background image

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy 
Sensing Capability Installation Instructions 

7

Setup and Adjustments

Thermostat Controller Operation Overview 

Thermostat Controller User Interface Keys

The T60x Series Thermostat Controller user interface 
consists of five keys on the front cover (as illustrated in 
Figure 10). The function of each key is as follows:

Use  the 

MODE

 key to toggle among the system 

modes available, as defined by selecting the 
appropriate operation sequence in the Installer 
Configuration Menu (for example, Off, Heat, Cool, 
Auto).

Note:

 If the automatic changeover function (auto 

function) is enabled in the sequence of operation 
(

SeqOpera

), then automatic changeover heating 

or cooling demand overrides the mode when 

MODE

 = 

off

.

Use  the 

FAN

 key to toggle among the fan modes 

available, as defined by selecting the appropriate 
fan menu options defined in the Installer 
Configuration Menu (for example, Low, Med, High, 
Auto).

Use the 

°C/°F

 key to change the temperature scale 

to either Celsius or Fahrenheit and allow access to 
the Installer Configuration Menu. See the 

Configuring the T60xDFH-4 and 
T60xDFH-4+PIR Series Thermostat Controller

 

section.

Use  the 

UP/DOWN

 arrow keys to change the 

configuration parameters and to activate a setpoint 
adjustment.

Backlit LCD

The T60x Series Thermostat Controllers include a 
2-line, 8-character backlit display. Low-level 
backlighting is present during normal operation, and it 
brightens when any user interface key is pressed. The 
backlight returns to low level when the thermostat 
controller is left unattended for 45 seconds.

LEDs

Three LEDs are included to indicate the fan status, call 
for heat, or call for cooling:

The fan LED 

 is on when the fan is on.

The heat LED 

 is on when heating is on.

The cool LED 

 is on when cooling is on.

Integrated PIR Sensor – T60xDFH-4+PIR 
Thermostat Controllers

The integrated PIR sensor allows for automatic 
switching between fully adjustable Occupied and 
Stand-By temperature setpoints without user 
interaction. This feature generates incremental energy 
savings during scheduled occupied periods while the 
space is unoccupied.

Figure 10: Front Cover of Thermostat Controller (T60xDFH-4+PIR Model Shown)

Содержание T60xDFH 4 PIR Series

Страница 1: ...ge grills or stairwells and from behind doors away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference For integrated Passive Infra...

Страница 2: ...the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the hole in the thermostat controller mounting base 5 Align the thermostat contr...

Страница 3: ...mperature readings 3 Reinsert the screw terminal blocks onto the PCB Note If multiple wires are inserted into the terminals be sure to properly twist the wires together prior to inserting them into th...

Страница 4: ...Fan H Fan H Fan H Fan On High 2 Fan M Fan M Fan M Fan On Medium 3 Fan L Fan L Fan L Fan On Low 4 24 V Hot 24 V Hot 24 V Hot 24 VAC from Transformer 5 24 V Com 24 V Com 24 V Com 24 VAC Common from Tran...

Страница 5: ...Alarm Voltage Free Contact Remote NSB Motion Window OR Same 24 VAC Power Source for Auxiliary Output 24 VAC Maximum Separate 24 VAC Power Source for Auxiliary Output 24 VAC Maximum BO5 Aux BO5 Aux 24...

Страница 6: ...Pipe Applications Four Pipe Applications FIG T6023dfh3ooc 24 V Com 24 V Hot or 24 V Com 24 V Hot Cooling Valve or Heating Valve or Figure 8 Wiring T602DFH 4 and T603DFH 4 Thermostat Controllers for F...

Страница 7: ...perature scale to either Celsius or Fahrenheit and allow access to the Installer Configuration Menu See the Configuring the T60xDFH 4 and T60xDFH 4 PIR Series Thermostat Controller section Use the UP...

Страница 8: ...ehumidification operation If the thermostat controller is in Cooling demand the chilled water valve opens to 100 the thermostat controller stages Heating to maintain the room temperature at the Coolin...

Страница 9: ...PIR sensing device used If movements are detected by the PIR sensor and the door is closed the room is considered occupied The thermostat controller switches back to Stand By mode only if the door sw...

Страница 10: ...nu begins press and release the center key to scroll through the parameters listed in Table 4 3 When the desired parameter is displayed use the UP DOWN arrow keys to choose the desired selection optio...

Страница 11: ...eration in Four Pipe Applications Selection Option Control Curve Terminal Numbers Used See Table 1 and Figure 5 On Off Control Floating Control Proportional 0 to 10 VDC Control 0 Cooling Only See Figu...

Страница 12: ...16 Cooling with Reheat Two or Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG clng_wth_rht Deadband Reheat On Off Fl...

Страница 13: ...ng Figure 20 This operation applies to the Occupied mode when the fan is set to Auto Figure 19 Heating Cooling with Reheat Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Set...

Страница 14: ...at controller remains in the Occupied mode if the contact is open until the TOccTime expires Advanced PIR occupancy functions using a Normally Open N O or Normally Closed N C remote PIR motion sensor...

Страница 15: ...an input COC NH Changeover Contact Normally Heat A dry contact input is used to signal seasonal hot cold water changeover The contact closes when cold water is present Valid only for two pipe systems...

Страница 16: ...sequence of operation Default 1 Sequence of Operation Default Based on AutoMode Parameter Setting On Off 0 Cooling Only Off Cool Cool Cool 1 Heating Only Off Heat Heat Heat 2 Cooling and Reheat Off Au...

Страница 17: ...ive Range 0 5 to 24 0 hrs adjustable in 0 5 hour increments Unocc TM Sets the Unoccupied timer value PIR models Default 0 0 hours Time delay between the moment the thermostat controller toggled to Sta...

Страница 18: ...d between the return and supply air feeds that is directly influenced by the supply air stream 3 3 0F 1 7C 4 4 0F 2 2C 5 5 0F 2 8C 6 6 0F 3 3C 7 7 0F 3 9C 8 8 0F 4 4C 9 9 0F 5 0C 10 10 0F 5 6C Set typ...

Страница 19: ...s the desired humidity sensor calibration offset The offset can be added to or subtracted from the actual displayed room humidity T603 and T605 models This parameter can be used only if the dehumidifi...

Страница 20: ...perature error from the setpoint FL time Sets the maximum actuator stroke timing floating CntrlTyp T602 and T603 models Default 1 5 min Range 0 5 to 9 0 min adjustable in 0 5 minute increments Cph Set...

Страница 21: ...at Controllers with Dehumidification and Occupancy Sensing Capability Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals 4 and 5 at 24 VAC Nominal Class 2 or Safety Extra Low Voltage...

Страница 22: ...2 2 No 24 Temperature Indicating and Regulating Equipment Industry Canada ICES 003 Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and o...

Отзывы: