TEC22x6(H)-4 and TEC22x6H-4+PIR Series L
ON
W
ORKS
® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
17
Pipe No
Selectable number of pipes in the
system.
Default:
4.0
(2.0):
Limits the number of sequences of operation available from
0 to 3, and enables heat/cool operation from the same output.
(4.0):
Allows access to all sequences of operation from 0 to 5, and
enables heat/cool operation from different outputs.
CntrlTyp
Defines the control output for the
type of valves used in the
installation (TEC2226-4,
TEC2226H-4, TEC2226H-4+PIR,
TEC2236-4, TEC2236H-4, and
TEC2236H-4+PIR models only).
Default:
Floating
(On/Off):
For Normally Open (N.O.) or Normally Closed (N.C.)
24 VAC two-position valves.
(Floating):
For proportional three-wire control of 24 VAC floating
valves.
SeqOpera
Determines the sequence of
operation.
Default:
1
(0):
Cooling Only (Off-Cool). The default is
Cool
.
(1):
Heating Only (Off-Heat). The default is
Heat
.
(2):
Cooling and Reheat (Off-Auto*-Heat-Cool). The default is
Auto
.
(3):
Heating and Reheat (Off-Heat). The default is
Heat
.
(4):
Cool/Heat Four-Pipe (Off-Auto*-Heat-Cool). The default is
Auto
.
(5):
Cool/Heat Four-Pipe and Reheat (Off-Auto*-Heat-Cool). The
default is
Auto
.
* Auto can be disabled with the
AutoMode
parameter.
Note:
Choose the selection option
(0): Cooling Only
when using a
changeover sensor to allow changeover to occur between
Cooling
Only
and
Heating Only
. Choose the selection option
(2): Cooling
and Reheat
when using a changeover sensor to allow changeover
to occur between
Cooling and Reheat
and
Heating and Reheat
.
Fan Menu
Sets the Fan Mode options.
Default:
4
(0):
Low-Med-High: Three-speed configuration using three fan
relays (L-M-H). Default is
High
.
(1):
Low-High: Two-speed configuration using two fan relays (L-H).
Default is
High
.
(2):
Low-Med-High-Auto: Three-speed configuration with Auto Fan
speed mode using three fan relays (L-M-H). Default is
High
.
(3):
Low-High-Auto: Two-speed configuration with Auto Fan speed
mode using two fan relays (L-H). Default is
High
.
(4):
On-Auto: One-speed configuration, (H) Auto is for Fan on
demand and On is for Fan on all the time. Default is
Auto
.
Note: (2)
and
(3)
automatically cycle the fan through speeds,
based on the room temperature.
DHumidLCK
Locks out dehumidification
capability (TEC2236-4,
TEC2236H-4, TEC2236H-4+PIR,
TEC2256-4, TEC2256H-4, and
TEC2256H-4+PIR models).
Default:
on
(on):
Dehumidification Allowed
(off):
Dehumidification Locked Out
%RH set
Sets dehumidification setpoints
(TEC2236-4, TEC2236H-4,
TEC2236H-4+PIR, TEC2256-4,
TEC2256H-4, and
TEC2256H-4+PIR models). This
parameter can be used only if
dehumidification sequence is
enabled.
Default:
50.0% RH
Range:
30.0
to
95.0%.RH
Table 5: Installer Configuration Menu (Part 3 of 8)
Parameter
Appearing
on Display
Description and Default
Selection Options