background image

TEC22x6(H)-4 and TEC22x6H-4+PIR Series L

ON

W

ORKS

® Network Thermostat Controllers with

Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions

11

Configuring the TEC22x6(H)-4  and 
TEC22x6H-4+PIR Series Thermostat 
Controllers

The TEC22x6(H)-4 and TEC22x6H-4+PIR Series 
Thermostat Controllers are shipped with default 
settings for all configurable parameters. The default 
settings are shown in Table 5. To reconfigure the 
parameters via the thermostat, follow the steps in this 
section.

1.

To access the Installer Configuration Menu, press 
and hold the center key for approximately 
8 seconds.

Note:

If the 

Password

 parameter is configured, 

Password 0 appears on the thermostat controller 
display indicating that the configured password is 
required to proceed. Use the 

UP/DOWN

 arrow 

keys to indicate the configured password, then 
press the 

MODE

 key to proceed through the 

Installer Configuration Menu parameters.

2.

Once the Installer Configuration Menu begins, 
press and release the center key to scroll through 
the parameters listed in Table 5.

3.

When the desired parameter is displayed, use the 

UP/DOWN

 arrow keys to choose the desired 

selection option.

4.

Press and release the center key to continue 
scrolling through the parameters.

Note:

Pressing the 

FAN

 key during configuration 

restarts the list of displayed parameters at the first 
parameter listed in Table 5.

When the thermostat is in the Installer Configuration 
Menu and left unattended for approximately 8 seconds, 
the thermostat reverts to the Status Display Menu.

For additional information on commissioning and 
configuring thermostat controllers, adding thermostat 
controllers to a Network Automation Engine (NAE), 
thermostat controller mapping, and remote thermostat 
controller commanding, refer to 

TEC22x6(H)-4 and 

TEC22x6H-4+PIR L

ON

W

ORKS

® Network Thermostat 

Controllers with Dehumidification Capability, Fan 
Control, and Occupancy Sensing Capability Technical 
Bulletin (LIT-12011610)

.

Configuring the Thermostat Controller’s 
Neuron® Identification

Press and hold the 

UP/DOWN

 arrow keys 

simultaneously for 5 seconds to broadcast the 
thermostat controller’s Neuron Identification on the 
L

ON

W

ORKS

 network. 

If the cover is removed, you can see a green LED 
under the LON board flash when the thermostat 
broadcasts the Neuron ID. The Neuron ID is on a label 
on the Echelon® chip.

You cannot send the Neuron ID while in the Installer 
Configuration menu.

Configuring Inputs BI1, BI2, and UI3

When BI1 and BI2 are configured for an alarm 
condition, an alarm condition is displayed locally when 
the input is closed. An alarm message is included on 
the scrolling Status Display Menu and when the 
message is displayed, the backlight momentarily 
lights up.

The UI3 input provides changeover of hot/cold water 
switching or supply air temperature monitoring at the 
thermostat.

Each input can be configured to the Selection Options 
included in Table 5. 

Configuring the Sequence of Operation 
(SeqOpera)

Choose the appropriate sequence of operation. The 
modes presented are user-dependent on the sequence 
of operation selected. For 2-pipe applications using a 
COS, choose 

0 = Cooling only

. Changeover occurs 

between 

Cooling only

 and 

Heating only

. For example 

sequences of operation, see Figure 15 through 
Figure 20.     

Содержание TEC2216-4

Страница 1: ...e temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills stairwells or outside doors away from steam or water pipes warm air stacks unconditioned areas not...

Страница 2: ...right side of the thermostat mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the...

Страница 3: ...sh any excess wire back into the wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto...

Страница 4: ...2226H 4 TEC2226H 4 PIR TEC2236 4 TEC2236H 4 TEC2236H 4 PIR On Off or Floating Control TEC2246 4 TEC2246H 4 TEC2246H 4 PIR TEC2256 4 TEC2256H 4 TEC2256H 4 PIR Proportional Control 1 Fan H Fan H Fan H F...

Страница 5: ...Service Alarm Voltage Free Contact Remote NSB Motion Window LON LON Supervisory Controller Twist wires together before inserting them into the terminals Thermostat to Network Connection FIG 22x6wir L...

Страница 6: ...Off Control Two Pipe Applications Four Pipe Applications FIG TEC2226 H 4onoff 24 V Com 24 V Hot or 24 V Com 24 V Hot Cooling Valve or Heating Valve or Figure 9 Wiring TEC2226 H 4 and TEC2236 H 4 Therm...

Страница 7: ...ed at the physical end of a LONWORKS network segment unless a terminator is attached Refer to LONWORKS Network Layout Technical Bulletin LIT 1162150 for end of line solutions Setup and Adjustments The...

Страница 8: ...models with dehumidification capability the default setting is no humidity reading on the display RH disp parameter is set to off The RH disp parameter must be set to on to display the current humidit...

Страница 9: ...in Stand By mode for the 1 minute period The PIR functionality and local movement status LEDs are activated after the 1 minute warm up period has elapsed after the initial powering of the thermostat...

Страница 10: ...4 TEC2xx6H 4 PIR and TEC2xx7 4 Series Thermostat Controllers Application Note LIT 12011594 Occupied Stand By Unoccupied Stand By 2 Hours Unoccupied Time 6 Hours Time Last Movement Detected by PIR Dev...

Страница 11: ...Status Display Menu For additional information on commissioning and configuring thermostat controllers adding thermostat controllers to a Network Automation Engine NAE thermostat controller mapping a...

Страница 12: ...ol Sequences for 4 Pipe Applications Sequence Control Curves Terminals Used See Figure 6 On Off Control Floating Control Proportional Control 0 Cooling Only See Figure 15 10 NO Cool 11 NC Cool 10 Open...

Страница 13: ...Output FIG ht_on Figure 17 Cooling with Reheat Two or Four Pipe Applications Temperature Increase Increments of 1 F 0 5 C o o Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG cl_rht D...

Страница 14: ...the medium setting Figure 21 This operation applies to the occupied mode when the fan is set to Auto Figure 20 Heating Cooling with Reheat Four Pipe Applications Temperature Increase Increments of 1...

Страница 15: ...ime expires Window Cancels the thermostat heating or cooling action when a window is open The fan operation is only affected if the Fan Menu parameter is set to 4 On Auto and Auto is the selected fan...

Страница 16: ...and Reheat applications SS Supply Air Sensor Monitoring MenuScro Gives the option of having the display continuously scroll the parameters Default on on The scroll is active off The scroll is inactiv...

Страница 17: ...e selection option 0 Cooling Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only Choose the selection option 2 Cooling and Reheat when using a change...

Страница 18: ...he capacity of the cooling coil St By TM Sets stand by timer value when used with occupancy sensor time delay between moment where occupancy sensor detected the last movement in the area and the time...

Страница 19: ...efault 90 0 F 32 0 C Range 40 0 F 4 5 C to 90 0 F 32 0 C Cool min Sets the Occupied and Unoccupied minimum Cooling setpoint values Default 54 0 F 12 0 C Range 54 0 F 12 0 C to 100 F 37 5 C Pband Propo...

Страница 20: ...ion of the Temporary Occupancy Time when the thermostat controller is in the Unoccupied mode and a Schedule Override Function is enabled using either the Main User Menu or BI1 or BI2 is configured as...

Страница 21: ...mand Auto Fan Affects the auto mode of operation for the following Fan Menu parameter selection options only 2 Low Med High Auto 3 Low High Auto Default AS AS AD The fan is on Auto during occupied per...

Страница 22: ...t systems 1 10 seconds six cycles per minute for various equipment with solid state relays that withstand short duty cycles such as electric heat UI3 dis Displays the supply or changeover temperature...

Страница 23: ...lue 0 to access all levels of the menu Temperature setpoints revert to original value after a certain time Temporary setpoint active for a period of time set by parameter TOccTime To do a permanent ch...

Страница 24: ...mistor Wire Size Unshielded Twisted Pair 22 AWG 0 6 mm Diameter Minimum 18 AWG 1 0 mm Diameter Recommended LONWORKS Network Standard 64 Devices Maximum without a Repeater 127 Devices Maximum with a Re...

Отзывы: