background image

 

TEC2103-1 Networked Multi-Stage Thermostat Installation Instructions    

11

 

Setting the Fan Control (Fan cont) 

This parameter controls how the fan activates in 
response to a call for heating. 

When the fan is in Auto Mode (as selected on the Main 
User Menu): 

 select 

on

 to enable the thermostat to control the 

fan on a call for heating or cooling 

 select 

off

 to energize the fan on a call for cooling 

only by the thermostat. On a call for heating, the 
fan is controlled by the equipment fan limit control. 

To set the fan control while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the fan control 

prompt appears in the display. Press YES to enter 
the fan control menu. 

2.  Using the UP/DOWN arrow keys, select 

on

 or 

off

Press YES to store the selection. 

The display now shows the fan delay prompt. See the

 

Setting the Fan Delay (Fan del)

 section for 

instructions. 

Setting the Fan Delay (Fan del) 

The fan delay extends the fan operation by 
60 seconds after the call for heating or cooling has 
ended. This feature is only active when the fan is in 
the 

Auto

 mode. 

To enable the fan delay while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the fan delay 

prompt appears in the display. Press YES to enter 
the fan delay menu. 

2.  Using the UP/DOWN arrow keys, select 

on

 or 

off

Press YES to store the selection. 

The display now shows the N2 address prompt. See 
the

 Setting the N2 Address (N2 addr)

 section for 

instructions. 

Setting the N2 Address (N2 addr) 

To adjust the N2 address (adjustable from 1 to 253) 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the setting the 

N2 address prompt appears in the display. Press 
YES to set the address. 

2.  Use the UP/DOWN arrow keys to display the 

desired address. Press YES to store the address. 

The display now shows the temporary occupancy time 
prompt. See the

 Establishing the Temporary 

Occupancy Time (ToccTime)

 section for instructions. 

Note: 

Pressing the YES and NO keys 

simultaneously for 5 seconds on the user interface of 
the TEC2103-1 temporarily displays the N2 address of 
the thermostat. 

Establishing the Temporary Occupancy Time 
(ToccTime) 

The temporary occupancy is the length of time the 
occupied mode setpoints are used when the override 
function is enabled (the override function can be 
enabled from the Main User Menu 

when the 

thermostat is in unoccupied mode

 or from one of 

the digital inputs) or a temporary setpoint is entered. 
The range is adjustable from 0 to 12 hours. 

To change the temporary occupancy time while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the temporary 

occupancy time prompt appears in the display. 
Press YES to enter the temporary occupancy time 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the length 

of time the temporary occupancy setpoint should 
be in effect. Press YES to store the time. 

The display now shows the room sensor calibration 
prompt. See the

 Room Air Sensor Calibration (Cal RS)

 

section for instructions. 

Room Air Sensor Calibration (Cal RS) 

An offset can be added or subtracted to the actual 
displayed room temperature as needed. The range is 

±

5.0 F

°

 (

±

2.5 C

°

), adjustable in increments of 1 F

°

 

(0.5 C

°

). 

To change the room sensor calibration/offset while in 
the Installer Configuration Menu: 

1.  Answer NO to all prompts until the room sensor 

calibration prompt appears in the display. Press 
YES to enter the room sensor calibration menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

correction that should be applied to the sensor 
reading. Press YES to store the offset. 

The display now shows the auxiliary 
temperature/outdoor air sensor calibration prompt. 
See the

 Auxiliary Temperature/Outdoor Air Sensor 

Calibration (Cal OS)

 section for instructions. 

Содержание TEC2103-1

Страница 1: ...a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills st...

Страница 2: ...re or malfunction of the TEC2103 1 fig1 b Figure 1 Removing the Thermostat Cover PCB Locking Tabs fig2 b Figure 2 Opening the Thermostat PCB fig3 b Figure 3 Mounting the Thermostat Base fig4 b Figure...

Страница 3: ...sformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable digital input Configura...

Страница 4: ...5 to 32 C Setback Cooling SP a g Unoccupied Cooling SP ADI 6 N2 AO CSAD 54 to 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C...

Страница 5: ...selects System Mode On at the TEC keypad the TEC ends up with the System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode...

Страница 6: ...u item MENU key to access the Main User Menu or exit the menu down arrow key to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manua...

Страница 7: ...he configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the...

Страница 8: ...scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with...

Страница 9: ...tions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection...

Страница 10: ...erature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to al...

Страница 11: ...ess YES to store the address The display now shows the temporary occupancy time prompt See the Establishing the Temporary Occupancy Time ToccTime section for instructions Note Pressing the YES and NO...

Страница 12: ...ages prompt appears in the display Press YES to enter the setting cooling stages menu 2 Using the UP DOWN arrow keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the...

Страница 13: ...e Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu...

Страница 14: ...to advance to the unoccupied heating setpoint Use the UP DOWN arrow keys to set temperature Press YES to store value and advance to next menu Press YES to change the unoccupied heating setpoint Press...

Страница 15: ...ed periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods This is the default setting Sma...

Страница 16: ...able runs are broken Locate and correct the wiring TEC2103 1 does not come online Device type is incorrect TEC2103 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed I...

Страница 17: ...50082 2 EMC Immunity Pending FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules The...

Отзывы: