® Networked Single Stage Thermostats Installation Instructions 

3

Note:

For more details on wiring the 

L

ON

W

ORKS

 network, refer to the 

L

ON

W

ORKS

 Network Layout Technical Bulletin 

(LIT-1162150).

2.

Carefully push any excess wire back into the wall. 
Seal the hole in the wall with fireproof material to 
prevent drafts from affecting the ambient 
temperature readings.

3.

Reinsert the screw terminal blocks onto the PCB.

4.

Reattach the L

ON

W

ORKS

 communication wires to 

the LON terminal block. See Figure 5.

Note:

If inserting multiple wires into the terminals, 

be sure to properly twist wires together prior to 
inserting them into the terminal connectors.

5.

Reattach the thermostat cover to the mounting 
base (top side first).

6.

Use a Phillips-head screwdriver to reinstall the 
security screw on the bottom of the thermostat 
cover. 

 

 

  

 

Figure 5: Terminal Blocks

Y1

G

RC

C

RH

W1

DI1 DI2 RS

Scom

Four-Pole
Left Top Connector

Two-Pole
Right Top
Connector

Seven-Pole Bottom Connector

MS

OS

Aux

F

IG

:t

rm

_

T

E

C

2

2

x

1

_

3

L

W

 

Bus Terminals

ON

ORKS

2

3

4

5

6

7

11

12

13

14

15

16

10

Figure 6: Wiring the TEC22x1-3 Thermostat

Cool 1

24 VAC

Thermostat Power

Heat 1

Y1

RC

C

RH

W1

DI1

DI2

If using the same power source
for the thermostat and heating loads,
install a jumper across RC and RH.

OS

Scom

Remote

Monitoring

Supply

Temperature

Sensor

Aux

Aux

MS

Supervisory

Controller

F

IG

:w

rn

g

_

2

2

x

1

Auxiliary/

Outdoor

Air Sensor

Fan

G

RS

Isolated Contact
• Lighting
• On/Off Actuation
• Exhaust Fan

Remote

Room

Sensor

L

W

Bus Terminals

ON

ORKS

Table 1:  Terminal Identification (See Figure 5.)

Number

Label

Function

2

Y1

Energizes on a call for first-stage 
cooling.

3

G

Energizes fan in accordance with 
selected fan mode.

4

RC

24 VAC from equipment transformer

5

C

24 VAC (Common) from equipment 
transformer

6

RH

24 VAC for heating stage

7

W1

Energizes on a call for first-stage 
heating.

10

Aux

Auxiliary output

11

DI1

Configurable Digital Input 1

12

DI2

Configurable Digital Input 2

13

RS

Remote Room Air Temperature 
Sensor

14

Scom

Sensor Common

15

OS

Auxiliary/Outdoor Air Sensor

16

MS

Remote Monitoring Supply 
Temperature Sensor

Blank

Blank

L

ON

W

ORKS

 Bus

Содержание TEC22x1-3 LONWORKS

Страница 1: ...ions Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x1 3 thermostat on a par...

Страница 2: ...lly snap it into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing...

Страница 3: ...Bottom Connector MS OS Aux FIG trm_TEC22x1_3 L W Bus Terminals ON ORKS 2 3 4 5 6 7 11 12 13 14 15 16 10 Figure 6 Wiring the TEC22x1 3 Thermostat Cool 1 24 VAC Thermostat Power Heat 1 Y1 RC C RH W1 DI1...

Страница 4: ...segment a segment is a physically continuous length of wire The thermostat is not equipped with the ability to provide this termination therefore it cannot be located at the physical end of a LONWORK...

Страница 5: ...figuration Menu is used to set up the thermostat for application specific operation To access this menu press and hold the MENU key for approximately 8 seconds Configuring the TEC22x1 3 Thermostat The...

Страница 6: ...ostat RemNSB Remote Night Setback NSB via a time clock input an occupancy sensor or from a voltage free contact Contact open Occupied contact closed Unoccupied DI21 Configuration of Digital Input 2 De...

Страница 7: ...er Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cyc...

Страница 8: ...ge 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Discontinues cooling operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed...

Страница 9: ...the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied overri...

Страница 10: ...ress the YES key to change the occupied heating setpoint Press the NO key to advance to the unoccupied cooling setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to st...

Страница 11: ...the desired fan mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the fan mode selection menu Selecting Schedule TEC2261 3 Only Programming the Daily Sche...

Страница 12: ...for all the days of the week following the last entry for Sunday press the YES key to return to the Status Display Menu or press the NO key to start again at Monday Table 4 Programming the Daily Sched...

Страница 13: ...y to copy the schedule from the previous day Press the NO key to set a different schedule If the YES key was pressed the next prompt is for Wednesday Repeat the procedure for all days of the week Afte...

Страница 14: ...lacement thermostat contact the nearest Johnson Controls representative Table 7 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Ind...

Страница 15: ...equipment can start Cooling setpoint is satisfied Lower the cooling setpoint Cooling lockout attained Mode is locked out based on outside air temperature Change configuration parameter C Lock to valu...

Страница 16: ...to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditio...

Страница 17: ...ished in U S A www johnsoncontrols com TEC22x1 3 LONWORKS Networked Single Stage Thermostats Installation Instructions 17 Controls Group 507 E Michigan Street Milwaukee WI 53202 2006 Johnson Controls...

Отзывы: