TEC2103-1 Networked Multi-Stage Thermostat Installation Instructions 

Troubleshooting 

Table 6: N2 Bus Configuration Troubleshooting 

Error/Trouble 
Condition 

Possible Causes 

Solution 

Two or more controllers have the same 
address. 

Change each duplicate address to a unique 
number. 

TEC2103-1 cycles 
online and offline. 

There are Y or T taps or the repeater lost 
power or is wired incorrectly. 

Refer to the 

N2 Communication

s

 Bus Technical 

Bulletin (LIT-636018)

Two or more controllers have the same 
address. 

Change each duplicate address to a unique 
number. 

N2 Bus contains too many devices. 

The maximum of N2 devices allowed on the 
N2 Bus is as follows: 100 devices per NCM, 
32 devices per N30, 32 devices per N31, 
150 devices per the Companion/Facilitator 
system. 

TEC2103-1 does not have power. 

Apply power to the TEC2103-1. 

N2 cable runs are broken. 

Locate and correct the wiring. 

TEC2103-1 does not 
come online. 

Device type is incorrect. 

TEC2103-1 address must be VND device type. 

EOL jumpers on MM-CVT101 or NCM are 
not installed. 

Install EOL jumpers properly. 

MM-CVT101 is not plugged into the 
Personal Computer (PC) or 120 VAC 
source. 

Plug MM-CVT101 into PC or plug it into a 
120 VAC source. 

Wiring near the Bus is broken. 

Repair the wiring. 

Entire N2 Bus is offline. 

No point mapping entered.  

Define the BAS dataset. 

 

Table 7: Alarm Messages 

Display Function 

Frost ON 

Indicates heating is energized by the low limit frost protection (42

°

F [5.5

°

C]). 

Service 

Indicates there is a service alarm in accordance with one of the programmable Digital 
Inputs (DI1 or DI2). 

Filter 

Indicates the filter (or filters) are dirty in accordance with one of the programmable 
Digital Inputs (DI1 or DI2). 

Note:

 

There is a temperature alarm message that appears at the headend control should the setpoint not be reached 

within 45 minutes (there is no indication locally at the TEC2103-1). 

Содержание TEC2103-1

Страница 1: ...a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills st...

Страница 2: ...re or malfunction of the TEC2103 1 fig1 b Figure 1 Removing the Thermostat Cover PCB Locking Tabs fig2 b Figure 2 Opening the Thermostat PCB fig3 b Figure 3 Mounting the Thermostat Base fig4 b Figure...

Страница 3: ...sformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable digital input Configura...

Страница 4: ...5 to 32 C Setback Cooling SP a g Unoccupied Cooling SP ADI 6 N2 AO CSAD 54 to 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C...

Страница 5: ...selects System Mode On at the TEC keypad the TEC ends up with the System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode...

Страница 6: ...u item MENU key to access the Main User Menu or exit the menu down arrow key to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manua...

Страница 7: ...he configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the...

Страница 8: ...scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with...

Страница 9: ...tions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection...

Страница 10: ...erature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to al...

Страница 11: ...ess YES to store the address The display now shows the temporary occupancy time prompt See the Establishing the Temporary Occupancy Time ToccTime section for instructions Note Pressing the YES and NO...

Страница 12: ...ages prompt appears in the display Press YES to enter the setting cooling stages menu 2 Using the UP DOWN arrow keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the...

Страница 13: ...e Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu...

Страница 14: ...to advance to the unoccupied heating setpoint Use the UP DOWN arrow keys to set temperature Press YES to store value and advance to next menu Press YES to change the unoccupied heating setpoint Press...

Страница 15: ...ed periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods This is the default setting Sma...

Страница 16: ...able runs are broken Locate and correct the wiring TEC2103 1 does not come online Device type is incorrect TEC2103 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed I...

Страница 17: ...50082 2 EMC Immunity Pending FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules The...

Отзывы: