(off):
Disabled (provides the desired occupied temperature after the
occupied schedule begins)
Table 2: Installer Configuration Menu (Part 3 of 3)
Parameter
Appearing
on Display
Description and Default
Selection Options