4    

System 350

 

A350A/B Electronic Temperature Control Product/Technical Bulletin

D

imensions

Mounting Slots

for No. 6 Screws

DIN Rail

Mount

Conduit

Hole

(75)

3/16 (4)

1/2 (13)

2 15/16

1 9/16

(40)

2 3/8 

(61)

1 3/16 

(31)

7/8

(22)

7/16 

(11)

9 3/4 (248)

Sensor

1/4 (6)

7/8 

(22)

  3 (76)

2 3/8 

(61)

5 (127)

4 (102)

Figure 3: A350A/B Control Dimensions, in. (mm)

I

nstallation and Wiring

The A350A/B Temperature Control is housed in a
compact NEMA 1 plastic enclosure designed for
standard 35 mm DIN rail mounting. The A350A/B is not
position sensitive but should be mounted for convenient
wiring and adjustment. Four key-slot mounting holes on
the back of the control case are provided for surface
mounting. Add-on modules must plug into the right side
of the A350A/B control.
Note: When mounting the System 350 modules to rigid

conduit, attach the hub to the conduit before
securing the hub to the control enclosure.

!

 WARNING:

Risk of Electrical Shock.

Disconnect power supply before
wiring connections are made to
avoid electrical shock or damage
to equipment.

All wiring must conform to the National Electrical
Code and/or local regulations.

Note:

For maximum electrical rating of control, see
label inside the control cover or 

Specifications

section. Use copper conductors only.

Consult the typical wiring diagrams (Figures 4 and 5)
for proper wiring and terminal designations.

A350A/B

D350

S350A

Sensor

Load

Load

L

L

 24
VAC

1

1

2

2

24V

COM

VDC

SEN

Note:  If sensor is mounted less than 50 ft
          (15.2 m) from the A350A/B,
          shielded cable is not required.

Figure 4: Typical Wiring Diagram for A350A/B

Powered by an External 10 VA Transformer

Содержание System 350 A350A

Страница 1: ...res and Benefits Modular Design Enables stage display and power modules to be purchased and installed as needed Plug together Connectors and 35 mm DIN Rail Mounting Eliminates wiring between modules and reduces installation costs Two Standard Models Cover Wide Setpoint Ranges 30 to 130 F 34 to 55 C or 90 to 250 F 32 to 121 C Reduces inventory by encompassing temperature ranges required to support ...

Страница 2: ...rvisory systems that warn of control failure Setpoint Adjustment Setpoint is defined as the temperature at which the A350A B s relay de energizes Use the Setpoint Dial on the front of the A350A B to adjust setpoint See Figure 2 Differential Adjustment Differential is defined as the change in sensor temperature between energization and de energization of the relay Adjustment of the A350A B differen...

Страница 3: ... power and sensor input from the A350 control S350C Slave Stage Modules perform switching functions based upon the A350 s sensor information Setpoint and differential are selected independently at the S350C For more information on these modules refer to the System 350 TM S350C Temperature Slave Stage Module Product Technical Bulletin LIT 930084 S350P Proportional Stage Modules S350P Proportional S...

Страница 4: ...into the right side of the A350A B control Note When mounting the System 350 modules to rigid conduit attach the hub to the conduit before securing the hub to the control enclosure WARNING Risk of Electrical Shock Disconnect power supply before wiring connections are made to avoid electrical shock or damage to equipment All wiring must conform to the National Electrical Code and or local regulatio...

Страница 5: ...with A350 Series Controls See Tables 3 and 6 The sensor must be connected to the COM and SEN terminals on the four position terminal strip located at the top left of the printed circuit board Refer to Figures 2 4 and 5 The sensors are not polarity sensitive The sensor must be mounted so that it can accurately sense the temperature of the controlled medium Table 3 Sensors Included With A350A B Cont...

Страница 6: ... The A350A B setpoint is factory calibrated at midscale to a tolerance of 1F 0 6C Setpoint tolerance at the extreme ends of the setpoint ranges in relation to the printed scale can be 3F 1 7C The D350 Display Module is unaffected by this tolerance shift Use the D350 for the most accurate setpoint selection Checkout Procedure Follow this procedure to verify that the A350A B is connected and functio...

Страница 7: ...etpoint Dial Setting Heating On Closed Ts Sp Diff Heating Off Open Ts Sp Cooling On Closed Ts Sp Diff Cooling Off Open Ts Sp Ts is sensed temperature and Sp is setpoint temperature Repairs and Replacement Do not make field repairs or perform calibration Replacement controls and A99B Temperature Sensors are available through the nearest Johnson Controls representative See Tables 5 and 6 for orderin...

Страница 8: ...emperature Control Supply Voltage Y350R Power Module Input 120 240 VAC 50 60 Hz Output 24 VDC unfiltered 10 VA Class 2 External Source 24 VAC 50 60 Hz Class 2 20 30 VAC Note Only one supply voltage source may be used Power Consumption 1 4 VA Ambient Temperatures Operating 30 to 150 F 34 to 66 C Shipping 40 to 185 F 40 to 85 C Humidity 0 to 95 RH non condensing maximum dew point 85 F 29 C Setpoint ...