® Networked Single Stage Thermostats Installation Instructions

12

Programming the Daily Schedule – Four-Event

The schedule-setting menu is used to enter the 
occupied and unoccupied states for each day of the 
week. The schedule-setting menu reflects either a 
two- or four-event schedule per day, based on what 
was selected in the 

2/4event 

parameter during the 

configuration process. If the schedule-setting menu 
does not reflect a four-event schedule, select four 
events in the 

2/4event

 parameter of the Installer 

Configuration Menu.

When changing the time, press the 

UP/DOWN

 arrow 

keys once to change the time in 1-minute increments; 
press and hold down the keys to change the time in 
30-minute increments.

Note:

Programming one of the digital inputs to remote 

NSB disables the menu.

To set the time schedule for a four-event schedule, 
follow the steps in Table 5. See Table 6 for an example 
of a four-event office schedule.     

Press the 

UP/DOWN

 arrow keys to 

set the unoccupied start time. Press 
the 

YES

 key to enter the time.

Press the 

YES

 key to set the 

schedule for Tuesday or press the 

NO

 key to advance to Wednesday.

Press the 

YES

 key to copy the 

schedule from the previous day. 
Press the 

NO

 key to set a different 

schedule.

If the 

YES

 key was pressed, the next 

prompt is for Wednesday. Repeat the 
procedure for the rest of the days of 
the week.

After setting the schedule for all the 
days of the week, following the last 
entry for Sunday, press the 

YES

 key 

to return to the Status Display Menu 
or press the 

NO

 key to start again at 

Monday.

Table 4:  Programming the Daily Schedule – 

Two-Event (Part 2 of 2)

Thermostat 
Display

Description

Unoccup 
12:00 AM 

Tuesday 
set? Y/N 

Copy Y/N 
previous 

Wednesda 
set? Y/N 

Exit? 
 Y/N

 

Table 5:  Programming the Daily Schedule – 

Four-Event (Part 1 of 2)

Thermostat 
Display

Description

Press the 

MENU

 key from the Status 

Display Menu to enter the Main User 
Menu.

Press the 

NO

 key to all prompts until 

the schedule set prompt appears on 
the display. Press the 

YES

 key to 

enter the scheduling menu.

Press the 

YES

 key to set the 

schedule for Monday or press the 

NO

 

key to advance to Tuesday.

Press the 

YES

 key to set the 

occupied start time for Monday or 
press the 

NO

 key to advance to 

Tuesday. Selecting 

NO

 will leave the 

thermostat in the unoccupied state 
for the entire day.

Press the 

UP/DOWN

 arrow keys to 

set the first occupied start time. Press 
the 

YES

 key to enter the time.

Press the 

UP/DOWN

 arrow keys to 

set the first unoccupied start time. 
Press the 

YES

 key to enter the time.

Press the 

UP/DOWN

 arrow keys to 

set the second occupied start time. 
Press the 

YES

 key to enter the time.

Press the 

UP/DOWN

 arrow keys to 

set the second unoccupied start time. 
Press the 

YES

 key to enter the time.

Press the 

YES

 key to set the 

schedule for Tuesday or press the 

NO

 key to advance to Wednesday.

RoomTemp
75.0

°

F

 

Schedule
set? Y/N 

Monday
set? Y/N 

Occupied
day? Y/N 

Occupied
12:00 AM 

Unoccup
12:00 AM 

Occupie2
12:00 AM

 

Unoccup2
12:00 AM

 

Tuesday
set? Y/N 

Содержание TEC22x1-3 LONWORKS

Страница 1: ...ions Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x1 3 thermostat on a par...

Страница 2: ...lly snap it into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing...

Страница 3: ...Bottom Connector MS OS Aux FIG trm_TEC22x1_3 L W Bus Terminals ON ORKS 2 3 4 5 6 7 11 12 13 14 15 16 10 Figure 6 Wiring the TEC22x1 3 Thermostat Cool 1 24 VAC Thermostat Power Heat 1 Y1 RC C RH W1 DI1...

Страница 4: ...segment a segment is a physically continuous length of wire The thermostat is not equipped with the ability to provide this termination therefore it cannot be located at the physical end of a LONWORK...

Страница 5: ...figuration Menu is used to set up the thermostat for application specific operation To access this menu press and hold the MENU key for approximately 8 seconds Configuring the TEC22x1 3 Thermostat The...

Страница 6: ...ostat RemNSB Remote Night Setback NSB via a time clock input an occupancy sensor or from a voltage free contact Contact open Occupied contact closed Unoccupied DI21 Configuration of Digital Input 2 De...

Страница 7: ...er Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cyc...

Страница 8: ...ge 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Discontinues cooling operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed...

Страница 9: ...the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied overri...

Страница 10: ...ress the YES key to change the occupied heating setpoint Press the NO key to advance to the unoccupied cooling setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to st...

Страница 11: ...the desired fan mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the fan mode selection menu Selecting Schedule TEC2261 3 Only Programming the Daily Sche...

Страница 12: ...for all the days of the week following the last entry for Sunday press the YES key to return to the Status Display Menu or press the NO key to start again at Monday Table 4 Programming the Daily Sched...

Страница 13: ...y to copy the schedule from the previous day Press the NO key to set a different schedule If the YES key was pressed the next prompt is for Wednesday Repeat the procedure for all days of the week Afte...

Страница 14: ...lacement thermostat contact the nearest Johnson Controls representative Table 7 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Ind...

Страница 15: ...equipment can start Cooling setpoint is satisfied Lower the cooling setpoint Cooling lockout attained Mode is locked out based on outside air temperature Change configuration parameter C Lock to valu...

Страница 16: ...to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditio...

Страница 17: ...ished in U S A www johnsoncontrols com TEC22x1 3 LONWORKS Networked Single Stage Thermostats Installation Instructions 17 Controls Group 507 E Michigan Street Milwaukee WI 53202 2006 Johnson Controls...

Отзывы: