background image

TEC22x6(H)-4 and TEC22x6H-4+PIR Series L

ON

W

ORKS

® Network Thermostat Controllers with 

Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions

14

Configuring Automatic Fan Speed

 

Use the 

Fan Menu

 parameter in the Installer 

Configuration menu to set the available Fan Mode 
options. Use the 

FAN

 key to select the desired Fan 

Mode option.

When selection option 

(2): Low-Med-High-Auto

 is 

chosen in the 

Fan Menu

 parameter, the fan operates 

as shown in Figure 21. When selection option 

(3): Low-High-Auto

 is chosen in the 

Fan Menu

 

parameter, the fan operates at only the low and high 
settings, ignoring the medium setting (Figure 21). This 
operation applies to the occupied mode when the fan is 
set to 

Auto

Figure 20: Heating/Cooling with Reheat, Four-Pipe Applications

Temperature Increase 

(Increments of 1 F/0.5 C)

o

o

Heating Setpoint

Device 
Closed

Device 
Closed

Device 

Opened

Cooling Setpoint

Device 

Opened

F

IG

:c

lh

t_

rh

t_

4

p

p

s

Deadband

Reheat
Output

On/Off, Floating,

or Proportional 

Outputs

Heating Output

Cooling output

Off

Off

On

On

Figure 21: Low-Med-High-Auto and Low-High-Auto Fan Operation

Temperature Deviation from Setpoint, F°

2.0F°/1.0C° to
5.0F°/2.5C°
Deadband

100%

0%

2.5

2.5

2.0

2.0

1.5

1.5

0.5

0.5

Heating 

Valve

Cooling

Valve

On

On

On

On

Off

Off

Off

Off

Low

Medium

Heating

Setpoint

Cooling

Setpoint

High

FI

G

:fn_

opr

tn

Fan

Speed

The fan is off 

between the 

heating and 

cooling setpoints 

if the 

 

parameter is 

set to 

.

Auto Fan

AS AD

Содержание TEC2216-4

Страница 1: ...e temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills stairwells or outside doors away from steam or water pipes warm air stacks unconditioned areas not...

Страница 2: ...right side of the thermostat mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the...

Страница 3: ...sh any excess wire back into the wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto...

Страница 4: ...2226H 4 TEC2226H 4 PIR TEC2236 4 TEC2236H 4 TEC2236H 4 PIR On Off or Floating Control TEC2246 4 TEC2246H 4 TEC2246H 4 PIR TEC2256 4 TEC2256H 4 TEC2256H 4 PIR Proportional Control 1 Fan H Fan H Fan H F...

Страница 5: ...Service Alarm Voltage Free Contact Remote NSB Motion Window LON LON Supervisory Controller Twist wires together before inserting them into the terminals Thermostat to Network Connection FIG 22x6wir L...

Страница 6: ...Off Control Two Pipe Applications Four Pipe Applications FIG TEC2226 H 4onoff 24 V Com 24 V Hot or 24 V Com 24 V Hot Cooling Valve or Heating Valve or Figure 9 Wiring TEC2226 H 4 and TEC2236 H 4 Therm...

Страница 7: ...ed at the physical end of a LONWORKS network segment unless a terminator is attached Refer to LONWORKS Network Layout Technical Bulletin LIT 1162150 for end of line solutions Setup and Adjustments The...

Страница 8: ...models with dehumidification capability the default setting is no humidity reading on the display RH disp parameter is set to off The RH disp parameter must be set to on to display the current humidit...

Страница 9: ...in Stand By mode for the 1 minute period The PIR functionality and local movement status LEDs are activated after the 1 minute warm up period has elapsed after the initial powering of the thermostat...

Страница 10: ...4 TEC2xx6H 4 PIR and TEC2xx7 4 Series Thermostat Controllers Application Note LIT 12011594 Occupied Stand By Unoccupied Stand By 2 Hours Unoccupied Time 6 Hours Time Last Movement Detected by PIR Dev...

Страница 11: ...Status Display Menu For additional information on commissioning and configuring thermostat controllers adding thermostat controllers to a Network Automation Engine NAE thermostat controller mapping a...

Страница 12: ...ol Sequences for 4 Pipe Applications Sequence Control Curves Terminals Used See Figure 6 On Off Control Floating Control Proportional Control 0 Cooling Only See Figure 15 10 NO Cool 11 NC Cool 10 Open...

Страница 13: ...Output FIG ht_on Figure 17 Cooling with Reheat Two or Four Pipe Applications Temperature Increase Increments of 1 F 0 5 C o o Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG cl_rht D...

Страница 14: ...the medium setting Figure 21 This operation applies to the occupied mode when the fan is set to Auto Figure 20 Heating Cooling with Reheat Four Pipe Applications Temperature Increase Increments of 1...

Страница 15: ...ime expires Window Cancels the thermostat heating or cooling action when a window is open The fan operation is only affected if the Fan Menu parameter is set to 4 On Auto and Auto is the selected fan...

Страница 16: ...and Reheat applications SS Supply Air Sensor Monitoring MenuScro Gives the option of having the display continuously scroll the parameters Default on on The scroll is active off The scroll is inactiv...

Страница 17: ...e selection option 0 Cooling Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only Choose the selection option 2 Cooling and Reheat when using a change...

Страница 18: ...he capacity of the cooling coil St By TM Sets stand by timer value when used with occupancy sensor time delay between moment where occupancy sensor detected the last movement in the area and the time...

Страница 19: ...efault 90 0 F 32 0 C Range 40 0 F 4 5 C to 90 0 F 32 0 C Cool min Sets the Occupied and Unoccupied minimum Cooling setpoint values Default 54 0 F 12 0 C Range 54 0 F 12 0 C to 100 F 37 5 C Pband Propo...

Страница 20: ...ion of the Temporary Occupancy Time when the thermostat controller is in the Unoccupied mode and a Schedule Override Function is enabled using either the Main User Menu or BI1 or BI2 is configured as...

Страница 21: ...mand Auto Fan Affects the auto mode of operation for the following Fan Menu parameter selection options only 2 Low Med High Auto 3 Low High Auto Default AS AS AD The fan is on Auto during occupied per...

Страница 22: ...t systems 1 10 seconds six cycles per minute for various equipment with solid state relays that withstand short duty cycles such as electric heat UI3 dis Displays the supply or changeover temperature...

Страница 23: ...lue 0 to access all levels of the menu Temperature setpoints revert to original value after a certain time Temporary setpoint active for a period of time set by parameter TOccTime To do a permanent ch...

Страница 24: ...mistor Wire Size Unshielded Twisted Pair 22 AWG 0 6 mm Diameter Minimum 18 AWG 1 0 mm Diameter Recommended LONWORKS Network Standard 64 Devices Maximum without a Repeater 127 Devices Maximum with a Re...