T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
16
Lockout
Selectable Lockout Levels for
limiting end-user keypad interaction.
Default:
0
Lockout
Level
Function
Mode
Setting
Fan
Setting
Local
Override
Occupied
Temperature
Setpoints
(0)
Access
Access
Access
Access
(1)
Access
Access
No Access
Access
(2)
No Access
No Access
Access
Access
(3)
No Access
No Access
No Access
Access
(4)
No Access
No Access
Access
No Access
(5)
No Access
No Access
No Access
No Access
Pipe No
Selectable number of pipes in the
system.
Default:
4.0 Pipes
(2.0 Pipes):
Limits the number of sequences of operation available
from 0 to 3, and enables heat/cool operation from the same output.
(4.0 Pipes):
Allows access to all sequences of operation from 0 to 5,
and enables heat/cool operation from different outputs.
CntrlTyp
Defines the control output for the
type of valves used in the
installation (T602 and T603
models).
Default:
Floating
(On/Off):
For Normally Open (N.O.) or Normally Closed (N.C.)
24 VAC two-position valves.
(Floating):
For three-wire control of 24 VAC floating valves.
SeqOpera
Determines the sequence of
operation.
Default:
1
Sequence of Operation
Default Based on
AutoMode Parameter
Setting
On
Off
(0):
Cooling Only (Off-Cool)
Cool
Cool
(1):
Heating Only (Off-Heat)
Heat
Heat
(2):
Cooling and Reheat (Off-Auto*-
Heat-Cool)
Auto
Heat
(3):
Heating and Reheat (Off-Heat)
Heat
Heat
(4):
Cool/Heat Four-Pipe (Off-Auto*-
Heat-Cool)
Auto
Heat
(5):
Cool/Heat Four-Pipe and Reheat
(Off-Auto*-Heat-Cool)
Auto
Heat
* Auto can be disabled with the
AutoMode
parameter.
Note:
Choose the selection option
(0): Cooling Only
when using a
changeover sensor to allow changeover to occur between
Cooling
Only
and
Heating Only
.
Note:
Default parameter settings are always equal to off when the
mode is equal to off.
Fan Menu
Sets the fan mode options.
Default:
4
(0):
Low-Med-High: Three-speed configuration using three fan
relays (L-M-H). The default is
High
.
(1):
Low-High: Two-speed configuration using two fan relays (L-H).
The default is
High
.
(2):
Low-Med-High-Auto: Three-speed configuration with Auto Fan
speed mode using three fan relays (L-M-H). The default is
High
.
(3):
Low-High-Auto: Two-speed configuration with Auto Fan speed
mode using two fan relays (L-H). The default is
High
.
(4):
On-Auto: One-speed configuration, (H) Auto is for Fan on
demand and On is for Fan on all the time. The default is
Auto
.
Table 4: Installer Configuration Menu (Part 3 of 7)
Parameter
Appearing
on Display
Description and Default
Selection Options