TEC2103-1 Networked Multi-Stage Thermostat Installation Instructions    

7

 

Programming Overview 

There are three menus used to view, program, and 
configure the TEC2103-1 thermostat: 

The 

Status Display Menu

 displays during normal 

thermostat operation. The menu continually scrolls 
through the following parameters. 

 Room 

Temperature 

 System 

Mode 

 

Schedule Status (Occupied/Unoccupied/Override 
[see Note]) 

Note: 

Override displays only when in the Override 

mode. 

 

Auxiliary Temperature (Displays outdoor or other 
auxiliary temperatures. Requires the sensor to be 
wired to the Auxiliary/Outdoor Air Sensor terminal 
OS [Figure 5]). The maximum temperature 
displayed is 122

°

F (50

°

C). The actual temperature 

may be above this point. 

 

Applicable Alarms (the backlight lights up as an 
alarm condition is displayed) 

To temporarily stop the scrolling, press the up 
arrow/SCROLL key. 

Use the 

Main User Menu

 to access and change the 

thermostat’s basic operating parameters. Access the 
menu by pressing the MENU key during normal 
thermostat operation. 

Use the 

Installer Configuration Menu

 to set up the 

thermostat for application specific operation. Access 
the menu by removing the front cover and pressing the 
configuration key, labeled CONFIG (Figure 7). 

Configuring the TEC2103-1 

The TEC2103-1 ships from the factory with default 
settings for all configurable parameters. The default 
settings are shown in Table 2. To reconfigure the 
parameters, follow the steps in this section for the 
corresponding parameters. The parameters must be 
set up first by accessing the Installer Configuration 
Menu. Access the Installer Configuration Menu by 
removing the front cover and pressing the 
configuration key (Figure 7). 

Exit the Installer Configuration Menu any time by 
pressing the MENU key and, at the exit prompt, 
pressing the YES key. To pass over a parameter 
without changing it press the NO key. 

When the thermostat is in the Installer Configuration 
Menu and left unattended for 45 seconds, it reverts to 
the Status Display Menu. 

Table 2: Installer Configuration Menu 

 

Remove the cover and press the 

CONFIG key from the Status Display 

Menu to enter the Installer 
Configuration Menu. 

 

Configures Digital Input 1 
Default: No Function 

(None) 

See the 

Configuring the Digital Inputs 

(DI1 and DI2) 

section

.

 

 

Configures Digital Input 2 
Default: No Function 

(None) 

See the 

Configuring the Digital Inputs 

(DI1 and DI2) 

section. 

 

Sets Keypad Lockout Level 
Default: No Lockout 

(0) 

See the 

Enabling the Keypad Lockout 

(Lockout) 

section

.

 

 

Sets Power-up Delay 
Default: Ten Seconds 

(10.0 sec) 

See the 

Setting the Power-up Delay 

(Pwr del) 

section

.

 

 

Enables/Disables Frost Protection 
Default: Disabled 

(Off) 

See the 

Enabling Frost Protection 

(Frost pr) 

section

.

 

 

Sets the Maximum Heating Setpoint 
Default: 

90.0

°

F (32.0

°

C)

 

See the 

Setting the Maximum Heating 

Setpoint (Heat max) 

section

.

 

 

Sets the Minimum Cooling Setpoint 
Default: 

54.0

°

F (12.0

°

C)

 

See the 

Setting the Minimum Cooling 

Setpoint (Cool min) 

section

.

 

 

Sets the Anti-Short Cycle Timer 
Default: Two Minutes 

(2.0 min)

 

See the 

Setting the Anti-Short Cycle 

Timer (Anticycl) 

section

.

 

 

Sets the Heating Cycles per Hour 
Default: Four 

(4.0) 

See the 

Setting the Maximum Heating 

Stage Cycles per Hour (Heat cph) 

section

.

 

 

Sets the Cooling Cycles per Hour 
Default: Four 

(4.0) 

See the 

Setting the Maximum Cooling 

Stage Cycles per Hour (Cool cph) 

section

.

 

Continued on next page . . . 

RoomTemp
75.0 

°

F

 

DI1
set? Y/N

 

DI2
set? Y/N 

Lockout
set? Y/N 

Pwr del
set? Y/N 

Frost pr
set? Y/N 

Heat max
set? Y/N 

Cool min
set? Y/N 

Cool cph
set? Y/N 

Heat cph
set? Y/N 

Anticycl
set? Y/N 

Содержание TEC2103-1

Страница 1: ...a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills st...

Страница 2: ...re or malfunction of the TEC2103 1 fig1 b Figure 1 Removing the Thermostat Cover PCB Locking Tabs fig2 b Figure 2 Opening the Thermostat PCB fig3 b Figure 3 Mounting the Thermostat Base fig4 b Figure...

Страница 3: ...sformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable digital input Configura...

Страница 4: ...5 to 32 C Setback Cooling SP a g Unoccupied Cooling SP ADI 6 N2 AO CSAD 54 to 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C...

Страница 5: ...selects System Mode On at the TEC keypad the TEC ends up with the System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode...

Страница 6: ...u item MENU key to access the Main User Menu or exit the menu down arrow key to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manua...

Страница 7: ...he configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the...

Страница 8: ...scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with...

Страница 9: ...tions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection...

Страница 10: ...erature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to al...

Страница 11: ...ess YES to store the address The display now shows the temporary occupancy time prompt See the Establishing the Temporary Occupancy Time ToccTime section for instructions Note Pressing the YES and NO...

Страница 12: ...ages prompt appears in the display Press YES to enter the setting cooling stages menu 2 Using the UP DOWN arrow keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the...

Страница 13: ...e Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu...

Страница 14: ...to advance to the unoccupied heating setpoint Use the UP DOWN arrow keys to set temperature Press YES to store value and advance to next menu Press YES to change the unoccupied heating setpoint Press...

Страница 15: ...ed periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods This is the default setting Sma...

Страница 16: ...able runs are broken Locate and correct the wiring TEC2103 1 does not come online Device type is incorrect TEC2103 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed I...

Страница 17: ...50082 2 EMC Immunity Pending FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules The...

Отзывы: