background image

 

4

    TEC2103-1 Networked Multi-Stage Thermostat Installation Instructions 

Table 1: N2 Bus Objects 

Point Name 

TEC Point 
Type/ 
Address 

N30/NAE 
Object 
Type 

BAS Model 
Point Type 

Override Range 

Room Temp

a

 

ADI-1 N2 

AI CSAD 32 to 122

°

F (0 to 50

°

C) 

Aux Temp / Outdoor Temp

a

 

ADI-2 N2 

AI CSAD -40 to

 

122

°

F (-40 to 50

°

C) 

Heating SP

a, g 

(Occupied Heating SP) 

ADI-3 N2 

AO CSAD 40 to 90

°

F (4.5 to 32

°

C) 

Cooling SP

a, g 

(Occupied Cooling SP) 

ADI-4 N2 

AO CSAD 54 to 100

°

F (12 to 37.5

°

C) 

Setback Heating SP

a, g

 

(Unoccupied Heating SP) 

ADI-5 N2 

AO CSAD 40 to 90

°

F (4.5 to 32

°

C) 

Setback Cooling SP

a, g

 

(Unoccupied Cooling SP) 

ADI-6 N2 

AO CSAD 54 to 100

°

F (12 to 37.5

°

C) 

Minimum Heat SP 

ADI-7 N2 

AI CSAD 40

°

F (4.5

°

C) 

Maximum Heat SP

a

 

ADI-8 N2 

AO CSAD 40 to 90

°

F (4.5 to 32

°

C) 

Minimum Cool SP

a

 

ADI-9 N2 

AI CSAD 54 to 100

°

F (12 to 37.5

°

C) 

Maximum Cool SP 

ADI-10 N2 

AO  CSAD  100

°

F (37.5

°

C) 

Fan

a

 

BD-1 

N2 BO 

CSBD 

0 = Auto, 1 = On 

Mode

a

 

BD-2 N2 

MSO

d, e

 

CSMS 

0 = Off, 1 = Cool, 2 = Heat, 3 = Auto 

Occupancy

a

 

BD-3 

N2 BO 

CSBD 

0 = Unoccupied, 1 = Occupied 

W1 State 

BD-4 

N2 BI 

CSBD 

0 = Off, 1 = On 

W2 State 

BD-5 

N2 BI 

CSBD 

0 = Off, 1 = On 

Y1 State 

BD-6 

N2 BI 

CSBD 

0 = Off, 1 = On 

Y2 State 

BD-7 

N2 BI 

CSBD 

0 = Off, 1 = On 

G State – Fan 

BD-8 

N2 BI 

CSBD 

0 = Off, 1 = On 

Temp Units

a, c

  

(Local Display Only) 

BD-9 N2 

BO 

See 
Footnote c. 

0 = 

°

C, 1 = 

°

Continued on the next page . . . 

Содержание TEC2103-1

Страница 1: ...a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills st...

Страница 2: ...re or malfunction of the TEC2103 1 fig1 b Figure 1 Removing the Thermostat Cover PCB Locking Tabs fig2 b Figure 2 Opening the Thermostat PCB fig3 b Figure 3 Mounting the Thermostat Base fig4 b Figure...

Страница 3: ...sformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable digital input Configura...

Страница 4: ...5 to 32 C Setback Cooling SP a g Unoccupied Cooling SP ADI 6 N2 AO CSAD 54 to 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C...

Страница 5: ...selects System Mode On at the TEC keypad the TEC ends up with the System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode...

Страница 6: ...u item MENU key to access the Main User Menu or exit the menu down arrow key to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manua...

Страница 7: ...he configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the...

Страница 8: ...scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with...

Страница 9: ...tions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection...

Страница 10: ...erature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to al...

Страница 11: ...ess YES to store the address The display now shows the temporary occupancy time prompt See the Establishing the Temporary Occupancy Time ToccTime section for instructions Note Pressing the YES and NO...

Страница 12: ...ages prompt appears in the display Press YES to enter the setting cooling stages menu 2 Using the UP DOWN arrow keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the...

Страница 13: ...e Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu...

Страница 14: ...to advance to the unoccupied heating setpoint Use the UP DOWN arrow keys to set temperature Press YES to store value and advance to next menu Press YES to change the unoccupied heating setpoint Press...

Страница 15: ...ed periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods This is the default setting Sma...

Страница 16: ...able runs are broken Locate and correct the wiring TEC2103 1 does not come online Device type is incorrect TEC2103 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed I...

Страница 17: ...50082 2 EMC Immunity Pending FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules The...

Отзывы: