TEC22x6(H)-4 and TEC22x6H-4+PIR Series L

ON

W

ORKS

® Network Thermostat Controllers with 

Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions

8

°C/°F

 key (hospitality models) changes the 

temperature scale to either Celsius or Fahrenheit 
and allows access to the Installer Configuration 
Menu. See the 

Configuring the TEC22x6(H)-4  and 

TEC22x6H-4+PIR Series Thermostat Controllers 

section.

Note:

For hospitality models, binary inputs can 

override the unoccupied mode to occupied mode.

UP/DOWN

 arrow keys change the configuration 

parameters and activate a setpoint adjustment.

Backlit Liquid Crystal Display (LCD)

The TEC22x6(H)-4 and TEC22x6H-4+PIR Series 
Thermostats include a 2-line, 8-character backlit 
display. Low-level backlighting is present during normal 
operation, and it brightens when any user interface key 
is pressed. The backlight returns to low level when the 
thermostat is left unattended for 45 seconds.

Light-Emitting Diodes (LEDs)

Three LEDs are included to indicate the fan status, call 
for heat, or call for cooling:

The fan LED 

 is on when the fan is on.

The heat LED 

 is on when heating is on.

The cool LED 

 is on when cooling is on.

Integrated PIR Sensor – 
TEC22x6H-4+PIR Series Thermostat 
Controllers

The integrated PIR sensor allows for automatic 
switching between fully adjustable Occupied and 
Stand-By temperature setpoints without user 
interaction. This feature generates incremental energy 
savings during scheduled occupied periods while the 
space is unoccupied.

Status Display Menu

The Status Display Menu is displayed during normal 
thermostat operation. This menu continuously scrolls 
through the following parameters:

Room Temperature (All Models) and Humidity 
(TEC2236-4, TEC2236H-4, TEC2236H-4+PIR, 
TEC2256-4, TEC2256H-4, and TEC2256H-4+PIR 
Models)

Note:

For models with dehumidification capability, 

the default setting is no humidity reading on the 
display (

%RH disp

 parameter is set to 

off

.) The 

%RH disp

 parameter must be set to 

on

 to display 

the current humidity reading.

System Mode

Occupancy Status
(Occupied/Unoccupied/Override)

Applicable Alarms (The backlight lights up as an 
alarm condition is displayed.)

Note:

An option is available within the Installer 

Configuration Menu to lock out the scrolling display and 
show only the 

Room Temperature

 parameter.

Status LED

The status LED shows the operational status of the 
thermostat. The Status LED is a small green light under 
the thermostat cover (under the L

ON

W

ORKS

 daughter 

board on the left edge when facing the thermostat).  

Dehumidification Operation – TEC2236(H)-4 
and TEC2256(H)-4 Models Only)

Upon detection of space humidity above the adjustable 
humidity setpoint as sensed by the internal humidity 
sensor, dehumidification activates. 

Note:

Dehumidification operates only in Cooling 

mode. Dehumidification does not operate in Off or 
Heating system mode.

Note:

A central network command can globally lock 

out dehumidification to all thermostats.

If the room temperature resides in the deadband 
between the Cooling and Heating Setpoint:

the thermostat forces the fan to low speed

the chilled water valve opens to the specified 
maximum value set by 

CoolMax

the thermostat stages heating to maintain space 
temperature at the cooling setpoint as sensed by 
the thermostat

If the room temperature falls below the current heating 
setpoint, the thermostat disables dehumidification.

Table 2:  Status LED Explanation

Status LED 
Condition

Explanation

Continuously 
On

The thermostat does not have an 
application loaded in its memory.

Flashing at a 
0.5 Hz rate

The thermostat has an application 
loaded in its memory but is not 
configured. Use a L

ON

W

ORKS

 network 

management tool to bind the thermostat 
to a L

ON

W

ORKS

 network.

Continuously 
Off

The thermostat has an application 
loaded in its memory and is bound to a 
L

ON

W

ORKS

 network.

Содержание TEC2216-4

Страница 1: ...e temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills stairwells or outside doors away from steam or water pipes warm air stacks unconditioned areas not...

Страница 2: ...right side of the thermostat mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the...

Страница 3: ...sh any excess wire back into the wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto...

Страница 4: ...2226H 4 TEC2226H 4 PIR TEC2236 4 TEC2236H 4 TEC2236H 4 PIR On Off or Floating Control TEC2246 4 TEC2246H 4 TEC2246H 4 PIR TEC2256 4 TEC2256H 4 TEC2256H 4 PIR Proportional Control 1 Fan H Fan H Fan H F...

Страница 5: ...Service Alarm Voltage Free Contact Remote NSB Motion Window LON LON Supervisory Controller Twist wires together before inserting them into the terminals Thermostat to Network Connection FIG 22x6wir L...

Страница 6: ...Off Control Two Pipe Applications Four Pipe Applications FIG TEC2226 H 4onoff 24 V Com 24 V Hot or 24 V Com 24 V Hot Cooling Valve or Heating Valve or Figure 9 Wiring TEC2226 H 4 and TEC2236 H 4 Therm...

Страница 7: ...ed at the physical end of a LONWORKS network segment unless a terminator is attached Refer to LONWORKS Network Layout Technical Bulletin LIT 1162150 for end of line solutions Setup and Adjustments The...

Страница 8: ...models with dehumidification capability the default setting is no humidity reading on the display RH disp parameter is set to off The RH disp parameter must be set to on to display the current humidit...

Страница 9: ...in Stand By mode for the 1 minute period The PIR functionality and local movement status LEDs are activated after the 1 minute warm up period has elapsed after the initial powering of the thermostat...

Страница 10: ...4 TEC2xx6H 4 PIR and TEC2xx7 4 Series Thermostat Controllers Application Note LIT 12011594 Occupied Stand By Unoccupied Stand By 2 Hours Unoccupied Time 6 Hours Time Last Movement Detected by PIR Dev...

Страница 11: ...Status Display Menu For additional information on commissioning and configuring thermostat controllers adding thermostat controllers to a Network Automation Engine NAE thermostat controller mapping a...

Страница 12: ...ol Sequences for 4 Pipe Applications Sequence Control Curves Terminals Used See Figure 6 On Off Control Floating Control Proportional Control 0 Cooling Only See Figure 15 10 NO Cool 11 NC Cool 10 Open...

Страница 13: ...Output FIG ht_on Figure 17 Cooling with Reheat Two or Four Pipe Applications Temperature Increase Increments of 1 F 0 5 C o o Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG cl_rht D...

Страница 14: ...the medium setting Figure 21 This operation applies to the occupied mode when the fan is set to Auto Figure 20 Heating Cooling with Reheat Four Pipe Applications Temperature Increase Increments of 1...

Страница 15: ...ime expires Window Cancels the thermostat heating or cooling action when a window is open The fan operation is only affected if the Fan Menu parameter is set to 4 On Auto and Auto is the selected fan...

Страница 16: ...and Reheat applications SS Supply Air Sensor Monitoring MenuScro Gives the option of having the display continuously scroll the parameters Default on on The scroll is active off The scroll is inactiv...

Страница 17: ...e selection option 0 Cooling Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only Choose the selection option 2 Cooling and Reheat when using a change...

Страница 18: ...he capacity of the cooling coil St By TM Sets stand by timer value when used with occupancy sensor time delay between moment where occupancy sensor detected the last movement in the area and the time...

Страница 19: ...efault 90 0 F 32 0 C Range 40 0 F 4 5 C to 90 0 F 32 0 C Cool min Sets the Occupied and Unoccupied minimum Cooling setpoint values Default 54 0 F 12 0 C Range 54 0 F 12 0 C to 100 F 37 5 C Pband Propo...

Страница 20: ...ion of the Temporary Occupancy Time when the thermostat controller is in the Unoccupied mode and a Schedule Override Function is enabled using either the Main User Menu or BI1 or BI2 is configured as...

Страница 21: ...mand Auto Fan Affects the auto mode of operation for the following Fan Menu parameter selection options only 2 Low Med High Auto 3 Low High Auto Default AS AS AD The fan is on Auto during occupied per...

Страница 22: ...t systems 1 10 seconds six cycles per minute for various equipment with solid state relays that withstand short duty cycles such as electric heat UI3 dis Displays the supply or changeover temperature...

Страница 23: ...lue 0 to access all levels of the menu Temperature setpoints revert to original value after a certain time Temporary setpoint active for a period of time set by parameter TOccTime To do a permanent ch...

Страница 24: ...mistor Wire Size Unshielded Twisted Pair 22 AWG 0 6 mm Diameter Minimum 18 AWG 1 0 mm Diameter Recommended LONWORKS Network Standard 64 Devices Maximum without a Repeater 127 Devices Maximum with a Re...

Отзывы: