background image

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy 
Sensing Capability Installation Instructions

10

When the local PIR occupancy routine is running at the 
thermostat controller, the zone never drifts into 
Unoccupied mode when the Unoccupied timer is set to 
its factory default value of 0.0 hours.

Refer to the 

T60xDFH-4 and T60xDFH-4+PIR Series 

Thermostat Controllers with Dehumidification and 
Occupancy Sensing Capability Application Note 
(LIT-12011569)

 for additional application scenarios 

using various combinations of occupancy levels and 
door switches.

Configuring the T60xDFH-4 and 
T60xDFH-4+PIR Series Thermostat Controller

The T60x Series Thermostat Controller comes from the 
factory with default settings for all configurable 
parameters. The default settings are shown in Table 4. 
To reconfigure the parameters via the thermostat 
controller, follow the steps in this section.

1.

To access the Installer Configuration Menu, press 
and hold the center key for approximately 
8 seconds.

Note:

If the 

Password

 parameter is configured, 

Password 0 appears on the thermostat controller 
display indicating that the configured password is 
required to proceed. Use the 

UP/DOWN

 arrow keys to 

indicate the configured password, then press the 

MODE

 key to proceed through the Installer 

Configuration Menu parameters.

2.

Once the Installer Configuration Menu begins, 
press and release the center key to scroll through 
the parameters listed in Table 4.

3.

When the desired parameter is displayed, use the 

UP/DOWN

 arrow keys to choose the desired 

selection option.

4.

Press and release the center key to continue 
scrolling through the parameters.

Note:

Pressing the 

FAN

 key during configuration 

restarts the list of displayed parameters at the first 
parameter listed in Table 4.

When the thermostat controller is in the Installer 
Configuration Menu and left unattended for 
approximately 8 seconds, the thermostat controller 
reverts to the Status Display Menu.

Configuring Inputs BI1, BI2, and UI3

When BI1 and BI2 are configured for an alarm 
condition, an alarm condition is displayed locally when 
the input is closed. An alarm message is included on 
the scrolling Status Display Menu and when the 
message is displayed, the backlight momentarily 
lights up.

The UI3 input provides changeover of hot/cold water 
switching or supply air temperature monitoring at the 
thermostat controller.

Each input can be configured to the selection options 
included in Table 4.

Configuring the Sequence of Operation 
(SeqOpera)

Choose the appropriate sequence of operation using 
Table 2 or Table 3. The modes presented are user-
dependent on the sequence of operation selected. For 
two-pipe applications using a changeover sensor, 
choose the selection option 

(0): Cooling Only

Changeover occurs between 

Cooling Only

 and 

Heating Only

. See Figure 14 through Figure 19 for 

sequence of operation examples.     

Figure 13: Unoccupied Timer Set to 0 Hours and Stand-By Timer Set to 2 Hours

Содержание T60xDFH 4 PIR Series

Страница 1: ...ge grills or stairwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infra...

Страница 2: ...the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermostat controller mounting base 5 Align the thermostat contr...

Страница 3: ...mperature readings 3 Reinsert the screw terminal blocks onto the PCB Note If multiple wires are inserted into the terminals be sure to properly twist the wires together prior to inserting them into th...

Страница 4: ...Fan H Fan H Fan H Fan On High 2 Fan M Fan M Fan M Fan On Medium 3 Fan L Fan L Fan L Fan On Low 4 24 V Hot 24 V Hot 24 V Hot 24 VAC from Transformer 5 24 V Com 24 V Com 24 V Com 24 VAC Common from Tran...

Страница 5: ...Alarm Voltage Free Contact Remote NSB Motion Window OR Same 24 VAC Power Source for Auxiliary Output 24 VAC Maximum Separate 24 VAC Power Source for Auxiliary Output 24 VAC Maximum BO5 Aux BO5 Aux 24...

Страница 6: ...Pipe Applications Four Pipe Applications FIG T6023dfh3ooc 24 V Com 24 V Hot or 24 V Com 24 V Hot Cooling Valve or Heating Valve or Figure 8 Wiring T602DFH 4 and T603DFH 4 Thermostat Controllers for F...

Страница 7: ...perature scale to either Celsius or Fahrenheit and allow access to the Installer Configuration Menu See the Configuring the T60xDFH 4 and T60xDFH 4 PIR Series Thermostat Controller section Use the UP...

Страница 8: ...ehumidification operation If the thermostat controller is in Cooling demand the chilled water valve opens to 100 the thermostat controller stages Heating to maintain the room temperature at the Coolin...

Страница 9: ...PIR sensing device used If movements are detected by the PIR sensor and the door is closed the room is considered occupied The thermostat controller switches back to Stand By mode only if the door sw...

Страница 10: ...nu begins press and release the center key to scroll through the parameters listed in Table 4 3 When the desired parameter is displayed use the UP DOWN arrow keys to choose the desired selection optio...

Страница 11: ...eration in Four Pipe Applications Selection Option Control Curve Terminal Numbers Used See Table 1 and Figure 5 On Off Control Floating Control Proportional 0 to 10 VDC Control 0 Cooling Only See Figu...

Страница 12: ...16 Cooling with Reheat Two or Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Fl...

Страница 13: ...ng Figure 20 This operation applies to the Occupied mode when the fan is set to Auto Figure 19 Heating Cooling with Reheat Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Set...

Страница 14: ...at controller remains in the Occupied mode if the contact is open until the TOccTime expires Advanced PIR occupancy functions using a Normally Open N O or Normally Closed N C remote PIR motion sensor...

Страница 15: ...an input COC NH Changeover Contact Normally Heat A dry contact input is used to signal seasonal hot cold water changeover The contact closes when cold water is present Valid only for two pipe systems...

Страница 16: ...sequence of operation Default 1 Sequence of Operation Default Based on AutoMode Parameter Setting On Off 0 Cooling Only Off Cool Cool Cool 1 Heating Only Off Heat Heat Heat 2 Cooling and Reheat Off Au...

Страница 17: ...ive Range 0 5 to 24 0 hrs adjustable in 0 5 hour increments Unocc TM Sets the Unoccupied timer value PIR models Default 0 0 hours Time delay between the moment the thermostat controller toggled to Sta...

Страница 18: ...d between the return and supply air feeds that is directly influenced by the supply air stream 3 3 0F 1 7C 4 4 0F 2 2C 5 5 0F 2 8C 6 6 0F 3 3C 7 7 0F 3 9C 8 8 0F 4 4C 9 9 0F 5 0C 10 10 0F 5 6C Set typ...

Страница 19: ...s the desired humidity sensor calibration offset The offset can be added to or subtracted from the actual displayed room humidity T603 and T605 models This parameter can be used only if the dehumidifi...

Страница 20: ...perature error from the setpoint FL time Sets the maximum actuator stroke timing floating CntrlTyp T602 and T603 models Default 1 5 min Range 0 5 to 9 0 min adjustable in 0 5 minute increments Cph Set...

Страница 21: ...at Controllers with Dehumidification and Occupancy Sensing Capability Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals 4 and 5 at 24 VAC Nominal Class 2 or Safety Extra Low Voltage...

Страница 22: ...2 2 No 24 Temperature Indicating and Regulating Equipment Industry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and o...

Отзывы: