T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy 
Sensing Capability Installation Instructions

18

Unocc HT

Sets the Unoccupied heating 
setpoint value.
Default: 

62.0°F/16.5°C

Range: 

40.0°F/4.5°C

 to 

90.0°F/32.0°C

Note:

When adjusting the 

temperature, press the 

UP/

DOWN

 arrow keys to 

change the temperature in 
0.5F°/0.5C° increments; 
press and hold the 

UP/DOWN

 arrow keys 

to change the temperature 
in 5.0F°/5.0C° increments.

Unocc CL

Sets the Unoccupied cooling 
setpoint value.
Default: 

80.0°F/26.5°C

Range: 

54.0°F/12.0°C

 to

100.0°F/37.5°C

Heat max

Sets the Occupied and Unoccupied 
maximum heating setpoint values.
Default: 

90.0°F/32.0°C

Range: 

40.0°F/4.5°C

 to

90.0°F/32.0°C

Cool min

Sets the Occupied and Unoccupied 
minimum cooling setpoint values.
Default: 

54.0°F/12.0°C

Range: 

54.0°F/12.0°C

 to

100.0°F/37.5°C

Pband

Sets the proportional band used by 
the thermostat controller 
Proportional-Integral (PI) control 
loop.
Default: 

3.0F°/1.7C°

Note:

The proportional band 

default setting of 3.0F°/1.7C° 
provides satisfactory thermostat 
controller operation in most 
instances. A proportional band 
setting other than the default is 
normally used in installations where 
the location of the thermostat 
controller is problematic, leading to 
unwanted cycling. An example of a 
problematic installation is a wall-
mounted thermostat controller 
installed between the return and 
supply air feeds, that is directly 
influenced by the supply air stream.

(3):

 3.0F°/1.7C°

(4):

 4.0F°/2.2C°

(5): 

5.0F°/2.8C°

(6):

 6.0F°/3.3C°

(7):

 7.0F°/3.9C°

(8):

 8.0F°/4.4C°

(9):

 9.0F°/5.0C°

(10):

 10.0F°/5.6C°

Set type

Provides the option of temporarily 
changing the heating or cooling 
setpoint by pressing the 

UP/DOWN

 

arrow keys.
Default: 

permnent

(temporar):

 Local changes to the heating or cooling setpoints are 

temporary, and remain effective for the specified TOccTime.

(permnent):

 Local changes to the heating or cooling setpoints are 

permanently stored in the thermostat memory.

Spt Func

Determines the operation and 
usage of the local setpoint interface 
by the user.
Default: 

Dual Stp

(Attch Stp):

 Single Occupied Setpoint Adjustment. The displayed 

setpoint is the setpoint from the last action taken by the thermostat 
controller, or the setpoint currently in use. Both the heating and 
cooling setpoints are changed simultaneously, while respecting the 
minimum configured deadband. If one setpoint is desired over the 
other, use the 

MODE

 key to toggle between the two setpoints.

(Dual Stp):

 Dual Occupied Setpoint Adjustment. The displayed 

setpoint is the setpoint from the last action taken by the thermostat 
controller, or the setpoint currently in use. The heating and cooling 
setpoints can be separated individually, allowing the minimum 
configured deadband to expand. If one setpoint is desired over the 
other, use the 

MODE

 key to toggle between the two setpoints.

Table 4:  Installer Configuration Menu  (Part 5 of 7)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание T60xDFH 4 PIR Series

Страница 1: ...ge grills or stairwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infra...

Страница 2: ...the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermostat controller mounting base 5 Align the thermostat contr...

Страница 3: ...mperature readings 3 Reinsert the screw terminal blocks onto the PCB Note If multiple wires are inserted into the terminals be sure to properly twist the wires together prior to inserting them into th...

Страница 4: ...Fan H Fan H Fan H Fan On High 2 Fan M Fan M Fan M Fan On Medium 3 Fan L Fan L Fan L Fan On Low 4 24 V Hot 24 V Hot 24 V Hot 24 VAC from Transformer 5 24 V Com 24 V Com 24 V Com 24 VAC Common from Tran...

Страница 5: ...Alarm Voltage Free Contact Remote NSB Motion Window OR Same 24 VAC Power Source for Auxiliary Output 24 VAC Maximum Separate 24 VAC Power Source for Auxiliary Output 24 VAC Maximum BO5 Aux BO5 Aux 24...

Страница 6: ...Pipe Applications Four Pipe Applications FIG T6023dfh3ooc 24 V Com 24 V Hot or 24 V Com 24 V Hot Cooling Valve or Heating Valve or Figure 8 Wiring T602DFH 4 and T603DFH 4 Thermostat Controllers for F...

Страница 7: ...perature scale to either Celsius or Fahrenheit and allow access to the Installer Configuration Menu See the Configuring the T60xDFH 4 and T60xDFH 4 PIR Series Thermostat Controller section Use the UP...

Страница 8: ...ehumidification operation If the thermostat controller is in Cooling demand the chilled water valve opens to 100 the thermostat controller stages Heating to maintain the room temperature at the Coolin...

Страница 9: ...PIR sensing device used If movements are detected by the PIR sensor and the door is closed the room is considered occupied The thermostat controller switches back to Stand By mode only if the door sw...

Страница 10: ...nu begins press and release the center key to scroll through the parameters listed in Table 4 3 When the desired parameter is displayed use the UP DOWN arrow keys to choose the desired selection optio...

Страница 11: ...eration in Four Pipe Applications Selection Option Control Curve Terminal Numbers Used See Table 1 and Figure 5 On Off Control Floating Control Proportional 0 to 10 VDC Control 0 Cooling Only See Figu...

Страница 12: ...16 Cooling with Reheat Two or Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Fl...

Страница 13: ...ng Figure 20 This operation applies to the Occupied mode when the fan is set to Auto Figure 19 Heating Cooling with Reheat Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Set...

Страница 14: ...at controller remains in the Occupied mode if the contact is open until the TOccTime expires Advanced PIR occupancy functions using a Normally Open N O or Normally Closed N C remote PIR motion sensor...

Страница 15: ...an input COC NH Changeover Contact Normally Heat A dry contact input is used to signal seasonal hot cold water changeover The contact closes when cold water is present Valid only for two pipe systems...

Страница 16: ...sequence of operation Default 1 Sequence of Operation Default Based on AutoMode Parameter Setting On Off 0 Cooling Only Off Cool Cool Cool 1 Heating Only Off Heat Heat Heat 2 Cooling and Reheat Off Au...

Страница 17: ...ive Range 0 5 to 24 0 hrs adjustable in 0 5 hour increments Unocc TM Sets the Unoccupied timer value PIR models Default 0 0 hours Time delay between the moment the thermostat controller toggled to Sta...

Страница 18: ...d between the return and supply air feeds that is directly influenced by the supply air stream 3 3 0F 1 7C 4 4 0F 2 2C 5 5 0F 2 8C 6 6 0F 3 3C 7 7 0F 3 9C 8 8 0F 4 4C 9 9 0F 5 0C 10 10 0F 5 6C Set typ...

Страница 19: ...s the desired humidity sensor calibration offset The offset can be added to or subtracted from the actual displayed room humidity T603 and T605 models This parameter can be used only if the dehumidifi...

Страница 20: ...perature error from the setpoint FL time Sets the maximum actuator stroke timing floating CntrlTyp T602 and T603 models Default 1 5 min Range 0 5 to 9 0 min adjustable in 0 5 minute increments Cph Set...

Страница 21: ...at Controllers with Dehumidification and Occupancy Sensing Capability Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals 4 and 5 at 24 VAC Nominal Class 2 or Safety Extra Low Voltage...

Страница 22: ...2 2 No 24 Temperature Indicating and Regulating Equipment Industry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and o...

Отзывы: