background image

System 350 A350A/B Electronic Temperature Control Product/Technical Bulletin

    3

A

dd-On Modules

The S350 Stage Modules, D350 Digital Temperature
Display Module, and Y350R Power Module connect
together and plug into the A350 via a connector on its
right side. The maximum number of add-on modules is
listed in Table 1.

Table 1: Maximum Number of S350 Stage
Modules per A350A/A350B

Power
Source

Number

of S350A

or S350C

Modules

Allowed

Number

of S350A

or S350C

Modules

(with

1 S350P)

Allowed

Number of

S350A or

S350C

Modules

(with

2 S350P)

Allowed

Y350R

9

6

4

External
Class 2
Transformer

9

8

7

Note:

For each S350P added, the number of S350A
or S350C Stage Modules that can be used
with a Y350R decreases by two. If an external
transformer is used, the number of S350A and
S350C Stage Modules used decreases by
one for each additional S350P.

S350A On-Off Stage Modules

S350A On-Off Stage Modules receive power, setpoint,
and sensor input from the A350 control. S350A Stage
Modules perform switching functions based upon the
A350’s setpoint and sensor information, with the offset
and differential selected at the S350A.

For more information on these modules, refer to the

System 350 S350 Temperature, S351 Humidity, and
S352 Pressure On/Off Stage Modules
Product/Technical Bulletin (LIT-930080).

S350C Slave Stage Modules

S350C Slave Stage Modules receive power and
sensor input from the A350 control. S350C Slave
Stage Modules perform switching functions based
upon the A350’s sensor information. (Setpoint and
differential are selected independently at the S350C.)
For more information on these modules, refer to the

System 350

TM

 S350C Temperature Slave Stage

Module Product/Technical Bulletin (LIT-930084).

S350P Proportional Stage Modules

S350P Proportional Stage Modules receive power,
setpoint, and sensor input from the A350 control.
The S350P responds with an analog 0-10 VDC and
0-20 mA output signal. This is based upon the A350’s
setpoint and sensor information, with the offset,
throttling range, and minimum output selected at the
S350P.

For more information on these modules, refer to the

System 350

TM

 S350P Proportional Plus Integral

Temperature Stage Module Product/Technical Bulletin
(LIT-930086).

D350 Temperature Sensor/Setpoint
Display Module

The D350 receives power, sensor, and setpoint
information from the A350. A 3-digit Liquid Crystal
Diode (LCD) gives continuous read-out of the sensed
temperature. Pushing the PRESS FOR SETPOINT
button on the front of the D350 causes the setpoint of
the adjoining A350 to be displayed.

Y350R Power Module

The Y350R provides a convenient method of powering
System 350 modules from a 120 or 240 VAC power
source. The Y350R supplies power to the modules.
See Figure 5 for a typical wiring diagram where a
Y350R is used to power the A350.

For more information on this module, refer to

System 350

TM

 Y350R Power Module

Product/Technical Bulletin (LIT-930090)

.

Содержание System 350 A350A

Страница 1: ...res and Benefits Modular Design Enables stage display and power modules to be purchased and installed as needed Plug together Connectors and 35 mm DIN Rail Mounting Eliminates wiring between modules and reduces installation costs Two Standard Models Cover Wide Setpoint Ranges 30 to 130 F 34 to 55 C or 90 to 250 F 32 to 121 C Reduces inventory by encompassing temperature ranges required to support ...

Страница 2: ...rvisory systems that warn of control failure Setpoint Adjustment Setpoint is defined as the temperature at which the A350A B s relay de energizes Use the Setpoint Dial on the front of the A350A B to adjust setpoint See Figure 2 Differential Adjustment Differential is defined as the change in sensor temperature between energization and de energization of the relay Adjustment of the A350A B differen...

Страница 3: ... power and sensor input from the A350 control S350C Slave Stage Modules perform switching functions based upon the A350 s sensor information Setpoint and differential are selected independently at the S350C For more information on these modules refer to the System 350 TM S350C Temperature Slave Stage Module Product Technical Bulletin LIT 930084 S350P Proportional Stage Modules S350P Proportional S...

Страница 4: ...into the right side of the A350A B control Note When mounting the System 350 modules to rigid conduit attach the hub to the conduit before securing the hub to the control enclosure WARNING Risk of Electrical Shock Disconnect power supply before wiring connections are made to avoid electrical shock or damage to equipment All wiring must conform to the National Electrical Code and or local regulatio...

Страница 5: ...with A350 Series Controls See Tables 3 and 6 The sensor must be connected to the COM and SEN terminals on the four position terminal strip located at the top left of the printed circuit board Refer to Figures 2 4 and 5 The sensors are not polarity sensitive The sensor must be mounted so that it can accurately sense the temperature of the controlled medium Table 3 Sensors Included With A350A B Cont...

Страница 6: ... The A350A B setpoint is factory calibrated at midscale to a tolerance of 1F 0 6C Setpoint tolerance at the extreme ends of the setpoint ranges in relation to the printed scale can be 3F 1 7C The D350 Display Module is unaffected by this tolerance shift Use the D350 for the most accurate setpoint selection Checkout Procedure Follow this procedure to verify that the A350A B is connected and functio...

Страница 7: ...etpoint Dial Setting Heating On Closed Ts Sp Diff Heating Off Open Ts Sp Cooling On Closed Ts Sp Diff Cooling Off Open Ts Sp Ts is sensed temperature and Sp is setpoint temperature Repairs and Replacement Do not make field repairs or perform calibration Replacement controls and A99B Temperature Sensors are available through the nearest Johnson Controls representative See Tables 5 and 6 for orderin...

Страница 8: ...emperature Control Supply Voltage Y350R Power Module Input 120 240 VAC 50 60 Hz Output 24 VDC unfiltered 10 VA Class 2 External Source 24 VAC 50 60 Hz Class 2 20 30 VAC Note Only one supply voltage source may be used Power Consumption 1 4 VA Ambient Temperatures Operating 30 to 150 F 34 to 66 C Shipping 40 to 185 F 40 to 85 C Humidity 0 to 95 RH non condensing maximum dew point 85 F 29 C Setpoint ...

Отзывы: